← Texas

Tap water quality report

City of Balch Springs

EPA monitoring tested this supplier for 44 contaminants and detected 19. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

44
contaminants tested
19
detected
28,300
people served
23
health-based violations
Water source
SWP
Ownership
Local government
Counties served
Dallas

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

23
health-based violations
44
violations on file
2
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2024-10-17
TT Health-based Resolved 2024-10-17
TT Health-based Resolved 2024-10-17
MCL Health-based Resolved 2007-08-01 → 2007-08-31
MCL Health-based Resolved 2007-08-01 → 2007-08-31
MCL Health-based Resolved 2007-08-01 → 2007-08-31
MCL Health-based Resolved 2007-07-01 → 2007-09-30
MCL Health-based Resolved 2007-07-01 → 2007-09-30
MCL Health-based Resolved 2007-07-01 → 2007-09-30
MCL Health-based Resolved 2007-07-01 → 2007-09-30

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
Pfba 0.0092 µg/L 8/8 2025
Pfhxa 0.0050 µg/L 7/8 2025
Pfpea 0.0046 µg/L 6/8 2025
PFBS 0.0038 µg/L 5/8 2025
PFOS 0.0042 µg/L 1/8 2025

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Bromodichloromethane
6.852 µg/L
No EPA limit set
worst single sample: 10.7 µg/L
128/128 SYR4 2012–2019
Chloroform
9.494 µg/L
No EPA limit set
worst single sample: 15.5 µg/L
128/128 SYR4 2012–2019
TTHM
17.565 µg/L 22%
of the EPA limit 80 µg/L
worst single sample: 35.6 µg/L
128/128 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
18.325 µg/L 31%
of the EPA limit 60 µg/L
worst single sample: 22.5 µg/L
126/128 SYR4 2012–2019
Dibromochloromethane
5.074 µg/L
No EPA limit set
worst single sample: 7.6 µg/L
125/128 SYR4 2012–2019
Dichloroacetic Acid
11.765 µg/L
No EPA limit set
worst single sample: 18.5 µg/L
120/128 SYR4 2012–2019
Copper
432.5 µg/L 33%
of the EPA limit 1300 µg/L
worst single sample: 1100 µg/L
90/90 SYR4 2013–2017
Trichloroacetic Acid
2.725 µg/L
No EPA limit set
worst single sample: 3.9 µg/L
86/128 SYR4 2012–2019
Dibromoacetic Acid
2.58 µg/L
No EPA limit set
worst single sample: 11 µg/L
65/128 SYR4 2012–2019
Monochloroacetic Acid
6.615 µg/L
No EPA limit set
worst single sample: 8.6 µg/L
52/128 SYR4 2012–2019
Bromoform
2.4 µg/L
No EPA limit set
worst single sample: 2.7 µg/L
51/128 SYR4 2012–2019
Lead
43.745 µg/L 292%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 110 µg/L
24/90 SYR4 2013–2017
Monobromoacetic Acid
1.3 µg/L
No EPA limit set
worst single sample: 1.4 µg/L
23/128 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
15/15 LCR 2023
25 contaminants tested, none detected
11Cl-PF3OUdS4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaHfpo-DaNetfosaaNfdhaNmefosaaPfdaPfdoaPfeesaPfhpaPfhpsPFHXSPfmbaPfmpaPFNAPFOAPfpesPftaPftrdaPfunaLithium

Utility contact

Contact
GORDON, CARRIE
Phone
972-286-4477

Frequently asked questions about City of Balch Springs

Is City of Balch Springs tap water safe to drink?

EPA monitoring detected 19 contaminants in City of Balch Springs's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in City of Balch Springs's water?

EPA monitoring detected Bromodichloromethane, Chloroform, TTHM, Total Haloacetic Acids (HAA5), Dibromochloromethane, and others. The full list with the level and data source for each is above.

How many people does City of Balch Springs serve?

City of Balch Springs reports serving 28,300 people in Texas, per its EPA record.

Has City of Balch Springs had any water quality violations?

The EPA has 44 violations on file for City of Balch Springs, of which 23 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.