← Washington

Tap water quality report

Republic City of

EPA monitoring tested this supplier for 55 contaminants and detected 15. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

55
contaminants tested
15
detected
1,673
people served
19
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Ferry

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

19
health-based violations
32
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2010-03-01 → 2010-03-31
MCL Health-based Archived 2006-04-01 → 2006-04-30
MCL Health-based Archived 2000-09-01 → 2000-09-30
MCL Health-based Archived 2000-09-01 → 2000-09-30
MCL Health-based Archived 2000-09-01 → 2000-09-30
MCL Health-based Archived 1998-06-01 → 1998-06-30
MCL Health-based Archived 1998-06-01 → 1998-06-30
MCL Health-based Archived 1998-06-01 → 1998-06-30
MCL Health-based Archived 1997-04-01 → 1997-04-30
MCL Health-based Archived 1997-04-01 → 1997-04-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Lead
0.0022 mg/L 15%
of the EPA limit 0.0150 mg/L
11/11 LCR 2025
Nitrate
408 µg/L 4.1%
of the EPA limit 10000 µg/L
8/12 SYR4 2012–2018
Bromodichloromethane
5.945 µg/L
No EPA limit set
worst single sample: 6.5 µg/L
7/8 SYR4 2014–2019
Chloroform
28.57 µg/L
No EPA limit set
worst single sample: 29.2 µg/L
7/7 SYR4 2014–2019
TTHM
33.775 µg/L 42%
of the EPA limit 80 µg/L
worst single sample: 33.85 µg/L
7/7 SYR4 2014–2019
Total Haloacetic Acids (HAA5)
7.1325 µg/L 12%
of the EPA limit 60 µg/L
worst single sample: 7.98 µg/L
6/7 SYR4 2014–2019
Trichloroacetic Acid
2.944 µg/L
No EPA limit set
worst single sample: 3.06 µg/L
5/7 SYR4 2014–2019
Dichloroacetic Acid
4.653 µg/L
No EPA limit set
worst single sample: 4.92 µg/L
4/7 SYR4 2014–2019
Antimony, Total
2.5 µg/L 42%
of the EPA limit 6 µg/L
1/1 SYR4 2012
Arsenic
6.5 µg/L 65%
of the EPA limit 10 µg/L
1/1 SYR4 2012
Barium
17.8 µg/L 0.9%
of the EPA limit 2000 µg/L
1/1 SYR4 2012
Copper
109 µg/L 8.4%
of the EPA limit 1300 µg/L
1/1 SYR4 2012
Fluoride
270 µg/L 6.8%
of the EPA limit 4000 µg/L
1/1 SYR4 2012
Nitrate-Nitrite
268 µg/L 2.7%
of the EPA limit 10000 µg/L
1/1 SYR4 2012
Selenium
1.2 µg/L 2.4%
of the EPA limit 50 µg/L
1/1 SYR4 2012
40 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DBenzeneBeryllium, TotalBromoformChlorobenzeneCyanideCadmiumCarbon TetrachlorideChromiumDichloromethaneDalaponDibromoacetic AcidDibromochloromethaneDinosebEthylbenzeneLeadMercuryMonobromoacetic AcidMonochloroacetic AcidNitritePentachlorophenolPicloramStyreneTetrachloroethyleneThallium, TotalTolueneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
Nick Olsen

Frequently asked questions about Republic City of

Is Republic City of tap water safe to drink?

EPA monitoring detected 15 contaminants in Republic City of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Republic City of's water?

EPA monitoring detected Lead, Nitrate, Bromodichloromethane, Chloroform, TTHM, and others. The full list with the level and data source for each is above.

How many people does Republic City of serve?

Republic City of reports serving 1,673 people in Washington, per its EPA record.

Has Republic City of had any water quality violations?

The EPA has 32 violations on file for Republic City of, of which 19 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.