Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2008-04-01 → 2008-04-30 |
| MCL | Health-based | Resolved | 2008-04-01 → 2008-04-30 |
| MCL | Health-based | Resolved | 2008-04-01 → 2008-04-30 |
| MCL | Health-based | Resolved | 2008-04-01 → 2008-04-30 |
| MCL | Health-based | Resolved | 2008-04-01 → 2008-04-30 |
| MCL | Health-based | Archived | 1991-09-01 → 1991-09-30 |
| RPT | Monitoring | Resolved | 2025-07-02 |
| RPT | Monitoring | Resolved | 2025-07-02 |
| MR | Monitoring | Unaddressed | 2024-02-14 |
| MR | Monitoring | Unaddressed | 2024-02-14 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 7.72 µg/L No EPA limit set
worst single sample: 19.7 µg/L | 135/136 | SYR4 | 2012–2019 |
| Chloroform | 20.7 µg/L No EPA limit set
worst single sample: 35 µg/L | 135/136 | SYR4 | 2012–2019 |
| TTHM | 29.075 µg/L 36% of the EPA limit 80 µg/L
worst single sample: 79.4 µg/L | 126/126 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 19.12 µg/L No EPA limit set
worst single sample: 32.7 µg/L | 125/126 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 27.92 µg/L 47% of the EPA limit 60 µg/L
worst single sample: 58.6 µg/L | 125/126 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 7.015 µg/L No EPA limit set
worst single sample: 9 µg/L | 120/126 | SYR4 | 2012–2019 |
| Copper | 1200 µg/L 92% of the EPA limit 1300 µg/L
worst single sample: 2290 µg/L | 107/125 | SYR4 | 2013–2018 |
| Dibromochloromethane | 2.6 µg/L No EPA limit set
worst single sample: 28.6 µg/L | 97/136 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 1.47 µg/L No EPA limit set
worst single sample: 2.9 µg/L | 47/126 | SYR4 | 2012–2019 |
| Nitrate | 700.5 µg/L 7% of the EPA limit 10000 µg/L
worst single sample: 750 µg/L | 32/32 | SYR4 | 2012–2019 |
| Lead | 4.525 µg/L 30% of the EPA limit 15 µg/L
worst single sample: 11 µg/L | 26/125 | SYR4 | 2013–2018 |
| Atrazine | 0.1900 µg/L 6.3% of the EPA limit 3 µg/L
worst single sample: 0.2600 µg/L | 24/29 | SYR4 | 2012–2019 |
| Lead | 0.0029 mg/L 19% of the EPA limit 0.0150 mg/L | 17/17 | LCR | 2025 |
| Monochloroacetic Acid | 10.48 µg/L No EPA limit set
worst single sample: 14.8 µg/L | 13/126 | SYR4 | 2012–2019 |
| Simazine | 0.1340 µg/L 3.4% of the EPA limit 4 µg/L
worst single sample: 0.1500 µg/L | 9/29 | SYR4 | 2012–2019 |
| Barium | 157.75 µg/L 7.9% of the EPA limit 2000 µg/L
worst single sample: 161 µg/L | 6/6 | SYR4 | 2016–2019 |
| Nitrate-Nitrite | 682.5 µg/L 6.8% of the EPA limit 10000 µg/L
worst single sample: 760 µg/L | 6/6 | SYR4 | 2012–2015 |
| Arsenic | 2.82 µg/L 28% of the EPA limit 10 µg/L
worst single sample: 2.9 µg/L | 5/6 | SYR4 | 2016–2019 |
| Lithium | 17.9 µg/L No EPA limit set | 5/8 | UCMR-5 | 2023 |
| Cyanide | 115.5 µg/L 58% of the EPA limit 200 µg/L
worst single sample: 120 µg/L | 4/4 | SYR4 | 2014–2017 |
| Fluoride | 340 µg/L 8.5% of the EPA limit 4000 µg/L | 4/4 | SYR4 | 2014–2017 |
| Nitrite | 19 µg/L 1.9% of the EPA limit 1000 µg/L
worst single sample: 20 µg/L | 3/6 | SYR4 | 2012–2015 |
| Hexachlorocyclopentadiene | 0.1570 µg/L 0.3% of the EPA limit 50 µg/L
worst single sample: 0.1600 µg/L | 2/29 | SYR4 | 2012–2019 |
| Bromoform | 21.8 µg/L No EPA limit set | 1/136 | SYR4 | 2012–2019 |
| Combined Uranium | 1.9 µg/L 6.3% of the EPA limit 30 µg/L | 1/3 | SYR4 | 2014–2017 |
| Di(2-ethylhexyl) Phthalate | 0.6100 µg/L 10% of the EPA limit 6 µg/L | 1/29 | SYR4 | 2012–2019 |
| Gross Alpha, Excl. Radon And U | 5 pCi/L 33% of the EPA limit 15 pCi/L | 1/3 | SYR4 | 2014–2017 |
| Monobromoacetic Acid | 2.1 µg/L No EPA limit set | 1/126 | SYR4 | 2012–2019 |
75 contaminants tested, none detected
Utility contact
Frequently asked questions about City of West University Place
Is City of West University Place tap water safe to drink?
EPA monitoring detected 34 contaminants in City of West University Place's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in City of West University Place's water?
EPA monitoring detected Bromodichloromethane, Chloroform, TTHM, Dichloroacetic Acid, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does City of West University Place serve?
City of West University Place reports serving 19,200 people in Texas, per its EPA record.
Has City of West University Place had any water quality violations?
The EPA has 73 violations on file for City of West University Place, of which 6 are health-based (a contaminant limit or required treatment was breached) and 4 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.