← Texas

Tap water quality report

Oak Hill Water

EPA monitoring tested this supplier for 79 contaminants and detected 14. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

79
contaminants tested
14
detected
96
people served
0
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Hill

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
5
violations on file
0
still open
ViolationTypeStatusPeriod
RPT Monitoring Resolved 2025-07-02
Other Monitoring Resolved 2008-07-25
MR Monitoring Resolved 2007-11-01 → 2007-11-30
MR Monitoring Resolved 2007-11-01 → 2007-11-30
MR Monitoring Resolved 2007-11-01 → 2007-11-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
60 µg/L 0.6%
of the EPA limit 10000 µg/L
16/16 SYR4 2012–2019
Copper
70.6 µg/L 5.4%
of the EPA limit 1300 µg/L
worst single sample: 75 µg/L
12/12 SYR4 2014–2017
Bromoform
2.4965 µg/L
No EPA limit set
worst single sample: 2.5 µg/L
8/8 SYR4 2012–2019
Dibromochloromethane
2.604 µg/L
No EPA limit set
worst single sample: 2.76 µg/L
7/8 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
6/6 LCR 2023
Bromodichloromethane
2.2605 µg/L
No EPA limit set
worst single sample: 2.43 µg/L
4/8 SYR4 2012–2019
Fluoride
509.8 µg/L 13%
of the EPA limit 4000 µg/L
worst single sample: 512 µg/L
3/3 SYR4 2013–2019
Nitrate-Nitrite
59 µg/L 0.6%
of the EPA limit 10000 µg/L
worst single sample: 60 µg/L
3/3 SYR4 2012–2015
Barium
48.955 µg/L 2.4%
of the EPA limit 2000 µg/L
worst single sample: 49 µg/L
2/2 SYR4 2014–2017
Chloroform
1.203 µg/L
No EPA limit set
worst single sample: 1.24 µg/L
2/8 SYR4 2012–2019
Combined Radium (-226 And -228)
1.475 pCi/L 30%
of the EPA limit 5 pCi/L
worst single sample: 1.5 pCi/L
2/2 SYR4 2012–2018
TTHM
4.0985 µg/L 5.1%
of the EPA limit 80 µg/L
worst single sample: 4.23 µg/L
2/2 SYR4 2016–2019
Chromium
1.1 µg/L 1.1%
of the EPA limit 100 µg/L
1/2 SYR4 2014–2017
Lead
3.4 µg/L 23%
of the EPA limit 15 µg/L
1/12 SYR4 2014–2017
65 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalArsenicAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneCombined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDibromoacetic AcidDichloroacetic AcidDinosebEthylene DibromideEndrinEthylbenzeneGross Alpha, Excl. Radon And UGross Beta Particle ActivityHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNitriteOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Haloacetic Acids (HAA5)ToxapheneTrichloroacetic AcidTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
CHEEK, THOMAS
Phone
254-687-2331
Email
[email protected]

Frequently asked questions about Oak Hill Water

Is Oak Hill Water tap water safe to drink?

EPA monitoring detected 14 contaminants in Oak Hill Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Oak Hill Water's water?

EPA monitoring detected Nitrate, Copper, Bromoform, Dibromochloromethane, Lead, and others. The full list with the level and data source for each is above.

How many people does Oak Hill Water serve?

Oak Hill Water reports serving 96 people in Texas, per its EPA record.

Has Oak Hill Water had any water quality violations?

The EPA has 5 violations on file for Oak Hill Water, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.