← Texas

Tap water quality report

City of West University Place

EPA monitoring tested this supplier for 109 contaminants and detected 34. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

109
contaminants tested
34
detected
19,200
people served
6
health-based violations
Water source
SWP
Ownership
Local government
Counties served
Harris

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

6
health-based violations
73
violations on file
4
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2008-04-01 → 2008-04-30
MCL Health-based Resolved 2008-04-01 → 2008-04-30
MCL Health-based Resolved 2008-04-01 → 2008-04-30
MCL Health-based Resolved 2008-04-01 → 2008-04-30
MCL Health-based Resolved 2008-04-01 → 2008-04-30
MCL Health-based Archived 1991-09-01 → 1991-09-30
RPT Monitoring Resolved 2025-07-02
RPT Monitoring Resolved 2025-07-02
MR Monitoring Unaddressed 2024-02-14
MR Monitoring Unaddressed 2024-02-14

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
Pfba 0.0103 µg/L 5/8 2024
Pfhxa 0.0085 µg/L 5/8 2024
PFOS 0.0054 µg/L 5/8 2024
Pfpea 0.0088 µg/L 5/8 2024
PFHXS 0.0039 µg/L 4/8 2024
PFBS 0.0051 µg/L 3/8 2024

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Bromodichloromethane
7.72 µg/L
No EPA limit set
worst single sample: 19.7 µg/L
135/136 SYR4 2012–2019
Chloroform
20.7 µg/L
No EPA limit set
worst single sample: 35 µg/L
135/136 SYR4 2012–2019
TTHM
29.075 µg/L 36%
of the EPA limit 80 µg/L
worst single sample: 79.4 µg/L
126/126 SYR4 2012–2019
Dichloroacetic Acid
19.12 µg/L
No EPA limit set
worst single sample: 32.7 µg/L
125/126 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
27.92 µg/L 47%
of the EPA limit 60 µg/L
worst single sample: 58.6 µg/L
125/126 SYR4 2012–2019
Trichloroacetic Acid
7.015 µg/L
No EPA limit set
worst single sample: 9 µg/L
120/126 SYR4 2012–2019
Copper
1200 µg/L 92%
of the EPA limit 1300 µg/L
worst single sample: 2290 µg/L
107/125 SYR4 2013–2018
Dibromochloromethane
2.6 µg/L
No EPA limit set
worst single sample: 28.6 µg/L
97/136 SYR4 2012–2019
Dibromoacetic Acid
1.47 µg/L
No EPA limit set
worst single sample: 2.9 µg/L
47/126 SYR4 2012–2019
Nitrate
700.5 µg/L 7%
of the EPA limit 10000 µg/L
worst single sample: 750 µg/L
32/32 SYR4 2012–2019
Lead
4.525 µg/L 30%
of the EPA limit 15 µg/L
worst single sample: 11 µg/L
26/125 SYR4 2013–2018
Atrazine
0.1900 µg/L 6.3%
of the EPA limit 3 µg/L
worst single sample: 0.2600 µg/L
24/29 SYR4 2012–2019
Lead
0.0029 mg/L 19%
of the EPA limit 0.0150 mg/L
17/17 LCR 2025
Monochloroacetic Acid
10.48 µg/L
No EPA limit set
worst single sample: 14.8 µg/L
13/126 SYR4 2012–2019
Simazine
0.1340 µg/L 3.4%
of the EPA limit 4 µg/L
worst single sample: 0.1500 µg/L
9/29 SYR4 2012–2019
Barium
157.75 µg/L 7.9%
of the EPA limit 2000 µg/L
worst single sample: 161 µg/L
6/6 SYR4 2016–2019
Nitrate-Nitrite
682.5 µg/L 6.8%
of the EPA limit 10000 µg/L
worst single sample: 760 µg/L
6/6 SYR4 2012–2015
Arsenic
2.82 µg/L 28%
of the EPA limit 10 µg/L
worst single sample: 2.9 µg/L
5/6 SYR4 2016–2019
Lithium
17.9 µg/L
No EPA limit set
5/8 UCMR-5 2023
Cyanide
115.5 µg/L 58%
of the EPA limit 200 µg/L
worst single sample: 120 µg/L
4/4 SYR4 2014–2017
Fluoride
340 µg/L 8.5%
of the EPA limit 4000 µg/L
4/4 SYR4 2014–2017
Nitrite
19 µg/L 1.9%
of the EPA limit 1000 µg/L
worst single sample: 20 µg/L
3/6 SYR4 2012–2015
Hexachlorocyclopentadiene
0.1570 µg/L 0.3%
of the EPA limit 50 µg/L
worst single sample: 0.1600 µg/L
2/29 SYR4 2012–2019
Bromoform
21.8 µg/L
No EPA limit set
1/136 SYR4 2012–2019
Combined Uranium
1.9 µg/L 6.3%
of the EPA limit 30 µg/L
1/3 SYR4 2014–2017
Di(2-ethylhexyl) Phthalate
0.6100 µg/L 10%
of the EPA limit 6 µg/L
1/29 SYR4 2012–2019
Gross Alpha, Excl. Radon And U
5 pCi/L 33%
of the EPA limit 15 pCi/L
1/3 SYR4 2014–2017
Monobromoacetic Acid
2.1 µg/L
No EPA limit set
1/126 SYR4 2012–2019
75 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAsbestosBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumCombined Radium (-226 And -228)DichloromethaneDalaponDi(2-ethylhexyl) AdipateDinosebEthylene DibromideEndrinEthylbenzeneGross Beta Particle ActivityHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaOxamylPfdaPfdoaPfeesaPfhpaPfhpsPfmbaPfmpaPFNAPFOAPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
SAMPLE, SUSAN
Phone
713-668-4441
Email
[email protected]

Frequently asked questions about City of West University Place

Is City of West University Place tap water safe to drink?

EPA monitoring detected 34 contaminants in City of West University Place's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in City of West University Place's water?

EPA monitoring detected Bromodichloromethane, Chloroform, TTHM, Dichloroacetic Acid, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.

How many people does City of West University Place serve?

City of West University Place reports serving 19,200 people in Texas, per its EPA record.

Has City of West University Place had any water quality violations?

The EPA has 73 violations on file for City of West University Place, of which 6 are health-based (a contaminant limit or required treatment was breached) and 4 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.