Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2024-12-01 → 2024-12-31 |
| MCL | Health-based | Resolved | 2024-12-01 → 2024-12-31 |
| MCL | Health-based | Resolved | 2024-12-01 → 2024-12-31 |
| MCL | Health-based | Resolved | 2024-12-01 → 2024-12-31 |
| MCL | Health-based | Resolved | 2021-04-01 → 2021-04-30 |
| MCL | Health-based | Resolved | 2021-04-01 → 2021-04-30 |
| MCL | Health-based | Resolved | 2021-04-01 → 2021-04-30 |
| MCL | Health-based | Resolved | 2021-04-01 → 2021-04-30 |
| MCL | Health-based | Resolved | 2021-04-01 → 2021-04-30 |
| MCL | Health-based | Resolved | 2021-04-01 → 2021-04-30 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 11.576 µg/L No EPA limit set
worst single sample: 16.43 µg/L | 312/312 | SYR4 | 2012–2019 |
| TTHM | 46.152 µg/L 58% of the EPA limit 80 µg/L
worst single sample: 64.7 µg/L | 312/312 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 53.8685 µg/L 90% of the EPA limit 60 µg/L
worst single sample: 68.6 µg/L | 312/312 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 20.8815 µg/L No EPA limit set
worst single sample: 37.79 µg/L | 312/312 | SYR4 | 2012–2019 |
| Chloroform | 28.875 µg/L No EPA limit set
worst single sample: 44.47 µg/L | 311/312 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 33.1375 µg/L No EPA limit set
worst single sample: 42.45 µg/L | 308/312 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 6.0805 µg/L No EPA limit set
worst single sample: 14.37 µg/L | 284/312 | SYR4 | 2012–2019 |
| Dibromochloromethane | 7.95 µg/L No EPA limit set
worst single sample: 28.24 µg/L | 277/312 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 11.17 µg/L No EPA limit set
worst single sample: 14.53 µg/L | 105/312 | SYR4 | 2012–2019 |
| Copper | 96.2 µg/L 7.4% of the EPA limit 1300 µg/L
worst single sample: 450 µg/L | 99/100 | SYR4 | 2014–2017 |
| Lead | 7.44 µg/L 50% of the EPA limit 15 µg/L
worst single sample: 13 µg/L | 33/100 | SYR4 | 2014–2017 |
| Nitrate | 461 µg/L 4.6% of the EPA limit 10000 µg/L
worst single sample: 470 µg/L | 30/34 | SYR4 | 2012–2019 |
| Lead | 0.0050 mg/L 33% of the EPA limit 0.0150 mg/L | 21/21 | LCR | 2023 |
| Bromoform | 16.4185 µg/L No EPA limit set
worst single sample: 18.28 µg/L | 18/312 | SYR4 | 2012–2019 |
| Fluoride | 654 µg/L 16% of the EPA limit 4000 µg/L
worst single sample: 670 µg/L | 17/17 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 22.2168 µg/L No EPA limit set
worst single sample: 23.4888 µg/L | 8/312 | SYR4 | 2012–2019 |
| Barium | 240 µg/L 12% of the EPA limit 2000 µg/L | 1/17 | SYR4 | 2012–2019 |
81 contaminants tested, none detected
Utility contact
Frequently asked questions about Columbia City of (sc4010001)
Is Columbia City of (sc4010001) tap water safe to drink?
EPA monitoring detected 24 contaminants in Columbia City of (sc4010001)'s water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Columbia City of (sc4010001)'s water?
EPA monitoring detected Bromodichloromethane, TTHM, Total Haloacetic Acids (HAA5), Trichloroacetic Acid, Chloroform, and others. The full list with the level and data source for each is above.
How many people does Columbia City of (sc4010001) serve?
Columbia City of (sc4010001) reports serving 354,068 people in South Carolina, per its EPA record.
Has Columbia City of (sc4010001) had any water quality violations?
The EPA has 66 violations on file for Columbia City of (sc4010001), of which 55 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.