Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2006-01-01 |
| TT | Health-based | Resolved | 2006-01-01 |
| TT | Health-based | Resolved | 2006-01-01 |
| TT | Health-based | Resolved | 2006-01-01 |
| TT | Health-based | Resolved | 1996-01-01 |
| TT | Health-based | Resolved | 1996-01-01 |
| MCL | Health-based | Resolved | 1992-09-01 → 1992-09-30 |
| MCL | Health-based | Resolved | 1992-09-01 → 1992-09-30 |
| MR | Monitoring | Unaddressed | 2026-01-01 |
| Other | Monitoring | Unaddressed | 2024-10-01 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 2348 µg/L 181% of the EPA limit, at the 95th percentile of samples — 1300 µg/L
worst single sample: 7440 µg/L | 149/151 | SYR4 | 2012–2019 |
| Lead | 16 µg/L 107% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 97 µg/L | 58/151 | SYR4 | 2012–2019 |
| Lead | 0.0050 mg/L 33% of the EPA limit 0.0150 mg/L | 32/32 | LCR | 2025 |
| Nitrate | 2935 µg/L 29% of the EPA limit 10000 µg/L
worst single sample: 3100 µg/L | 32/32 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 3.92 pCi/L 78% of the EPA limit 5 pCi/L
worst single sample: 4.2 pCi/L | 8/8 | SYR4 | 2012–2018 |
| Dibromoacetic Acid | 2.889 µg/L No EPA limit set
worst single sample: 3.07 µg/L | 3/14 | SYR4 | 2013–2019 |
| Dibromochloromethane | 1.32293 µg/L No EPA limit set
worst single sample: 1.3477 µg/L | 3/14 | SYR4 | 2013–2019 |
| TTHM | 2.55773 µg/L 3.2% of the EPA limit 80 µg/L
worst single sample: 2.6062 µg/L | 3/14 | SYR4 | 2013–2019 |
| Total Haloacetic Acids (HAA5) | 2.889 µg/L 4.8% of the EPA limit 60 µg/L
worst single sample: 3.07 µg/L | 3/14 | SYR4 | 2013–2019 |
| Bromodichloromethane | 1.25076 µg/L No EPA limit set
worst single sample: 1.2585 µg/L | 2/14 | SYR4 | 2013–2019 |
| Gross Alpha, Excl. Radon And U | 6.1905 pCi/L 41% of the EPA limit 15 pCi/L
worst single sample: 6.39 pCi/L | 2/7 | SYR4 | 2012–2017 |
| Nitrate-Nitrite | 2170 µg/L 22% of the EPA limit 10000 µg/L
worst single sample: 2200 µg/L | 2/2 | SYR4 | 2017 |
| Barium | 55 µg/L 2.8% of the EPA limit 2000 µg/L | 1/5 | SYR4 | 2012–2017 |
| Combined Uranium | 3.5 µg/L 12% of the EPA limit 30 µg/L | 1/1 | SYR4 | 2012 |
65 contaminants tested, none detected
Utility contact
Frequently asked questions about Eastover Town of (sc4010002)
Is Eastover Town of (sc4010002) tap water safe to drink?
EPA monitoring detected 14 contaminants in Eastover Town of (sc4010002)'s water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Eastover Town of (sc4010002)'s water?
EPA monitoring detected Copper, Lead, Lead, Nitrate, Combined Radium (-226 And -228), and others. The full list with the level and data source for each is above.
How many people does Eastover Town of (sc4010002) serve?
Eastover Town of (sc4010002) reports serving 700 people in South Carolina, per its EPA record.
Has Eastover Town of (sc4010002) had any water quality violations?
The EPA has 103 violations on file for Eastover Town of (sc4010002), of which 8 are health-based (a contaminant limit or required treatment was breached) and 3 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.