Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2020-01-01 → 2020-12-31 |
| MCL | Health-based | Resolved | 2019-01-01 → 2019-12-31 |
| MCL | Health-based | Resolved | 2018-01-01 → 2018-12-31 |
| MCL | Health-based | Resolved | 2018-01-01 → 2018-12-31 |
| MCL | Health-based | Resolved | 2017-07-01 → 2017-09-30 |
| MCL | Health-based | Resolved | 2016-04-01 → 2016-06-30 |
| MCL | Health-based | Resolved | 2016-01-01 → 2016-12-31 |
| MCL | Health-based | Archived | 2000-11-01 → 2000-11-30 |
| MCL | Health-based | Archived | 2000-11-01 → 2000-11-30 |
| MCL | Health-based | Archived | 2000-11-01 → 2000-11-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 12970 µg/L 130% of the EPA limit, at the 95th percentile of samples — 10000 µg/L
worst single sample: 13600 µg/L | 30/32 | SYR4 | 2012–2019 |
| Lead | 0.00060 mg/L 4% of the EPA limit 0.0150 mg/L | 10/10 | LCR | 2024 |
| Bromoform | 11.12 µg/L No EPA limit set
worst single sample: 11.4 µg/L | 3/8 | SYR4 | 2012–2019 |
| TTHM | 11.57 µg/L 14% of the EPA limit 80 µg/L
worst single sample: 11.9 µg/L | 3/3 | SYR4 | 2012–2014 |
| Arsenic | 2 µg/L 20% of the EPA limit 10 µg/L | 2/2 | SYR4 | 2012–2017 |
| Dibromoacetic Acid | 1.865 µg/L No EPA limit set
worst single sample: 1.9 µg/L | 2/3 | SYR4 | 2013–2017 |
| Fluoride | 1808 µg/L 45% of the EPA limit 4000 µg/L
worst single sample: 1840 µg/L | 2/2 | SYR4 | 2012–2017 |
| Nitrate-Nitrite | 9635 µg/L 96% of the EPA limit 10000 µg/L
worst single sample: 10000 µg/L | 2/2 | SYR4 | 2012–2017 |
| Selenium | 4.9 µg/L 9.8% of the EPA limit 50 µg/L
worst single sample: 5 µg/L | 2/2 | SYR4 | 2012–2017 |
| Total Haloacetic Acids (HAA5) | 1.865 µg/L 3.1% of the EPA limit 60 µg/L
worst single sample: 1.9 µg/L | 2/3 | SYR4 | 2013–2017 |
| Barium | 24 µg/L 1.2% of the EPA limit 2000 µg/L | 1/2 | SYR4 | 2012–2017 |
| Chromium | 2 µg/L 2% of the EPA limit 100 µg/L | 1/2 | SYR4 | 2012–2017 |
| Dibromochloromethane | 0.5000 µg/L No EPA limit set | 1/8 | SYR4 | 2012–2019 |
| Tetrachloroethylene | 0.6000 µg/L 12% of the EPA limit 5 µg/L | 1/5 | SYR4 | 2012–2019 |
59 contaminants tested, none detected
Utility contact
Frequently asked questions about Plymouth Water District
Is Plymouth Water District tap water safe to drink?
EPA monitoring detected 14 contaminants in Plymouth Water District's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Plymouth Water District's water?
EPA monitoring detected Nitrate, Lead, Bromoform, TTHM, Arsenic, and others. The full list with the level and data source for each is above.
How many people does Plymouth Water District serve?
Plymouth Water District reports serving 288 people in Washington, per its EPA record.
Has Plymouth Water District had any water quality violations?
The EPA has 629 violations on file for Plymouth Water District, of which 23 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.