Compliance record
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Chloroform | 17.53 µg/L No EPA limit set
worst single sample: 23 µg/L | 59/61 | SYR4 | 2012–2019 |
| Bromodichloromethane | 3.22 µg/L No EPA limit set
worst single sample: 3.8 µg/L | 57/61 | SYR4 | 2012–2019 |
| Copper | 154.5 µg/L 12% of the EPA limit 1300 µg/L
worst single sample: 1380 µg/L | 56/72 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 21.74 µg/L No EPA limit set
worst single sample: 24.2 µg/L | 52/53 | SYR4 | 2013–2019 |
| TTHM | 20.135 µg/L 25% of the EPA limit 80 µg/L
worst single sample: 21 µg/L | 52/53 | SYR4 | 2013–2019 |
| Total Haloacetic Acids (HAA5) | 26.845 µg/L 45% of the EPA limit 60 µg/L
worst single sample: 34 µg/L | 52/53 | SYR4 | 2013–2019 |
| Trichloroacetic Acid | 3.7 µg/L No EPA limit set
worst single sample: 4.3 µg/L | 52/53 | SYR4 | 2013–2019 |
| Monochloroacetic Acid | 7.83 µg/L No EPA limit set
worst single sample: 8 µg/L | 18/53 | SYR4 | 2013–2019 |
| Lead | 27.32 µg/L 182% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 51.4 µg/L | 17/72 | SYR4 | 2012–2019 |
| Nitrate | 1560 µg/L 16% of the EPA limit 10000 µg/L | 14/16 | SYR4 | 2012–2019 |
| Lead | 0.00081 mg/L 5.4% of the EPA limit 0.0150 mg/L | 13/13 | LCR | 2025 |
| Arsenic | 8.005 µg/L 80% of the EPA limit 10 µg/L
worst single sample: 8.3 µg/L | 2/6 | SYR4 | 2012–2017 |
| Barium | 52.47 µg/L 2.6% of the EPA limit 2000 µg/L
worst single sample: 52.6 µg/L | 2/2 | SYR4 | 2014–2017 |
| Dibromochloromethane | 1.095 µg/L No EPA limit set
worst single sample: 1.1 µg/L | 2/61 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 689 µg/L 6.9% of the EPA limit 10000 µg/L
worst single sample: 700 µg/L | 2/3 | SYR4 | 2012–2015 |
| Nitrite | 10 µg/L 1% of the EPA limit 1000 µg/L | 2/3 | SYR4 | 2012–2015 |
| Atrazine | 0.1600 µg/L 5.3% of the EPA limit 3 µg/L | 1/2 | SYR4 | 2015–2018 |
| Combined Radium (-226 And -228) | 1.5 pCi/L 30% of the EPA limit 5 pCi/L | 1/1 | SYR4 | 2016 |
| Dibromoacetic Acid | 1 µg/L No EPA limit set | 1/53 | SYR4 | 2013–2019 |
| Fluoride | 120 µg/L 3% of the EPA limit 4000 µg/L | 1/2 | SYR4 | 2014–2017 |
| Simazine | 0.0900 µg/L 2.3% of the EPA limit 4 µg/L | 1/2 | SYR4 | 2015–2018 |
85 contaminants tested, none detected
Utility contact
Frequently asked questions about Louetta North Pud
Is Louetta North Pud tap water safe to drink?
EPA monitoring detected 24 contaminants in Louetta North Pud's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Louetta North Pud's water?
EPA monitoring detected Chloroform, Bromodichloromethane, Copper, Dichloroacetic Acid, TTHM, and others. The full list with the level and data source for each is above.
How many people does Louetta North Pud serve?
Louetta North Pud reports serving 4,848 people in Texas, per its EPA record.
Has Louetta North Pud had any water quality violations?
The EPA has no formal drinking-water violations on file for Louetta North Pud.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.