Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2023-10-01 → 2023-12-31 |
| MCL | Health-based | Resolved | 2023-10-01 → 2023-12-31 |
| MCL | Health-based | Resolved | 2023-10-01 → 2023-12-31 |
| MCL | Health-based | Resolved | 2023-10-01 → 2023-12-31 |
| MCL | Health-based | Resolved | 2023-07-01 → 2023-09-30 |
| MCL | Health-based | Resolved | 2023-07-01 → 2023-09-30 |
| MCL | Health-based | Resolved | 2023-07-01 → 2023-09-30 |
| MCL | Health-based | Resolved | 2023-07-01 → 2023-09-30 |
| MCL | Health-based | Resolved | 2023-04-01 → 2023-06-30 |
| MCL | Health-based | Resolved | 2023-04-01 → 2023-06-30 |
PFAS detected
| Contaminant | Max | Detection rate | Period |
|---|---|---|---|
| Pfba | 0.0167 µg/L | 1/4 | 2024 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 47.1 µg/L No EPA limit set
worst single sample: 56.5 µg/L | 66/66 | SYR4 | 2012–2019 |
| Chloroform | 95.475 µg/L No EPA limit set
worst single sample: 118 µg/L | 66/66 | SYR4 | 2012–2019 |
| Dibromochloromethane | 25.455 µg/L No EPA limit set
worst single sample: 32.9 µg/L | 64/66 | SYR4 | 2012–2019 |
| Copper | 247.5 µg/L 19% of the EPA limit 1300 µg/L
worst single sample: 745 µg/L | 63/65 | SYR4 | 2013–2019 |
| Dichloroacetic Acid | 62.15 µg/L No EPA limit set
worst single sample: 122 µg/L | 55/55 | SYR4 | 2012–2019 |
| TTHM | 176.5 µg/L 221% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 201 µg/L | 55/56 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 140.8 µg/L 235% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 233 µg/L | 55/55 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 70.82 µg/L No EPA limit set
worst single sample: 96 µg/L | 55/55 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 7.64 µg/L No EPA limit set
worst single sample: 10.3 µg/L | 53/55 | SYR4 | 2012–2019 |
| Bromoform | 4.565 µg/L No EPA limit set
worst single sample: 4.7 µg/L | 48/66 | SYR4 | 2012–2019 |
| Lead | 15.903 µg/L 106% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 41.8 µg/L | 32/65 | SYR4 | 2013–2019 |
| Nitrate | 410 µg/L 4.1% of the EPA limit 10000 µg/L | 18/18 | SYR4 | 2012–2019 |
| Lead | 0.0014 mg/L 9.5% of the EPA limit 0.0150 mg/L | 14/14 | LCR | 2024 |
| Monochloroacetic Acid | 10.205 µg/L No EPA limit set
worst single sample: 10.4 µg/L | 14/55 | SYR4 | 2012–2019 |
| Fluoride | 246.5 µg/L 6.2% of the EPA limit 4000 µg/L
worst single sample: 250 µg/L | 8/8 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 5.23 µg/L No EPA limit set
worst single sample: 6.7 µg/L | 8/55 | SYR4 | 2012–2019 |
| Barium | 76.06 µg/L 3.8% of the EPA limit 2000 µg/L
worst single sample: 77.5 µg/L | 7/7 | SYR4 | 2013–2019 |
| Cyanide | 197.5 µg/L 99% of the EPA limit 200 µg/L
worst single sample: 220 µg/L | 6/7 | SYR4 | 2012–2018 |
| Dalapon | 4.14 µg/L 2.1% of the EPA limit 200 µg/L
worst single sample: 4.4 µg/L | 5/55 | SYR4 | 2012–2019 |
| Lithium | 11.3 µg/L No EPA limit set | 2/4 | UCMR-5 | 2024 |
| Arsenic | 2.09 µg/L 21% of the EPA limit 10 µg/L | 1/7 | SYR4 | 2013–2019 |
| Atrazine | 0.1400 µg/L 4.7% of the EPA limit 3 µg/L | 1/9 | SYR4 | 2012–2019 |
| Chromium | 3.37 µg/L 3.4% of the EPA limit 100 µg/L | 1/7 | SYR4 | 2013–2019 |
| Selenium | 4.93 µg/L 9.9% of the EPA limit 50 µg/L | 1/7 | SYR4 | 2013–2019 |
| Thallium, Total | 0.3460 µg/L 17% of the EPA limit 2 µg/L | 1/7 | SYR4 | 2013–2019 |
| Toluene | 0.6700 µg/L 0.1% of the EPA limit 1000 µg/L | 1/11 | SYR4 | 2012–2019 |
| Xylenes, Total | 2 µg/L 0% of the EPA limit 10000 µg/L | 1/11 | SYR4 | 2012–2019 |
79 contaminants tested, none detected
Utility contact
Frequently asked questions about City of Granite Shoals
Is City of Granite Shoals tap water safe to drink?
EPA monitoring detected 28 contaminants in City of Granite Shoals's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in City of Granite Shoals's water?
EPA monitoring detected Bromodichloromethane, Chloroform, Dibromochloromethane, Copper, Dichloroacetic Acid, and others. The full list with the level and data source for each is above.
How many people does City of Granite Shoals serve?
City of Granite Shoals reports serving 6,795 people in Texas, per its EPA record.
Has City of Granite Shoals had any water quality violations?
The EPA has 401 violations on file for City of Granite Shoals, of which 213 are health-based (a contaminant limit or required treatment was breached) and 4 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.