Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Archived | 2019-05-01 → 2019-05-31 |
| MCL | Health-based | Archived | 2019-05-01 → 2019-05-31 |
| MCL | Health-based | Archived | 2019-05-01 → 2019-05-31 |
| MCL | Health-based | Archived | 2019-05-01 → 2019-05-31 |
| MCL | Health-based | Archived | 2019-05-01 → 2019-05-31 |
| MCL | Health-based | Archived | 2019-05-01 → 2019-05-31 |
| MCL | Health-based | Archived | 2019-05-01 → 2019-05-31 |
| MCL | Health-based | Archived | 2019-05-01 → 2019-05-31 |
| MCL | Health-based | Archived | 2019-05-01 → 2019-05-31 |
| MCL | Health-based | Resolved | 2013-04-01 → 2013-06-30 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 119.5 µg/L 9.2% of the EPA limit 1300 µg/L
worst single sample: 222 µg/L | 67/81 | SYR4 | 2012–2019 |
| Bromodichloromethane | 25.61 µg/L No EPA limit set
worst single sample: 36.5 µg/L | 64/64 | SYR4 | 2012–2019 |
| TTHM | 110.17 µg/L 138% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 197.36 µg/L | 64/64 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 45.84 µg/L 76% of the EPA limit 60 µg/L
worst single sample: 54.28 µg/L | 64/64 | SYR4 | 2012–2019 |
| Chloroform | 70.92 µg/L No EPA limit set
worst single sample: 90.5 µg/L | 63/64 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 22.87 µg/L No EPA limit set
worst single sample: 29.52 µg/L | 63/64 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 20.585 µg/L No EPA limit set
worst single sample: 26.7 µg/L | 63/64 | SYR4 | 2012–2019 |
| Dibromochloromethane | 26.37 µg/L No EPA limit set
worst single sample: 82.86 µg/L | 61/64 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 20.133 µg/L No EPA limit set
worst single sample: 21.55 µg/L | 23/64 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 17/17 | LCR | 2025 |
| Bromoform | 75.795 µg/L No EPA limit set
worst single sample: 78.72 µg/L | 14/64 | SYR4 | 2012–2019 |
| Lead | 13.6 µg/L 91% of the EPA limit 15 µg/L
worst single sample: 15 µg/L | 8/81 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 14.096 µg/L No EPA limit set
worst single sample: 14.66 µg/L | 7/64 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 2.37 µg/L No EPA limit set
worst single sample: 2.4 µg/L | 3/64 | SYR4 | 2012–2019 |
25 contaminants tested, none detected
Utility contact
Frequently asked questions about Meansville Riley W/D (sc4420001)
Is Meansville Riley W/D (sc4420001) tap water safe to drink?
EPA monitoring detected 19 contaminants in Meansville Riley W/D (sc4420001)'s water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Meansville Riley W/D (sc4420001)'s water?
EPA monitoring detected Copper, Bromodichloromethane, TTHM, Total Haloacetic Acids (HAA5), Chloroform, and others. The full list with the level and data source for each is above.
How many people does Meansville Riley W/D (sc4420001) serve?
Meansville Riley W/D (sc4420001) reports serving 7,368 people in South Carolina, per its EPA record.
Has Meansville Riley W/D (sc4420001) had any water quality violations?
The EPA has 72 violations on file for Meansville Riley W/D (sc4420001), of which 57 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.