← Texas

Tap water quality report

Pleasure Point

EPA monitoring tested this supplier for 75 contaminants and detected 20. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

75
contaminants tested
20
detected
110
people served
197
health-based violations
Water source
Ground water
Ownership
Private
Counties served
Angelina

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

197
health-based violations
1,354
violations on file
44
still open
ViolationTypeStatusPeriod
TT Health-based Unaddressed 2024-10-17
TT Health-based Unaddressed 2024-10-17
TT Health-based Unaddressed 2024-10-17
TT Health-based Unaddressed 2024-10-17
MCL Health-based Resolved 2018-07-01 → 2018-09-30
MCL Health-based Resolved 2018-07-01 → 2018-09-30
MCL Health-based Resolved 2018-07-01 → 2018-09-30
MCL Health-based Resolved 2018-07-01 → 2018-09-30
MCL Health-based Resolved 2018-04-01 → 2018-06-30
MCL Health-based Resolved 2018-04-01 → 2018-06-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Chloroform
114.36 µg/L
No EPA limit set
worst single sample: 210.3 µg/L
33/38 SYR4 2012–2019
Bromodichloromethane
122.25 µg/L
No EPA limit set
worst single sample: 216.6 µg/L
31/38 SYR4 2012–2019
Dibromochloromethane
97.375 µg/L
No EPA limit set
worst single sample: 151.3 µg/L
30/38 SYR4 2012–2019
Bromoform
16.845 µg/L
No EPA limit set
worst single sample: 17.4 µg/L
28/38 SYR4 2012–2019
TTHM
337.34 µg/L 422%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 345.8 µg/L
28/32 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
108.705 µg/L 181%
of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 123 µg/L
28/32 SYR4 2012–2019
Trichloroacetic Acid
35.09 µg/L
No EPA limit set
worst single sample: 53.1 µg/L
27/32 SYR4 2012–2019
Dichloroacetic Acid
46.55 µg/L
No EPA limit set
worst single sample: 53.5 µg/L
26/32 SYR4 2012–2019
Dibromoacetic Acid
22.04 µg/L
No EPA limit set
worst single sample: 30.5 µg/L
25/32 SYR4 2012–2019
Monochloroacetic Acid
9.54 µg/L
No EPA limit set
worst single sample: 13.6 µg/L
15/32 SYR4 2012–2019
Monobromoacetic Acid
3.035 µg/L
No EPA limit set
worst single sample: 3.1 µg/L
14/32 SYR4 2012–2019
Nitrate
385 µg/L 3.9%
of the EPA limit 10000 µg/L
10/16 SYR4 2012–2019
Copper
5.14 µg/L 0.4%
of the EPA limit 1300 µg/L
worst single sample: 5.2 µg/L
7/12 SYR4 2014–2017
Lead
0.0037 mg/L 25%
of the EPA limit 0.0150 mg/L
6/6 LCR 2000
Lead
1.9 µg/L 13%
of the EPA limit 15 µg/L
worst single sample: 2 µg/L
5/12 SYR4 2014–2017
Fluoride
1007.3 µg/L 25%
of the EPA limit 4000 µg/L
worst single sample: 1010 µg/L
3/3 SYR4 2013–2019
Nitrate-Nitrite
354.65 µg/L 3.5%
of the EPA limit 10000 µg/L
worst single sample: 385 µg/L
3/3 SYR4 2012–2015
Barium
54.32 µg/L 2.7%
of the EPA limit 2000 µg/L
worst single sample: 54.6 µg/L
2/2 SYR4 2014–2017
Cyanide
41.3 µg/L 21%
of the EPA limit 200 µg/L
1/2 SYR4 2014–2018
Chromium
6.8 µg/L 6.8%
of the EPA limit 100 µg/L
1/2 SYR4 2014–2017
55 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalArsenicAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebEthylene DibromideEndrinEthylbenzeneHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNitriteOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
WILLIS, LEE, L
Phone
409-429-5712

Frequently asked questions about Pleasure Point

Is Pleasure Point tap water safe to drink?

EPA monitoring detected 20 contaminants in Pleasure Point's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Pleasure Point's water?

EPA monitoring detected Chloroform, Bromodichloromethane, Dibromochloromethane, Bromoform, TTHM, and others. The full list with the level and data source for each is above.

How many people does Pleasure Point serve?

Pleasure Point reports serving 110 people in Texas, per its EPA record.

Has Pleasure Point had any water quality violations?

The EPA has 1354 violations on file for Pleasure Point, of which 197 are health-based (a contaminant limit or required treatment was breached) and 44 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.