Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2023-09-01 → 2023-09-30 |
| TT | Health-based | Resolved | 2023-09-01 → 2023-09-30 |
| TT | Health-based | Resolved | 2023-09-01 → 2023-09-30 |
| TT | Health-based | Resolved | 2023-09-01 → 2023-09-30 |
| TT | Health-based | Resolved | 2023-09-01 → 2023-09-30 |
| TT | Health-based | Resolved | 2023-09-01 → 2023-09-30 |
| TT | Health-based | Resolved | 2023-09-01 → 2023-09-30 |
| TT | Health-based | Resolved | 2023-09-01 → 2023-09-30 |
| TT | Health-based | Resolved | 2023-09-01 → 2023-09-30 |
| TT | Health-based | Resolved | 2023-09-01 → 2023-09-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Chlorite | 665 µg/L 67% of the EPA limit 1000 µg/L
worst single sample: 850 µg/L | 129/156 | SYR4 | 2013–2019 |
| Bromodichloromethane | 13.14 µg/L No EPA limit set
worst single sample: 19 µg/L | 39/39 | SYR4 | 2012–2019 |
| Chloroform | 8.63 µg/L No EPA limit set
worst single sample: 14.4 µg/L | 39/39 | SYR4 | 2012–2019 |
| Dibromochloromethane | 27.06 µg/L No EPA limit set
worst single sample: 36.1 µg/L | 39/39 | SYR4 | 2012–2019 |
| Bromoform | 24.14 µg/L No EPA limit set
worst single sample: 32.3 µg/L | 37/39 | SYR4 | 2012–2019 |
| Nitrate | 652.5 µg/L 6.5% of the EPA limit 10000 µg/L
worst single sample: 780 µg/L | 36/36 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 10.255 µg/L No EPA limit set
worst single sample: 14.6 µg/L | 24/24 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 12.61 µg/L No EPA limit set
worst single sample: 29.5 µg/L | 24/24 | SYR4 | 2012–2019 |
| TTHM | 80.4 µg/L 101% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 91.1 µg/L | 24/26 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 24.44 µg/L 41% of the EPA limit 60 µg/L
worst single sample: 39 µg/L | 24/24 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 3.565 µg/L No EPA limit set
worst single sample: 6.2 µg/L | 18/24 | SYR4 | 2012–2019 |
| Barium | 54.32 µg/L 2.7% of the EPA limit 2000 µg/L
worst single sample: 57.4 µg/L | 15/15 | SYR4 | 2012–2019 |
| Fluoride | 317 µg/L 7.9% of the EPA limit 4000 µg/L
worst single sample: 450 µg/L | 15/15 | SYR4 | 2012–2019 |
| Cyanide | 180 µg/L 90% of the EPA limit 200 µg/L | 12/12 | SYR4 | 2014–2019 |
| Atrazine | 0.2360 µg/L 7.9% of the EPA limit 3 µg/L
worst single sample: 0.2600 µg/L | 9/17 | SYR4 | 2012–2019 |
| Copper | 99.46 µg/L 7.7% of the EPA limit 1300 µg/L
worst single sample: 108 µg/L | 8/11 | SYR4 | 2012–2017 |
| Monobromoacetic Acid | 2.555 µg/L No EPA limit set
worst single sample: 2.6 µg/L | 4/24 | SYR4 | 2012–2019 |
| Arsenic | 1.11585 µg/L 11% of the EPA limit 10 µg/L
worst single sample: 1.13 µg/L | 2/15 | SYR4 | 2012–2019 |
| Chromium | 5.8625 µg/L 5.9% of the EPA limit 100 µg/L
worst single sample: 6.08 µg/L | 2/15 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 2.2 µg/L No EPA limit set | 1/24 | SYR4 | 2012–2019 |
| Xylenes, Total | 0.7000 µg/L 0% of the EPA limit 10000 µg/L | 1/15 | SYR4 | 2012–2019 |
56 contaminants tested, none detected
Utility contact
Frequently asked questions about Central Texas Wsc
Is Central Texas Wsc tap water safe to drink?
EPA monitoring detected 21 contaminants in Central Texas Wsc's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Central Texas Wsc's water?
EPA monitoring detected Chlorite, Bromodichloromethane, Chloroform, Dibromochloromethane, Bromoform, and others. The full list with the level and data source for each is above.
How many people does Central Texas Wsc serve?
Central Texas Wsc reports serving 0 people in Texas, per its EPA record.
Has Central Texas Wsc had any water quality violations?
The EPA has 141 violations on file for Central Texas Wsc, of which 56 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.