Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2023-01-01 → 2023-03-31 |
| MCL | Health-based | Resolved | 2023-01-01 → 2023-03-31 |
| MCL | Health-based | Resolved | 2023-01-01 → 2023-03-31 |
| MCL | Health-based | Resolved | 2023-01-01 → 2023-03-31 |
| MCL | Health-based | Resolved | 2020-04-01 → 2020-06-30 |
| MCL | Health-based | Resolved | 2020-04-01 → 2020-06-30 |
| MCL | Health-based | Resolved | 2020-04-01 → 2020-06-30 |
| MCL | Health-based | Resolved | 2020-04-01 → 2020-06-30 |
| MCL | Health-based | Resolved | 2015-01-01 → 2015-03-31 |
| MCL | Health-based | Resolved | 2015-01-01 → 2015-03-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 1491.5 µg/L 115% of the EPA limit, at the 95th percentile of samples — 1300 µg/L
worst single sample: 2500 µg/L | 72/72 | SYR4 | 2012–2019 |
| Nitrate | 22470 µg/L 225% of the EPA limit, at the 95th percentile of samples — 10000 µg/L
worst single sample: 22600 µg/L | 64/64 | SYR4 | 2012–2019 |
| Lead | 29.07 µg/L 194% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 102 µg/L | 47/72 | SYR4 | 2012–2019 |
| Arsenic | 24.74 µg/L 247% of the EPA limit, at the 95th percentile of samples — 10 µg/L
worst single sample: 25.1 µg/L | 19/19 | SYR4 | 2012–2019 |
| Selenium | 44.74 µg/L 89% of the EPA limit 50 µg/L
worst single sample: 54.6 µg/L | 18/19 | SYR4 | 2012–2019 |
| Bromoform | 40.32 µg/L No EPA limit set
worst single sample: 45.3 µg/L | 13/15 | SYR4 | 2012–2019 |
| Lead | 0.00047 mg/L 3.1% of the EPA limit 0.0150 mg/L | 11/11 | LCR | 2025 |
| Nitrate-Nitrite | 21940 µg/L 219% of the EPA limit, at the 95th percentile of samples — 10000 µg/L
worst single sample: 22300 µg/L | 10/10 | SYR4 | 2012–2015 |
| Dibromochloromethane | 3.14 µg/L No EPA limit set
worst single sample: 3.92 µg/L | 9/15 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 9.75 µg/L No EPA limit set
worst single sample: 10.8 µg/L | 6/7 | SYR4 | 2013–2019 |
| TTHM | 44.675 µg/L 56% of the EPA limit 80 µg/L
worst single sample: 46.8 µg/L | 6/7 | SYR4 | 2013–2019 |
| Total Haloacetic Acids (HAA5) | 27.5 µg/L 46% of the EPA limit 60 µg/L
worst single sample: 30.7 µg/L | 6/7 | SYR4 | 2013–2019 |
| Barium | 27.51 µg/L 1.4% of the EPA limit 2000 µg/L
worst single sample: 29.5 µg/L | 3/3 | SYR4 | 2012–2019 |
| Fluoride | 3220 µg/L 81% of the EPA limit 4000 µg/L
worst single sample: 3450 µg/L | 3/3 | SYR4 | 2012–2018 |
| Monochloroacetic Acid | 19.45 µg/L No EPA limit set
worst single sample: 19.9 µg/L | 3/7 | SYR4 | 2013–2019 |
| Chromium | 0.7300 µg/L 0.7% of the EPA limit 100 µg/L | 1/3 | SYR4 | 2012–2019 |
59 contaminants tested, none detected
Utility contact
Frequently asked questions about Greenwood Isd
Is Greenwood Isd tap water safe to drink?
EPA monitoring detected 16 contaminants in Greenwood Isd's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Greenwood Isd's water?
EPA monitoring detected Copper, Nitrate, Lead, Arsenic, Selenium, and others. The full list with the level and data source for each is above.
How many people does Greenwood Isd serve?
Greenwood Isd reports serving 3,945 people in Texas, per its EPA record.
Has Greenwood Isd had any water quality violations?
The EPA has 302 violations on file for Greenwood Isd, of which 250 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.