Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Unaddressed | 2023-01-16 |
| TT | Health-based | Unaddressed | 2023-01-16 |
| TT | Health-based | Unaddressed | 2023-01-16 |
| MCL | Health-based | Resolved | 2005-10-01 → 2005-12-31 |
| MCL | Health-based | Resolved | 2005-10-01 → 2005-12-31 |
| MCL | Health-based | Resolved | 2005-10-01 → 2005-12-31 |
| MCL | Health-based | Resolved | 2005-07-01 → 2005-09-30 |
| MCL | Health-based | Resolved | 2005-07-01 → 2005-09-30 |
| MCL | Health-based | Resolved | 2005-07-01 → 2005-09-30 |
| MCL | Health-based | Resolved | 2005-07-01 → 2005-09-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Chloroform | 39.03 µg/L No EPA limit set
worst single sample: 45.6 µg/L | 67/75 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 13.895 µg/L No EPA limit set
worst single sample: 28.5 µg/L | 62/64 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 36.595 µg/L 61% of the EPA limit 60 µg/L
worst single sample: 65.7 µg/L | 62/64 | SYR4 | 2012–2019 |
| TTHM | 91.23 µg/L 114% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 104 µg/L | 58/64 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 19.54 µg/L No EPA limit set
worst single sample: 28.5 µg/L | 49/64 | SYR4 | 2012–2019 |
| Bromodichloromethane | 31.51 µg/L No EPA limit set
worst single sample: 36.3 µg/L | 47/75 | SYR4 | 2012–2019 |
| Copper | 1505 µg/L 116% of the EPA limit, at the 95th percentile of samples — 1300 µg/L
worst single sample: 1700 µg/L | 46/50 | SYR4 | 2013–2019 |
| Lead | 6.06 µg/L 40% of the EPA limit 15 µg/L
worst single sample: 9.1 µg/L | 37/50 | SYR4 | 2013–2019 |
| Dibromochloromethane | 22.4 µg/L No EPA limit set
worst single sample: 27.6 µg/L | 35/75 | SYR4 | 2012–2019 |
| Bromoform | 6.9 µg/L No EPA limit set
worst single sample: 8.78 µg/L | 29/75 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 9.255 µg/L No EPA limit set
worst single sample: 15.9 µg/L | 24/64 | SYR4 | 2012–2019 |
| Nitrate | 464.075 µg/L 4.6% of the EPA limit 10000 µg/L
worst single sample: 533 µg/L | 24/30 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 4.89 µg/L No EPA limit set
worst single sample: 5.6 µg/L | 23/64 | SYR4 | 2012–2019 |
| Lead | 0.0117 mg/L 78% of the EPA limit 0.0150 mg/L | 9/9 | LCR | 2025 |
| Monobromoacetic Acid | 2.24 µg/L No EPA limit set
worst single sample: 2.3 µg/L | 7/64 | SYR4 | 2012–2019 |
| Fluoride | 1058 µg/L 26% of the EPA limit 4000 µg/L
worst single sample: 1070 µg/L | 5/5 | SYR4 | 2013–2019 |
| Nitrate-Nitrite | 69 µg/L 0.7% of the EPA limit 10000 µg/L
worst single sample: 73.5 µg/L | 5/6 | SYR4 | 2012–2015 |
| Combined Radium (-226 And -228) | 1.5 pCi/L 30% of the EPA limit 5 pCi/L | 4/4 | SYR4 | 2012–2018 |
| Barium | 55.7 µg/L 2.8% of the EPA limit 2000 µg/L
worst single sample: 56 µg/L | 3/3 | SYR4 | 2016–2019 |
| Cyanide | 46.3485 µg/L 23% of the EPA limit 200 µg/L
worst single sample: 48.5 µg/L | 2/5 | SYR4 | 2012–2018 |
| Chromium | 5.3 µg/L 5.3% of the EPA limit 100 µg/L | 1/3 | SYR4 | 2016–2019 |
| Ethylbenzene | 0.6300 µg/L 0.1% of the EPA limit 700 µg/L | 1/11 | SYR4 | 2014–2019 |
| Toluene | 0.8200 µg/L 0.1% of the EPA limit 1000 µg/L | 1/11 | SYR4 | 2014–2019 |
| Xylenes, Total | 4.26 µg/L 0% of the EPA limit 10000 µg/L | 1/11 | SYR4 | 2014–2019 |
55 contaminants tested, none detected
Utility contact
Frequently asked questions about Crestwood Water Co
Is Crestwood Water Co tap water safe to drink?
EPA monitoring detected 24 contaminants in Crestwood Water Co's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Crestwood Water Co's water?
EPA monitoring detected Chloroform, Dichloroacetic Acid, Total Haloacetic Acids (HAA5), TTHM, Trichloroacetic Acid, and others. The full list with the level and data source for each is above.
How many people does Crestwood Water Co serve?
Crestwood Water Co reports serving 744 people in Texas, per its EPA record.
Has Crestwood Water Co had any water quality violations?
The EPA has 30 violations on file for Crestwood Water Co, of which 10 are health-based (a contaminant limit or required treatment was breached) and 3 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.