← Texas

Tap water quality report

Tanglewood on Texoma

EPA monitoring tested this supplier for 109 contaminants and detected 34. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

109
contaminants tested
34
detected
4,341
people served
43
health-based violations
Water source
SWP
Ownership
Private
Counties served
Grayson

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

43
health-based violations
109
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2015-01-01 → 2015-03-31
MCL Health-based Resolved 2015-01-01 → 2015-03-31
MCL Health-based Resolved 2015-01-01 → 2015-03-31
MCL Health-based Resolved 2015-01-01 → 2015-03-31
MCL Health-based Resolved 2015-01-01 → 2015-03-31
MCL Health-based Resolved 2015-01-01 → 2015-03-31
MCL Health-based Resolved 2014-10-01 → 2014-12-31
MCL Health-based Resolved 2014-10-01 → 2014-12-31
MCL Health-based Resolved 2014-10-01 → 2014-12-31
MCL Health-based Resolved 2014-10-01 → 2014-12-31

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
PFBS 0.0102 µg/L 3/10 2025
PFHXS 0.0280 µg/L 3/10 2025
Pfhxa 0.0060 µg/L 2/10 2025
Pfba 0.0050 µg/L 1/10 2025
Pfpea 0.0041 µg/L 1/10 2025
Pfpes 0.0052 µg/L 1/10 2025

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
320 µg/L 25%
of the EPA limit 1300 µg/L
worst single sample: 735 µg/L
84/85 SYR4 2012–2019
Nitrate
2937.5 µg/L 29%
of the EPA limit 10000 µg/L
worst single sample: 3020 µg/L
66/70 SYR4 2012–2019
Bromoform
48.63 µg/L
No EPA limit set
worst single sample: 184 µg/L
62/77 SYR4 2012–2019
TTHM
102.4 µg/L 128%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 308.7 µg/L
54/58 SYR4 2012–2019
Dibromochloromethane
32.345 µg/L
No EPA limit set
worst single sample: 75.8 µg/L
52/77 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
37.27 µg/L 62%
of the EPA limit 60 µg/L
worst single sample: 50.6 µg/L
52/57 SYR4 2012–2019
Dibromoacetic Acid
14.5 µg/L
No EPA limit set
worst single sample: 20.1 µg/L
49/57 SYR4 2012–2019
Lead
6.674 µg/L 44%
of the EPA limit 15 µg/L
worst single sample: 7.83 µg/L
45/85 SYR4 2012–2019
Bromodichloromethane
30.685 µg/L
No EPA limit set
worst single sample: 36.7 µg/L
34/77 SYR4 2012–2019
Trichloroacetic Acid
12.7 µg/L
No EPA limit set
worst single sample: 16.8 µg/L
31/57 SYR4 2012–2019
Monochloroacetic Acid
9.76 µg/L
No EPA limit set
worst single sample: 10.6 µg/L
29/57 SYR4 2012–2019
Chloroform
23.565 µg/L
No EPA limit set
worst single sample: 47.3 µg/L
28/77 SYR4 2012–2019
Dichloroacetic Acid
15.7 µg/L
No EPA limit set
worst single sample: 26.6 µg/L
24/57 SYR4 2012–2019
Monobromoacetic Acid
3.1 µg/L
No EPA limit set
worst single sample: 3.5 µg/L
17/57 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
15/15 LCR 2026
Nitrate-Nitrite
2726 µg/L 27%
of the EPA limit 10000 µg/L
worst single sample: 3020 µg/L
15/16 SYR4 2012–2019
Lithium
40.3 µg/L
No EPA limit set
10/10 UCMR-5 2025
Barium
81 µg/L 4.1%
of the EPA limit 2000 µg/L
worst single sample: 84 µg/L
6/6 SYR4 2014–2019
Fluoride
1540 µg/L 39%
of the EPA limit 4000 µg/L
worst single sample: 1710 µg/L
6/6 SYR4 2014–2017
Chromium
3.07 µg/L 3.1%
of the EPA limit 100 µg/L
worst single sample: 3.4 µg/L
4/6 SYR4 2014–2019
Xylenes, Total
10.3955 µg/L 0.1%
of the EPA limit 10000 µg/L
worst single sample: 11.6 µg/L
4/20 SYR4 2012–2019
Combined Radium (-226 And -228)
1.208 pCi/L 24%
of the EPA limit 5 pCi/L
worst single sample: 1.22 pCi/L
3/3 SYR4 2012–2018
Arsenic
2.2315 µg/L 22%
of the EPA limit 10 µg/L
worst single sample: 2.3 µg/L
2/6 SYR4 2014–2019
Ethylbenzene
2.14465 µg/L 0.3%
of the EPA limit 700 µg/L
worst single sample: 2.23 µg/L
2/20 SYR4 2012–2019
Selenium
12.44 µg/L 25%
of the EPA limit 50 µg/L
worst single sample: 13 µg/L
2/6 SYR4 2014–2019
Combined Uranium
1.4 µg/L 4.7%
of the EPA limit 30 µg/L
1/3 SYR4 2014–2018
Gross Alpha, Excl. Radon And U
5.3 pCi/L 35%
of the EPA limit 15 pCi/L
1/3 SYR4 2014–2018
Nitrite
1500 µg/L 150%
of the EPA limit, at the 95th percentile of samples — 1000 µg/L
1/34 SYR4 2012–2019
75 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebEthylene DibromideEndrinGross Beta Particle ActivityHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaOxamylPfdaPfdoaPfeesaPfhpaPfhpsPfmbaPfmpaPFNAPFOAPFOSPftaPftrdaPfunaPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
BARRY, CHUCK
Phone
737-376-2534
Email
[email protected]

Frequently asked questions about Tanglewood on Texoma

Is Tanglewood on Texoma tap water safe to drink?

EPA monitoring detected 34 contaminants in Tanglewood on Texoma's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Tanglewood on Texoma's water?

EPA monitoring detected Copper, Nitrate, Bromoform, TTHM, Dibromochloromethane, and others. The full list with the level and data source for each is above.

How many people does Tanglewood on Texoma serve?

Tanglewood on Texoma reports serving 4,341 people in Texas, per its EPA record.

Has Tanglewood on Texoma had any water quality violations?

The EPA has 109 violations on file for Tanglewood on Texoma, of which 43 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.