Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| Other | Monitoring | Resolved | 2025-07-01 |
| Other | Monitoring | Resolved | 2025-07-01 |
| MR | Monitoring | Resolved | 2016-07-01 |
| MR | Monitoring | Resolved | 2016-07-01 |
| MR | Monitoring | Resolved | 2016-07-01 |
| MR | Monitoring | Resolved | 2016-07-01 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 327.4 µg/L 25% of the EPA limit 1300 µg/L
worst single sample: 1083 µg/L | 155/161 | SYR4 | 2015–2017 |
| Lead | 9.085 µg/L 61% of the EPA limit 15 µg/L
worst single sample: 20 µg/L | 30/161 | SYR4 | 2015–2017 |
| Dibromochloromethane | 13.72 µg/L No EPA limit set
worst single sample: 13.8 µg/L | 17/17 | SYR4 | 2015–2019 |
| Bromoform | 25.67 µg/L No EPA limit set
worst single sample: 25.8 µg/L | 14/17 | SYR4 | 2015–2019 |
| Bromodichloromethane | 4.57 µg/L No EPA limit set
worst single sample: 4.9 µg/L | 12/17 | SYR4 | 2015–2019 |
| TTHM | 43.385 µg/L 54% of the EPA limit 80 µg/L
worst single sample: 43.7 µg/L | 10/10 | SYR4 | 2015–2019 |
| Dibromoacetic Acid | 4.065 µg/L No EPA limit set
worst single sample: 4.1 µg/L | 8/10 | SYR4 | 2015–2019 |
| Nitrate | 30 µg/L 0.3% of the EPA limit 10000 µg/L | 8/10 | SYR4 | 2015–2019 |
| Total Haloacetic Acids (HAA5) | 4.99 µg/L 8.3% of the EPA limit 60 µg/L
worst single sample: 5.2 µg/L | 8/10 | SYR4 | 2015–2019 |
| Chloroform | 1.65 µg/L No EPA limit set
worst single sample: 1.7 µg/L | 6/17 | SYR4 | 2015–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 6/6 | LCR | 2023 |
| Barium | 118.52 µg/L 5.9% of the EPA limit 2000 µg/L
worst single sample: 120 µg/L | 2/2 | SYR4 | 2015–2018 |
| Dichloroacetic Acid | 1.285 µg/L No EPA limit set
worst single sample: 1.3 µg/L | 2/10 | SYR4 | 2015–2019 |
| Fluoride | 2201 µg/L 55% of the EPA limit 4000 µg/L
worst single sample: 2280 µg/L | 2/2 | SYR4 | 2015–2018 |
| Trichloroacetic Acid | 1.095 µg/L No EPA limit set
worst single sample: 1.1 µg/L | 2/10 | SYR4 | 2015–2019 |
| Lithium | 44.6 µg/L No EPA limit set | 2/2 | UCMR-5 | 2025 |
| Arsenic | 2.1 µg/L 21% of the EPA limit 10 µg/L | 1/2 | SYR4 | 2015–2018 |
| Selenium | 3.8 µg/L 7.6% of the EPA limit 50 µg/L | 1/2 | SYR4 | 2015–2018 |
89 contaminants tested, none detected
Utility contact
Frequently asked questions about Harris County Improvement District 18
Is Harris County Improvement District 18 tap water safe to drink?
EPA monitoring detected 18 contaminants in Harris County Improvement District 18's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Harris County Improvement District 18's water?
EPA monitoring detected Copper, Lead, Dibromochloromethane, Bromoform, Bromodichloromethane, and others. The full list with the level and data source for each is above.
How many people does Harris County Improvement District 18 serve?
Harris County Improvement District 18 reports serving 5,025 people in Texas, per its EPA record.
Has Harris County Improvement District 18 had any water quality violations?
The EPA has 6 violations on file for Harris County Improvement District 18, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.