← Texas

Tap water quality report

Eula Wsc

EPA monitoring tested this supplier for 44 contaminants and detected 23. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

44
contaminants tested
23
detected
3,918
people served
73
health-based violations
Water source
SWP
Ownership
Local government
Counties served
Callahan

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

73
health-based violations
145
violations on file
4
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2025-01-01 → 2025-03-31
MCL Health-based Resolved 2025-01-01 → 2025-03-31
MCL Health-based Resolved 2025-01-01 → 2025-03-31
MCL Health-based Resolved 2025-01-01 → 2025-03-31
MCL Health-based Resolved 2024-10-01 → 2024-12-31
MCL Health-based Resolved 2024-10-01 → 2024-12-31
MCL Health-based Resolved 2024-10-01 → 2024-12-31
MCL Health-based Resolved 2024-10-01 → 2024-12-31
MCL Health-based Resolved 2024-07-01 → 2024-09-30
MCL Health-based Resolved 2024-07-01 → 2024-09-30

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
Pfba 0.0310 µg/L 5/8 2024
PFBS 0.0059 µg/L 5/8 2024
PFHXS 0.0213 µg/L 4/8 2024
Pfpea 0.0130 µg/L 4/8 2024
Pfhpa 0.0075 µg/L 3/8 2024
Pfhxa 0.0160 µg/L 3/8 2024
PFOS 0.0200 µg/L 3/8 2024
PFOA 0.0062 µg/L 2/8 2024

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Bromoform
95.01 µg/L
No EPA limit set
worst single sample: 187 µg/L
55/55 SYR4 2012–2019
Dibromochloromethane
39.84 µg/L
No EPA limit set
worst single sample: 67.7 µg/L
55/55 SYR4 2012–2019
TTHM
171.1 µg/L 214%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 234 µg/L
55/55 SYR4 2012–2019
Bromodichloromethane
24.03 µg/L
No EPA limit set
worst single sample: 37.1 µg/L
54/55 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
33 µg/L 55%
of the EPA limit 60 µg/L
worst single sample: 50.3 µg/L
51/55 SYR4 2012–2019
Dibromoacetic Acid
24.1 µg/L
No EPA limit set
worst single sample: 43.6 µg/L
45/55 SYR4 2012–2019
Dichloroacetic Acid
6.26 µg/L
No EPA limit set
worst single sample: 7.6 µg/L
33/55 SYR4 2012–2019
Chloroform
24.525 µg/L
No EPA limit set
worst single sample: 25.2 µg/L
32/55 SYR4 2012–2019
Monobromoacetic Acid
3.32 µg/L
No EPA limit set
worst single sample: 6.1 µg/L
27/55 SYR4 2012–2019
Monochloroacetic Acid
7.335 µg/L
No EPA limit set
worst single sample: 8.6 µg/L
12/55 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
11/11 LCR 2025
Trichloroacetic Acid
2.9 µg/L
No EPA limit set
worst single sample: 4 µg/L
11/55 SYR4 2012–2019
Copper
126.3 µg/L 9.7%
of the EPA limit 1300 µg/L
worst single sample: 129 µg/L
7/50 SYR4 2015–2019
Lead
10.6 µg/L 71%
of the EPA limit 15 µg/L
7/50 SYR4 2015–2019
Lithium
11.9 µg/L
No EPA limit set
2/8 UCMR-5 2023
21 contaminants tested, none detected
11Cl-PF3OUdS4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaHfpo-DaNetfosaaNfdhaNmefosaaPfdaPfdoaPfeesaPfhpsPfmbaPfmpaPFNAPfpesPftaPftrdaPfuna

Utility contact

Contact
FARMER, BRYAN
Phone
325-529-3555
Email
[email protected]

Frequently asked questions about Eula Wsc

Is Eula Wsc tap water safe to drink?

EPA monitoring detected 23 contaminants in Eula Wsc's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Eula Wsc's water?

EPA monitoring detected Bromoform, Dibromochloromethane, TTHM, Bromodichloromethane, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.

How many people does Eula Wsc serve?

Eula Wsc reports serving 3,918 people in Texas, per its EPA record.

Has Eula Wsc had any water quality violations?

The EPA has 145 violations on file for Eula Wsc, of which 73 are health-based (a contaminant limit or required treatment was breached) and 4 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.