Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Unaddressed | 2025-10-01 |
| TT | Health-based | Unaddressed | 2025-10-01 |
| TT | Health-based | Resolved | 2025-04-01 |
| TT | Health-based | Resolved | 2025-04-01 |
| TT | Health-based | Resolved | 2025-04-01 |
| TT | Health-based | Unaddressed | 2025-03-31 |
| TT | Health-based | Unaddressed | 2025-03-31 |
| TT | Health-based | Resolved | 2024-12-01 |
| TT | Health-based | Resolved | 2024-12-01 |
| TT | Health-based | Resolved | 2024-12-01 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 224.5 µg/L 17% of the EPA limit 1300 µg/L
worst single sample: 247 µg/L | 32/32 | SYR4 | 2012–2018 |
| Nitrate | 84.28 µg/L 0.8% of the EPA limit 10000 µg/L
worst single sample: 84.5 µg/L | 32/32 | SYR4 | 2012–2019 |
| Bromodichloromethane | 6.11 µg/L No EPA limit set
worst single sample: 6.96 µg/L | 18/18 | SYR4 | 2013–2019 |
| Dibromochloromethane | 7.486 µg/L No EPA limit set
worst single sample: 7.69 µg/L | 18/18 | SYR4 | 2013–2019 |
| Chloroform | 3.774 µg/L No EPA limit set
worst single sample: 4.95 µg/L | 17/18 | SYR4 | 2013–2019 |
| Bromoform | 2.725 µg/L No EPA limit set
worst single sample: 2.8 µg/L | 16/18 | SYR4 | 2013–2019 |
| Lead | 0.0026 mg/L 17% of the EPA limit 0.0150 mg/L | 11/11 | LCR | 2025 |
| Lead | 1.564 µg/L 10% of the EPA limit 15 µg/L
worst single sample: 1.7 µg/L | 9/32 | SYR4 | 2012–2018 |
| Dichloroacetic Acid | 2.16 µg/L No EPA limit set
worst single sample: 2.3 µg/L | 8/8 | SYR4 | 2013–2019 |
| TTHM | 20.23 µg/L 25% of the EPA limit 80 µg/L
worst single sample: 21 µg/L | 8/8 | SYR4 | 2013–2019 |
| Total Haloacetic Acids (HAA5) | 7.31 µg/L 12% of the EPA limit 60 µg/L
worst single sample: 7.8 µg/L | 8/8 | SYR4 | 2013–2019 |
| Dibromoacetic Acid | 3.29 µg/L No EPA limit set
worst single sample: 3.5 µg/L | 7/8 | SYR4 | 2013–2019 |
| Nitrate-Nitrite | 66.5 µg/L 0.7% of the EPA limit 10000 µg/L
worst single sample: 67 µg/L | 6/6 | SYR4 | 2012–2015 |
| Barium | 31 µg/L 1.6% of the EPA limit 2000 µg/L | 4/4 | SYR4 | 2016–2019 |
| Chromium | 2.555 µg/L 2.6% of the EPA limit 100 µg/L
worst single sample: 2.6 µg/L | 4/4 | SYR4 | 2016–2019 |
| Fluoride | 205.7 µg/L 5.1% of the EPA limit 4000 µg/L
worst single sample: 212 µg/L | 4/4 | SYR4 | 2014–2017 |
| Lithium | 11.2 µg/L No EPA limit set | 4/4 | UCMR-5 | 2024 |
| Combined Radium (-226 And -228) | 1.5 pCi/L 30% of the EPA limit 5 pCi/L | 2/2 | SYR4 | 2015 |
| Trichloroacetic Acid | 1.3 µg/L No EPA limit set | 2/8 | SYR4 | 2013–2019 |
| Di(2-ethylhexyl) Phthalate | 0.5000 µg/L 8.3% of the EPA limit 6 µg/L | 1/8 | SYR4 | 2015–2019 |
| Monochloroacetic Acid | 3.2 µg/L No EPA limit set | 1/8 | SYR4 | 2013–2019 |
88 contaminants tested, none detected
Utility contact
Frequently asked questions about City of Fairfield
Is City of Fairfield tap water safe to drink?
EPA monitoring detected 21 contaminants in City of Fairfield's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in City of Fairfield's water?
EPA monitoring detected Copper, Nitrate, Bromodichloromethane, Dibromochloromethane, Chloroform, and others. The full list with the level and data source for each is above.
How many people does City of Fairfield serve?
City of Fairfield reports serving 3,005 people in Texas, per its EPA record.
Has City of Fairfield had any water quality violations?
The EPA has 51 violations on file for City of Fairfield, of which 11 are health-based (a contaminant limit or required treatment was breached) and 15 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.