Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2011-01-01 → 2011-03-31 |
| MCL | Health-based | Resolved | 2009-01-01 → 2009-03-31 |
| MCL | Health-based | Resolved | 2009-01-01 → 2009-03-31 |
| MCL | Health-based | Resolved | 2009-01-01 → 2009-03-31 |
| MCL | Health-based | Resolved | 2009-01-01 → 2009-03-31 |
| MCL | Health-based | Resolved | 2009-01-01 → 2009-03-31 |
| MCL | Health-based | Resolved | 2009-01-01 → 2009-03-31 |
| MCL | Health-based | Resolved | 2008-10-01 → 2008-12-31 |
| MCL | Health-based | Resolved | 2008-10-01 → 2008-12-31 |
| MCL | Health-based | Resolved | 2008-10-01 → 2008-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 8850.5 µg/L 89% of the EPA limit 10000 µg/L
worst single sample: 9470 µg/L | 78/78 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 8375 µg/L 84% of the EPA limit 10000 µg/L
worst single sample: 9080 µg/L | 31/31 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 9/9 | LCR | 2024 |
| Bromodichloromethane | 4.25 µg/L No EPA limit set
worst single sample: 4.6 µg/L | 6/10 | SYR4 | 2013–2019 |
| Chloroform | 8.375 µg/L No EPA limit set
worst single sample: 8.7 µg/L | 6/9 | SYR4 | 2013–2019 |
| TTHM | 13.525 µg/L 17% of the EPA limit 80 µg/L
worst single sample: 13.8 µg/L | 6/6 | SYR4 | 2014–2019 |
| Dibromochloromethane | 1.92 µg/L No EPA limit set
worst single sample: 1.95 µg/L | 5/10 | SYR4 | 2013–2019 |
| Dichloroacetic Acid | 35.09 µg/L No EPA limit set
worst single sample: 40.4 µg/L | 4/7 | SYR4 | 2014–2019 |
| Total Haloacetic Acids (HAA5) | 61.6 µg/L 103% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 70.9 µg/L | 4/6 | SYR4 | 2014–2016 |
| Arsenic | 6.162 µg/L 62% of the EPA limit 10 µg/L
worst single sample: 6.75 µg/L | 3/3 | SYR4 | 2013–2019 |
| Barium | 107.17 µg/L 5.4% of the EPA limit 2000 µg/L
worst single sample: 109.1 µg/L | 3/3 | SYR4 | 2013–2019 |
| Copper | 37.684 µg/L 2.9% of the EPA limit 1300 µg/L
worst single sample: 38.87 µg/L | 3/3 | SYR4 | 2013–2019 |
| Chromium | 5.847 µg/L 5.8% of the EPA limit 100 µg/L
worst single sample: 6.25 µg/L | 3/3 | SYR4 | 2013–2019 |
| Fluoride | 199 µg/L 5% of the EPA limit 4000 µg/L
worst single sample: 200 µg/L | 3/3 | SYR4 | 2013–2019 |
| Lead | 1.325 µg/L 8.8% of the EPA limit 15 µg/L
worst single sample: 1.41 µg/L | 3/3 | SYR4 | 2013–2019 |
| Thallium, Total | 0.5760 µg/L 29% of the EPA limit 2 µg/L
worst single sample: 0.6200 µg/L | 3/3 | SYR4 | 2013–2019 |
| Trichloroacetic Acid | 15.87 µg/L No EPA limit set
worst single sample: 17.2 µg/L | 3/7 | SYR4 | 2014–2019 |
| Selenium | 0.8655 µg/L 1.7% of the EPA limit 50 µg/L
worst single sample: 0.8700 µg/L | 2/3 | SYR4 | 2013–2019 |
| Antimony, Total | 0.3800 µg/L 6.3% of the EPA limit 6 µg/L | 1/3 | SYR4 | 2013–2019 |
| Combined Radium (-226 And -228) | 4.45 pCi/L 89% of the EPA limit 5 pCi/L | 1/1 | SYR4 | 2012 |
| Dibromoacetic Acid | 1.8 µg/L No EPA limit set | 1/7 | SYR4 | 2014–2019 |
| Monochloroacetic Acid | 11.5 µg/L No EPA limit set | 1/7 | SYR4 | 2014–2019 |
52 contaminants tested, none detected
Utility contact
Frequently asked questions about Greater Bar Water District
Is Greater Bar Water District tap water safe to drink?
EPA monitoring detected 22 contaminants in Greater Bar Water District's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Greater Bar Water District's water?
EPA monitoring detected Nitrate, Nitrate-Nitrite, Lead, Bromodichloromethane, Chloroform, and others. The full list with the level and data source for each is above.
How many people does Greater Bar Water District serve?
Greater Bar Water District reports serving 330 people in Washington, per its EPA record.
Has Greater Bar Water District had any water quality violations?
The EPA has 1602 violations on file for Greater Bar Water District, of which 171 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.