Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MR | Monitoring | Resolved | 2014-10-01 |
| MR | Monitoring | Resolved | 2014-10-01 |
| MR | Monitoring | Resolved | 2014-10-01 |
| MR | Monitoring | Resolved | 2014-10-01 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 136 µg/L 10% of the EPA limit 1300 µg/L
worst single sample: 400 µg/L | 29/40 | SYR4 | 2015–2018 |
| Nitrate | 1320 µg/L 13% of the EPA limit 10000 µg/L | 18/18 | SYR4 | 2012–2019 |
| Chloroform | 15.99 µg/L No EPA limit set
worst single sample: 16.8 µg/L | 10/10 | SYR4 | 2012–2019 |
| Bromodichloromethane | 3.26 µg/L No EPA limit set
worst single sample: 3.3 µg/L | 9/10 | SYR4 | 2012–2019 |
| Lead | 0.00050 mg/L 3.3% of the EPA limit 0.0150 mg/L | 9/9 | LCR | 2024 |
| Dichloroacetic Acid | 26.43 µg/L No EPA limit set
worst single sample: 31.4 µg/L | 8/8 | SYR4 | 2012–2019 |
| TTHM | 18.33 µg/L 23% of the EPA limit 80 µg/L
worst single sample: 18.4 µg/L | 8/8 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 40.17 µg/L 67% of the EPA limit 60 µg/L
worst single sample: 49.9 µg/L | 8/8 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 4.995 µg/L No EPA limit set
worst single sample: 5.8 µg/L | 8/8 | SYR4 | 2012–2019 |
| Lead | 9.1 µg/L 61% of the EPA limit 15 µg/L
worst single sample: 10 µg/L | 7/40 | SYR4 | 2015–2018 |
| Nitrate-Nitrite | 1229 µg/L 12% of the EPA limit 10000 µg/L
worst single sample: 1340 µg/L | 4/4 | SYR4 | 2012–2015 |
| Nitrite | 98 µg/L 9.8% of the EPA limit 1000 µg/L
worst single sample: 110 µg/L | 4/4 | SYR4 | 2012–2015 |
| Dibromochloromethane | 1 µg/L No EPA limit set | 2/10 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 12.18 µg/L No EPA limit set
worst single sample: 12.7 µg/L | 2/8 | SYR4 | 2012–2019 |
| Arsenic | 2.4 µg/L 24% of the EPA limit 10 µg/L | 1/1 | SYR4 | 2019 |
| Barium | 172 µg/L 8.6% of the EPA limit 2000 µg/L | 1/1 | SYR4 | 2019 |
| Fluoride | 150 µg/L 3.8% of the EPA limit 4000 µg/L | 1/1 | SYR4 | 2019 |
88 contaminants tested, none detected
Utility contact
Frequently asked questions about Harris County Wcid 96
Is Harris County Wcid 96 tap water safe to drink?
EPA monitoring detected 20 contaminants in Harris County Wcid 96's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Harris County Wcid 96's water?
EPA monitoring detected Copper, Nitrate, Chloroform, Bromodichloromethane, Lead, and others. The full list with the level and data source for each is above.
How many people does Harris County Wcid 96 serve?
Harris County Wcid 96 reports serving 10,530 people in Texas, per its EPA record.
Has Harris County Wcid 96 had any water quality violations?
The EPA has 4 violations on file for Harris County Wcid 96, of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.