← Tennessee

Tap water quality report

Savannah Utility Dept

EPA monitoring tested this supplier for 59 contaminants and detected 7. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

59
contaminants tested
7
detected
19,495
people served
4
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Hardin

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

4
health-based violations
12
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2005-06-01 → 2005-06-30
MCL Health-based Resolved 2005-06-01 → 2005-06-30
MCL Health-based Resolved 2005-06-01 → 2005-06-30
MCL Health-based Resolved 2005-06-01 → 2005-06-30
MR Monitoring Resolved 2021-01-01 → 2021-03-31
MR Monitoring Resolved 2021-01-01 → 2021-03-31
MR Monitoring Resolved 2021-01-01 → 2021-03-31
MR Monitoring Resolved 2021-01-01 → 2021-03-31
MR Monitoring Resolved 2021-01-01 → 2021-03-31
MR Monitoring Resolved 2021-01-01 → 2021-03-31

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
PFBS 0.0041 µg/L 2/2 2023
PFOS 0.0158 µg/L 2/2 2023
Pfba 0.0063 µg/L 1/2 2023

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
TTHM
40.6 µg/L 51%
of the EPA limit 80 µg/L
worst single sample: 57.7 µg/L
96/96 SYR4 2014–2019
Total Haloacetic Acids (HAA5)
15.1 µg/L 25%
of the EPA limit 60 µg/L
worst single sample: 100 µg/L
96/96 SYR4 2014–2019
Lead
0.0010 mg/L 6.7%
of the EPA limit 0.0150 mg/L
11/11 LCR 2025
Nitrate
133 µg/L 1.3%
of the EPA limit 10000 µg/L
4/12 SYR4 2014–2019
52 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAtrazineBenzeneChlorobenzeneCarbon TetrachlorideDichloromethaneEthylbenzeneGross Alpha, Excl. Radon And UHfpo-DaLassoNetfosaaNfdhaNmefosaaPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPfpeaPfpesPftaPftrdaPfunaPicloramStyreneTetrachloroethyleneTolueneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
LITTLEFIELD, GREG
Phone
731-925-4216
Email
[email protected]

Frequently asked questions about Savannah Utility Dept

Is Savannah Utility Dept tap water safe to drink?

EPA monitoring detected 7 contaminants in Savannah Utility Dept's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Savannah Utility Dept's water?

EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Lead, Nitrate, PFBS, and others. The full list with the level and data source for each is above.

How many people does Savannah Utility Dept serve?

Savannah Utility Dept reports serving 19,495 people in Tennessee, per its EPA record.

Has Savannah Utility Dept had any water quality violations?

The EPA has 12 violations on file for Savannah Utility Dept, of which 4 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.