Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Archived | 1993-06-01 → 1993-06-30 |
| MR | Monitoring | Archived | 2019-04-01 → 2019-06-30 |
| MR | Monitoring | Archived | 2019-04-01 → 2019-06-30 |
| MR | Monitoring | Archived | 2019-04-01 → 2019-06-30 |
| MR | Monitoring | Archived | 2019-04-01 → 2019-06-30 |
| MR | Monitoring | Archived | 2019-04-01 → 2019-06-30 |
| MR | Monitoring | Resolved | 2018-10-01 → 2018-12-31 |
| MR | Monitoring | Resolved | 2018-10-01 → 2018-12-31 |
| MR | Monitoring | Resolved | 2018-10-01 → 2018-12-31 |
| MR | Monitoring | Resolved | 2018-10-01 → 2018-12-31 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| TTHM | 68.353 µg/L 85% of the EPA limit 80 µg/L
worst single sample: 91.39 µg/L | 275/275 | SYR4 | 2012–2019 |
| Chloroform | 60.98 µg/L No EPA limit set
worst single sample: 81.09 µg/L | 267/268 | SYR4 | 2012–2019 |
| Bromodichloromethane | 7.598 µg/L No EPA limit set
worst single sample: 8.63 µg/L | 265/268 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 51.01 µg/L 85% of the EPA limit 60 µg/L
worst single sample: 63.39 µg/L | 256/256 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 21.55 µg/L No EPA limit set
worst single sample: 30.6 µg/L | 251/251 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 33.29 µg/L No EPA limit set
worst single sample: 37.9 µg/L | 248/248 | SYR4 | 2012–2019 |
| Dibromochloromethane | 7.828 µg/L No EPA limit set
worst single sample: 14.1137 µg/L | 185/267 | SYR4 | 2012–2019 |
| Bromoform | 6.4 µg/L No EPA limit set
worst single sample: 14.4165 µg/L | 158/263 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 2.28 µg/L No EPA limit set
worst single sample: 2.48 µg/L | 69/256 | SYR4 | 2012–2019 |
| Nitrate | 3196 µg/L 32% of the EPA limit 10000 µg/L
worst single sample: 3300 µg/L | 34/46 | SYR4 | 2012–2019 |
| Copper | 22.725 µg/L 1.7% of the EPA limit 1300 µg/L
worst single sample: 46.8 µg/L | 16/17 | SYR4 | 2012–2019 |
| Barium | 83.11 µg/L 4.2% of the EPA limit 2000 µg/L
worst single sample: 86.4 µg/L | 15/15 | SYR4 | 2012–2019 |
| Lead | 0.0024 mg/L 16% of the EPA limit 0.0150 mg/L | 15/15 | LCR | 2024 |
| Monochloroacetic Acid | 1.425 µg/L No EPA limit set
worst single sample: 1.59 µg/L | 11/256 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 3040 µg/L 30% of the EPA limit 10000 µg/L
worst single sample: 3140 µg/L | 11/15 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 1.1085 µg/L No EPA limit set
worst single sample: 1.14 µg/L | 10/256 | SYR4 | 2012–2019 |
| Arsenic | 5.4585 µg/L 55% of the EPA limit 10 µg/L
worst single sample: 5.56 µg/L | 8/15 | SYR4 | 2012–2019 |
| Fluoride | 227.25 µg/L 5.7% of the EPA limit 4000 µg/L
worst single sample: 229 µg/L | 8/15 | SYR4 | 2012–2019 |
| Selenium | 1.812 µg/L 3.6% of the EPA limit 50 µg/L
worst single sample: 1.84 µg/L | 5/15 | SYR4 | 2012–2019 |
| 1,2,4-Trichlorobenzene | 0.0994 µg/L 0.1% of the EPA limit 70 µg/L
worst single sample: 0.1000 µg/L | 3/20 | SYR4 | 2012–2019 |
| Chlorobenzene | 0.0200 µg/L 0% of the EPA limit 100 µg/L | 1/20 | SYR4 | 2012–2019 |
| Chromium | 1.78 µg/L 1.8% of the EPA limit 100 µg/L | 1/15 | SYR4 | 2012–2019 |
| Dalapon | 1.17 µg/L 0.6% of the EPA limit 200 µg/L | 1/7 | SYR4 | 2013–2019 |
| Tetrachloroethylene | 2.74 µg/L 55% of the EPA limit 5 µg/L | 1/20 | SYR4 | 2012–2019 |
| Xylenes, Total | 0.0700 µg/L 0% of the EPA limit 10000 µg/L | 1/20 | SYR4 | 2012–2019 |
72 contaminants tested, none detected
Utility contact
Frequently asked questions about Richland City of
Is Richland City of tap water safe to drink?
EPA monitoring detected 33 contaminants in Richland City of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Richland City of's water?
EPA monitoring detected TTHM, Chloroform, Bromodichloromethane, Total Haloacetic Acids (HAA5), Dichloroacetic Acid, and others. The full list with the level and data source for each is above.
How many people does Richland City of serve?
Richland City of reports serving 106,499 people in Washington, per its EPA record.
Has Richland City of had any water quality violations?
The EPA has 45 violations on file for Richland City of, of which 1 is health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.