Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MR | Monitoring | Resolved | 2025-04-01 → 2025-06-30 |
| MR | Monitoring | Resolved | 2025-04-01 → 2025-06-30 |
| MR | Monitoring | Resolved | 2025-04-01 → 2025-06-30 |
| MR | Monitoring | Resolved | 2025-04-01 → 2025-06-30 |
| Other | Monitoring | Resolved | 2018-07-01 |
| Other | Monitoring | Resolved | 2018-07-01 |
| Other | Monitoring | Resolved | 2018-07-01 |
| MR | Monitoring | Unaddressed | 2017-12-30 |
| MON | Monitoring | Resolved | 2016-09-01 → 2016-09-30 |
| MON | Monitoring | Resolved | 2016-09-01 → 2016-09-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 2150 µg/L 22% of the EPA limit 10000 µg/L | 16/16 | SYR4 | 2012–2019 |
| Copper | 65.885 µg/L 5.1% of the EPA limit 1300 µg/L
worst single sample: 68.3 µg/L | 8/12 | SYR4 | 2013–2017 |
| Bromoform | 2.35 µg/L No EPA limit set
worst single sample: 2.5 µg/L | 6/7 | SYR4 | 2015–2019 |
| Dibromochloromethane | 1.57 µg/L No EPA limit set
worst single sample: 1.6 µg/L | 4/7 | SYR4 | 2015–2019 |
| Barium | 30.31 µg/L 1.5% of the EPA limit 2000 µg/L
worst single sample: 30.9 µg/L | 3/3 | SYR4 | 2013–2019 |
| Fluoride | 1207 µg/L 30% of the EPA limit 4000 µg/L
worst single sample: 1210 µg/L | 3/3 | SYR4 | 2013–2019 |
| Nitrate-Nitrite | 1437 µg/L 14% of the EPA limit 10000 µg/L
worst single sample: 1440 µg/L | 3/3 | SYR4 | 2012–2015 |
| Lead | 0.0010 mg/L 6.7% of the EPA limit 0.0150 mg/L | 2/2 | LCR | 2023 |
| Lead | 1.585 µg/L 11% of the EPA limit 15 µg/L
worst single sample: 1.6 µg/L | 2/12 | SYR4 | 2013–2017 |
| TTHM | 4.805 µg/L 6% of the EPA limit 80 µg/L
worst single sample: 4.9 µg/L | 2/2 | SYR4 | 2016–2019 |
| Chloroform | 1.3 µg/L No EPA limit set | 1/7 | SYR4 | 2015–2019 |
| Combined Radium (-226 And -228) | 2.3 pCi/L 46% of the EPA limit 5 pCi/L | 1/1 | SYR4 | 2013 |
| Dibromoacetic Acid | 1.1 µg/L No EPA limit set | 1/2 | SYR4 | 2016–2019 |
| Gross Alpha, Excl. Radon And U | 3.3 pCi/L 22% of the EPA limit 15 pCi/L | 1/1 | SYR4 | 2019 |
| Total Haloacetic Acids (HAA5) | 4.1 µg/L 6.8% of the EPA limit 60 µg/L | 1/2 | SYR4 | 2016–2019 |
| Trichloroacetic Acid | 3 µg/L No EPA limit set | 1/2 | SYR4 | 2016–2019 |
63 contaminants tested, none detected
Utility contact
Frequently asked questions about Cardinal Motor Home Park
Is Cardinal Motor Home Park tap water safe to drink?
EPA monitoring detected 16 contaminants in Cardinal Motor Home Park's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Cardinal Motor Home Park's water?
EPA monitoring detected Nitrate, Copper, Bromoform, Dibromochloromethane, Barium, and others. The full list with the level and data source for each is above.
How many people does Cardinal Motor Home Park serve?
Cardinal Motor Home Park reports serving 57 people in Texas, per its EPA record.
Has Cardinal Motor Home Park had any water quality violations?
The EPA has 28 violations on file for Cardinal Motor Home Park, of which 0 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.