← Utah

Tap water quality report

Bay View Heights Inc

EPA monitoring tested this supplier for 75 contaminants and detected 9. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

75
contaminants tested
9
detected
450
people served
21
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Dane

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

21
health-based violations
53
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2022-12-01 → 2022-12-31
MCL Health-based Resolved 2022-12-01 → 2022-12-31
MCL Health-based Resolved 2022-12-01 → 2022-12-31
MCL Health-based Resolved 2022-12-01 → 2022-12-31
MCL Health-based Resolved 2022-12-01 → 2022-12-31
MCL Health-based Resolved 1994-03-01 → 1994-03-31
MCL Health-based Resolved 1994-03-01 → 1994-03-31
MCL Health-based Resolved 1994-03-01 → 1994-03-31
MCL Health-based Resolved 1994-03-01 → 1994-03-31
MCL Health-based Resolved 1994-03-01 → 1994-03-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
477.2 µg/L 37%
of the EPA limit 1300 µg/L
worst single sample: 697 µg/L
15/15 SYR4 2012–2018
Lead
0.00066 mg/L 4.4%
of the EPA limit 0.0150 mg/L
13/13 LCR 2024
Nitrate
2800 µg/L 28%
of the EPA limit 10000 µg/L
10/20 SYR4 2013–2017
Lead
2.74 µg/L 18%
of the EPA limit 15 µg/L
worst single sample: 2.8 µg/L
7/15 SYR4 2012–2018
Barium
46.575 µg/L 2.3%
of the EPA limit 2000 µg/L
worst single sample: 47.1 µg/L
6/6 SYR4 2012–2018
Fluoride
180 µg/L 4.5%
of the EPA limit 4000 µg/L
5/6 SYR4 2012–2018
Nitrate-Nitrite
3600 µg/L 36%
of the EPA limit 10000 µg/L
worst single sample: 3900 µg/L
5/12 SYR4 2012–2019
Gross Alpha, Excl. Radon And U
3.41 pCi/L 23%
of the EPA limit 15 pCi/L
worst single sample: 3.5 pCi/L
2/2 SYR4 2012–2015
Combined Radium (-226 And -228)
1.12 pCi/L 22%
of the EPA limit 5 pCi/L
1/1 SYR4 2012
66 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalArsenicAsbestosAtrazineBhc-GammaBenzeneBeryllium, TotalBromodichloromethaneBromoformChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneChloroformChromiumDichloromethaneDalaponDibromoacetic AcidDibromochloromethaneDichloroacetic AcidDinosebDiquatEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNitriteOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTTHMTetrachloroethyleneThallium, TotalTolueneTotal Haloacetic Acids (HAA5)Total Polychlorinated Biphenyls (PCB)ToxapheneTrichloroacetic AcidTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Frequently asked questions about Bay View Heights Inc

Is Bay View Heights Inc tap water safe to drink?

EPA monitoring detected 9 contaminants in Bay View Heights Inc's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Bay View Heights Inc's water?

EPA monitoring detected Copper, Lead, Nitrate, Lead, Barium, and others. The full list with the level and data source for each is above.

How many people does Bay View Heights Inc serve?

Bay View Heights Inc reports serving 450 people in Utah, per its EPA record.

Has Bay View Heights Inc had any water quality violations?

The EPA has 53 violations on file for Bay View Heights Inc, of which 21 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.