← Texas

Tap water quality report

Patriot Rv Park Burnet

EPA monitoring tested this supplier for 79 contaminants and detected 13. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

79
contaminants tested
13
detected
90
people served
7
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Burnet

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

7
health-based violations
598
violations on file
2
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2024-10-17
TT Health-based Resolved 2024-10-17
TT Health-based Resolved 2024-10-17
TT Health-based Resolved 2024-10-17
MCL Health-based Resolved 2005-04-01 → 2005-04-30
MCL Health-based Resolved 2005-04-01 → 2005-04-30
MCL Health-based Resolved 2005-04-01 → 2005-04-30
MR Monitoring Unaddressed 2026-01-01
MR Monitoring Unaddressed 2026-01-01
Other Monitoring Resolved 2025-05-01

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
2150 µg/L 22%
of the EPA limit 10000 µg/L
16/16 SYR4 2012–2019
Bromoform
1.61 µg/L
No EPA limit set
worst single sample: 1.7 µg/L
4/11 SYR4 2012–2019
Barium
178.8 µg/L 8.9%
of the EPA limit 2000 µg/L
worst single sample: 180 µg/L
3/3 SYR4 2013–2019
Combined Radium (-226 And -228)
1.5 pCi/L 30%
of the EPA limit 5 pCi/L
3/3 SYR4 2013–2019
Combined Uranium
1.29 µg/L 4.3%
of the EPA limit 30 µg/L
worst single sample: 1.3 µg/L
3/3 SYR4 2013–2019
Fluoride
317 µg/L 7.9%
of the EPA limit 4000 µg/L
worst single sample: 320 µg/L
3/3 SYR4 2013–2019
Nitrate-Nitrite
1935 µg/L 19%
of the EPA limit 10000 µg/L
worst single sample: 1940 µg/L
3/3 SYR4 2012–2015
Dibromochloromethane
1.48 µg/L
No EPA limit set
worst single sample: 1.5 µg/L
2/11 SYR4 2012–2019
Lead
0.0153 mg/L 102%
above the EPA limit of 0.0150 mg/L
2/2 LCR 2025
TTHM
2.715 µg/L 3.4%
of the EPA limit 80 µg/L
worst single sample: 2.8 µg/L
2/3 SYR4 2012–2019
Copper
3.6 µg/L 0.3%
of the EPA limit 1300 µg/L
1/2 SYR4 2013–2016
Chromium
5.44 µg/L 5.4%
of the EPA limit 100 µg/L
1/3 SYR4 2013–2019
Selenium
2.44 µg/L 4.9%
of the EPA limit 50 µg/L
1/3 SYR4 2013–2019
66 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalArsenicAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromodichloromethaneChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChloroformDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDibromoacetic AcidDichloroacetic AcidDinosebEthylene DibromideEndrinEthylbenzeneGross Alpha, Excl. Radon And UGross Beta Particle ActivityHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoLeadMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNitriteOxamylPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Haloacetic Acids (HAA5)ToxapheneTrichloroacetic AcidTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
COOLEY, TRAVIS
Phone
512-705-2454
Email
[email protected]

Frequently asked questions about Patriot Rv Park Burnet

Is Patriot Rv Park Burnet tap water safe to drink?

EPA monitoring detected 13 contaminants in Patriot Rv Park Burnet's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Patriot Rv Park Burnet's water?

EPA monitoring detected Nitrate, Bromoform, Barium, Combined Radium (-226 And -228), Combined Uranium, and others. The full list with the level and data source for each is above.

How many people does Patriot Rv Park Burnet serve?

Patriot Rv Park Burnet reports serving 90 people in Texas, per its EPA record.

Has Patriot Rv Park Burnet had any water quality violations?

The EPA has 598 violations on file for Patriot Rv Park Burnet, of which 7 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.