Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2011-01-01 → 2011-01-31 |
| MCL | Health-based | Resolved | 2011-01-01 → 2011-01-31 |
| MCL | Health-based | Resolved | 2011-01-01 → 2011-01-31 |
| MCL | Health-based | Resolved | 2011-01-01 → 2011-01-31 |
| MCL | Health-based | Archived | 1995-07-01 → 1995-07-31 |
| MR | Monitoring | Resolved | 2024-04-02 |
| MR | Monitoring | Resolved | 2024-04-02 |
| MR | Monitoring | Resolved | 2024-04-02 |
| MR | Monitoring | Resolved | 2024-04-02 |
| MR | Monitoring | Resolved | 2024-04-02 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 86 µg/L 6.6% of the EPA limit 1300 µg/L
worst single sample: 140 µg/L | 51/60 | SYR4 | 2012–2018 |
| Fluoride | 2400 µg/L 60% of the EPA limit 4000 µg/L | 24/24 | SYR4 | 2012–2019 |
| Lead | 7 µg/L 47% of the EPA limit 15 µg/L
worst single sample: 11 µg/L | 21/60 | SYR4 | 2012–2018 |
| Lead | 0.0029 mg/L 19% of the EPA limit 0.0150 mg/L | 17/17 | LCR | 2024 |
| Nitrate | 2400 µg/L 24% of the EPA limit 10000 µg/L | 8/64 | SYR4 | 2012–2019 |
| Bromodichloromethane | 11.874 µg/L No EPA limit set
worst single sample: 12.33 µg/L | 7/7 | SYR4 | 2013–2019 |
| Bromoform | 15.763 µg/L No EPA limit set
worst single sample: 21.58 µg/L | 7/7 | SYR4 | 2013–2019 |
| Dibromochloromethane | 11.173 µg/L No EPA limit set
worst single sample: 11.41 µg/L | 7/7 | SYR4 | 2013–2019 |
| TTHM | 35.127 µg/L 44% of the EPA limit 80 µg/L
worst single sample: 36.39 µg/L | 7/7 | SYR4 | 2013–2019 |
| Chloroform | 13.2528 µg/L No EPA limit set
worst single sample: 14.1004 µg/L | 6/7 | SYR4 | 2013–2019 |
| Dibromoacetic Acid | 3.47 µg/L No EPA limit set
worst single sample: 3.74 µg/L | 6/7 | SYR4 | 2013–2019 |
| Dichloroacetic Acid | 5.5375 µg/L No EPA limit set
worst single sample: 5.61 µg/L | 6/7 | SYR4 | 2013–2019 |
| Total Haloacetic Acids (HAA5) | 24.87 µg/L 41% of the EPA limit 60 µg/L
worst single sample: 26.84 µg/L | 6/7 | SYR4 | 2013–2019 |
| Trichloroacetic Acid | 5.1625 µg/L No EPA limit set
worst single sample: 5.84 µg/L | 6/7 | SYR4 | 2013–2019 |
| Monobromoacetic Acid | 12.328 µg/L No EPA limit set
worst single sample: 13.62 µg/L | 5/7 | SYR4 | 2013–2019 |
| Gross Alpha, Excl. Radon And U | 1.1039 pCi/L 7.4% of the EPA limit 15 pCi/L
worst single sample: 1.14 pCi/L | 3/8 | SYR4 | 2012–2019 |
| Antimony, Total | 0.1100 µg/L 1.8% of the EPA limit 6 µg/L | 1/12 | SYR4 | 2013–2019 |
| Cadmium | 0.1400 µg/L 2.8% of the EPA limit 5 µg/L | 1/12 | SYR4 | 2013–2019 |
| Combined Radium (-226 And -228) | 0.6270 pCi/L 13% of the EPA limit 5 pCi/L | 1/8 | SYR4 | 2012–2019 |
| Di(2-ethylhexyl) Phthalate | 1.4 µg/L 23% of the EPA limit 6 µg/L | 1/12 | SYR4 | 2013–2019 |
| Nitrate-Nitrite | 2400 µg/L 24% of the EPA limit 10000 µg/L | 1/4 | SYR4 | 2013 |
88 contaminants tested, none detected
Utility contact
Frequently asked questions about Kingstree Town of (sc4510002)
Is Kingstree Town of (sc4510002) tap water safe to drink?
EPA monitoring detected 21 contaminants in Kingstree Town of (sc4510002)'s water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Kingstree Town of (sc4510002)'s water?
EPA monitoring detected Copper, Fluoride, Lead, Lead, Nitrate, and others. The full list with the level and data source for each is above.
How many people does Kingstree Town of (sc4510002) serve?
Kingstree Town of (sc4510002) reports serving 6,009 people in South Carolina, per its EPA record.
Has Kingstree Town of (sc4510002) had any water quality violations?
The EPA has 68 violations on file for Kingstree Town of (sc4510002), of which 5 are health-based (a contaminant limit or required treatment was breached) and 8 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.