Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MON | Monitoring | Resolved | 2020-10-01 → 2020-10-31 |
| MON | Monitoring | Resolved | 2020-10-01 → 2020-10-31 |
| MON | Monitoring | Resolved | 2020-10-01 → 2020-10-31 |
| MON | Monitoring | Resolved | 2020-10-01 → 2020-10-31 |
| MR | Monitoring | Resolved | 1994-04-01 → 1994-04-30 |
| MR | Monitoring | Resolved | 1994-04-01 → 1994-04-30 |
| MR | Monitoring | Resolved | 1994-04-01 → 1994-04-30 |
| MR | Monitoring | Resolved | 1994-04-01 → 1994-04-30 |
PFAS detected
| Contaminant | Max | Detection rate | Period |
|---|---|---|---|
| PFHXS | 0.0036 µg/L | 2/8 | 2025 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 174 µg/L 13% of the EPA limit 1300 µg/L
worst single sample: 450 µg/L | 273/278 | SYR4 | 2014–2019 |
| Lead | 21.45 µg/L 143% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 77 µg/L | 272/278 | SYR4 | 2014–2019 |
| Fluoride | 1140 µg/L 28% of the EPA limit 4000 µg/L
worst single sample: 2700 µg/L | 102/200 | SYR4 | 2012–2019 |
| Nitrate | 5910 µg/L 59% of the EPA limit 10000 µg/L
worst single sample: 6300 µg/L | 34/70 | SYR4 | 2012–2019 |
| Lead | 0.0042 mg/L 28% of the EPA limit 0.0150 mg/L | 21/21 | LCR | 2023 |
| TTHM | 13.0295 µg/L 16% of the EPA limit 80 µg/L
worst single sample: 20.96 µg/L | 18/18 | SYR4 | 2012–2019 |
| Chloroform | 10.95 µg/L No EPA limit set
worst single sample: 18 µg/L | 16/45 | SYR4 | 2012–2019 |
| Bromodichloromethane | 2.18 µg/L No EPA limit set
worst single sample: 2.3 µg/L | 13/45 | SYR4 | 2012–2019 |
| Dibromochloromethane | 1.98 µg/L No EPA limit set
worst single sample: 2.2 µg/L | 12/45 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 2.3745 µg/L 4% of the EPA limit 60 µg/L
worst single sample: 2.49 µg/L | 12/16 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 1.396 µg/L No EPA limit set
worst single sample: 1.7 µg/L | 9/16 | SYR4 | 2012–2019 |
| Barium | 38.9 µg/L 1.9% of the EPA limit 2000 µg/L
worst single sample: 41 µg/L | 8/8 | SYR4 | 2014–2017 |
| Bromoform | 1.24 µg/L No EPA limit set
worst single sample: 1.3 µg/L | 7/45 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 1.28 µg/L No EPA limit set
worst single sample: 1.4 µg/L | 7/16 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 4.5925 pCi/L 92% of the EPA limit 5 pCi/L
worst single sample: 4.64 pCi/L | 6/6 | SYR4 | 2014–2017 |
| Gross Alpha, Excl. Radon And U | 8.422 pCi/L 56% of the EPA limit 15 pCi/L
worst single sample: 9.66 pCi/L | 5/5 | SYR4 | 2014–2017 |
| Nitrate-Nitrite | 4970 µg/L 50% of the EPA limit 10000 µg/L
worst single sample: 5000 µg/L | 3/8 | SYR4 | 2014–2017 |
| Thallium, Total | 0.2480 µg/L 12% of the EPA limit 2 µg/L
worst single sample: 0.2500 µg/L | 3/8 | SYR4 | 2014–2017 |
| Chromium | 0.8700 µg/L 0.9% of the EPA limit 100 µg/L | 1/8 | SYR4 | 2014–2017 |
| Monobromoacetic Acid | 0.4200 µg/L No EPA limit set | 1/16 | SYR4 | 2012–2019 |
83 contaminants tested, none detected
Utility contact
Frequently asked questions about Stoughton Waterworks
Is Stoughton Waterworks tap water safe to drink?
EPA monitoring detected 21 contaminants in Stoughton Waterworks's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Stoughton Waterworks's water?
EPA monitoring detected Copper, Lead, Fluoride, Nitrate, Lead, and others. The full list with the level and data source for each is above.
How many people does Stoughton Waterworks serve?
Stoughton Waterworks reports serving 13,078 people in Wisconsin, per its EPA record.
Has Stoughton Waterworks had any water quality violations?
The EPA has 8 violations on file for Stoughton Waterworks, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.