Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MR | Monitoring | Resolved | 2013-10-01 |
| MR | Monitoring | Resolved | 2011-10-01 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 21.455 µg/L No EPA limit set
worst single sample: 24.6 µg/L | 32/32 | SYR4 | 2012–2019 |
| Chloroform | 51.655 µg/L No EPA limit set
worst single sample: 72.2 µg/L | 32/32 | SYR4 | 2012–2019 |
| Dibromochloromethane | 11.635 µg/L No EPA limit set
worst single sample: 12.5 µg/L | 32/32 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 28.325 µg/L No EPA limit set
worst single sample: 34.7 µg/L | 32/32 | SYR4 | 2012–2019 |
| TTHM | 72.41 µg/L 91% of the EPA limit 80 µg/L
worst single sample: 94.1 µg/L | 32/32 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 49.265 µg/L 82% of the EPA limit 60 µg/L
worst single sample: 60.3 µg/L | 32/32 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 19.185 µg/L No EPA limit set
worst single sample: 25.6 µg/L | 32/32 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 2.98 µg/L No EPA limit set
worst single sample: 3.7 µg/L | 17/32 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 4.2 µg/L No EPA limit set
worst single sample: 4.5 µg/L | 11/32 | SYR4 | 2012–2019 |
| Bromoform | 1.9605 µg/L No EPA limit set
worst single sample: 2.01 µg/L | 10/32 | SYR4 | 2012–2019 |
| Copper | 37.75 µg/L 2.9% of the EPA limit 1300 µg/L
worst single sample: 40 µg/L | 6/10 | SYR4 | 2014–2017 |
| Monobromoacetic Acid | 2.48 µg/L No EPA limit set
worst single sample: 2.8 µg/L | 5/32 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 1/1 | LCR | 2023 |
1 contaminants tested, none detected
Utility contact
Frequently asked questions about Northcrest Water
Is Northcrest Water tap water safe to drink?
EPA monitoring detected 13 contaminants in Northcrest Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Northcrest Water's water?
EPA monitoring detected Bromodichloromethane, Chloroform, Dibromochloromethane, Dichloroacetic Acid, TTHM, and others. The full list with the level and data source for each is above.
How many people does Northcrest Water serve?
Northcrest Water reports serving 60 people in Texas, per its EPA record.
Has Northcrest Water had any water quality violations?
The EPA has 2 violations on file for Northcrest Water, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.