← Virginia

Tap water quality report

Puddledock Road

EPA monitoring tested this supplier for 45 contaminants and detected 15. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

45
contaminants tested
15
detected
9,271
people served
4
health-based violations
Water source
SWP
Ownership
Local government
Counties served
Prince George

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

4
health-based violations
23
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2000-07-01 → 2000-07-31
MCL Health-based Resolved 2000-07-01 → 2000-07-31
MCL Health-based Resolved 2000-07-01 → 2000-07-31
MCL Health-based Resolved 2000-07-01 → 2000-07-31
MR Monitoring Resolved 2023-04-01 → 2023-06-30
MR Monitoring Resolved 2023-04-01 → 2023-06-30
MR Monitoring Resolved 2023-04-01 → 2023-06-30
MR Monitoring Resolved 2023-04-01 → 2023-06-30
MR Monitoring Resolved 2023-04-01 → 2023-06-30
MR Monitoring Resolved 2023-04-01 → 2023-06-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Chlorite
265.3 µg/L 27%
of the EPA limit 1000 µg/L
worst single sample: 423 µg/L
79/101 SYR4 2012–2019
Bromodichloromethane
8.458 µg/L
No EPA limit set
worst single sample: 9.67 µg/L
63/63 SYR4 2012–2019
Chloroform
36.759 µg/L
No EPA limit set
worst single sample: 60.78 µg/L
63/63 SYR4 2012–2019
TTHM
44.932 µg/L 56%
of the EPA limit 80 µg/L
worst single sample: 67.86 µg/L
63/63 SYR4 2012–2019
Copper
129.1 µg/L 9.9%
of the EPA limit 1300 µg/L
worst single sample: 541 µg/L
60/80 SYR4 2013–2017
Total Haloacetic Acids (HAA5)
43.873 µg/L 73%
of the EPA limit 60 µg/L
worst single sample: 55.91 µg/L
43/63 SYR4 2012–2019
Dichloroacetic Acid
27.5684 µg/L
No EPA limit set
worst single sample: 33.3 µg/L
40/63 SYR4 2012–2019
Trichloroacetic Acid
12.9632 µg/L
No EPA limit set
worst single sample: 20.47 µg/L
37/63 SYR4 2012–2019
Dibromochloromethane
2.862 µg/L
No EPA limit set
worst single sample: 3.16 µg/L
35/63 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
14/14 LCR 2023
Monochloroacetic Acid
6.1264 µg/L
No EPA limit set
worst single sample: 7.36 µg/L
13/63 SYR4 2012–2019
Dibromoacetic Acid
6.6604 µg/L
No EPA limit set
worst single sample: 6.907 µg/L
10/63 SYR4 2012–2019
Lead
5.947 µg/L 40%
of the EPA limit 15 µg/L
worst single sample: 6.07 µg/L
4/80 SYR4 2013–2017
Monobromoacetic Acid
3.4655 µg/L
No EPA limit set
worst single sample: 3.74 µg/L
4/63 SYR4 2012–2019
Bromoform
1.724 µg/L
No EPA limit set
worst single sample: 1.75 µg/L
3/63 SYR4 2012–2019
30 contaminants tested, none detected
11Cl-PF3OUdS4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaHfpo-DaNetfosaaNfdhaNmefosaaPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaLithium

Utility contact

Contact
LUMPKIN, RACHEL
Phone
804-722-8706
Email
[email protected]

Frequently asked questions about Puddledock Road

Is Puddledock Road tap water safe to drink?

EPA monitoring detected 15 contaminants in Puddledock Road's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Puddledock Road's water?

EPA monitoring detected Chlorite, Bromodichloromethane, Chloroform, TTHM, Copper, and others. The full list with the level and data source for each is above.

How many people does Puddledock Road serve?

Puddledock Road reports serving 9,271 people in Virginia, per its EPA record.

Has Puddledock Road had any water quality violations?

The EPA has 23 violations on file for Puddledock Road, of which 4 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.