Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2016-04-01 → 2016-06-30 |
| MCL | Health-based | Resolved | 2016-04-01 → 2016-06-30 |
| MCL | Health-based | Resolved | 2016-04-01 → 2016-06-30 |
| MCL | Health-based | Resolved | 2016-04-01 → 2016-06-30 |
| MCL | Health-based | Resolved | 2016-04-01 → 2016-06-30 |
| MCL | Health-based | Resolved | 2014-10-01 → 2014-12-31 |
| MCL | Health-based | Resolved | 2014-10-01 → 2014-12-31 |
| MCL | Health-based | Resolved | 2014-10-01 → 2014-12-31 |
| MCL | Health-based | Resolved | 2014-10-01 → 2014-12-31 |
| MCL | Health-based | Resolved | 2014-10-01 → 2014-12-31 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 17.623 µg/L No EPA limit set
worst single sample: 21.41 µg/L | 127/127 | SYR4 | 2012–2019 |
| Chloroform | 72.856 µg/L No EPA limit set
worst single sample: 97.62 µg/L | 127/127 | SYR4 | 2012–2019 |
| TTHM | 91.49 µg/L 114% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 116.45 µg/L | 127/127 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 78.008 µg/L 130% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 95.8 µg/L | 125/127 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 33.765 µg/L No EPA limit set
worst single sample: 57.6 µg/L | 124/127 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 40.477 µg/L No EPA limit set
worst single sample: 49.75 µg/L | 122/127 | SYR4 | 2012–2019 |
| Dibromochloromethane | 4.58 µg/L No EPA limit set
worst single sample: 5.25 µg/L | 103/127 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 5.4115 µg/L No EPA limit set
worst single sample: 5.94 µg/L | 78/127 | SYR4 | 2012–2019 |
| Copper | 108.2 µg/L 8.3% of the EPA limit 1300 µg/L
worst single sample: 510 µg/L | 49/60 | SYR4 | 2012–2018 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 20/20 | LCR | 2024 |
| Nitrate | 380 µg/L 3.8% of the EPA limit 10000 µg/L | 16/16 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 2.845 µg/L No EPA limit set
worst single sample: 2.98 µg/L | 11/127 | SYR4 | 2012–2019 |
| Fluoride | 895 µg/L 22% of the EPA limit 4000 µg/L
worst single sample: 930 µg/L | 8/8 | SYR4 | 2012–2019 |
| Lead | 4.7 µg/L 31% of the EPA limit 15 µg/L
worst single sample: 5 µg/L | 3/60 | SYR4 | 2012–2018 |
| Monochloroacetic Acid | 33.472 µg/L No EPA limit set
worst single sample: 36.79 µg/L | 3/127 | SYR4 | 2012–2019 |
85 contaminants tested, none detected
Utility contact
Frequently asked questions about Newberry Co W&Sa (sc3620002)
Is Newberry Co W&Sa (sc3620002) tap water safe to drink?
EPA monitoring detected 20 contaminants in Newberry Co W&Sa (sc3620002)'s water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Newberry Co W&Sa (sc3620002)'s water?
EPA monitoring detected Bromodichloromethane, Chloroform, TTHM, Total Haloacetic Acids (HAA5), Dichloroacetic Acid, and others. The full list with the level and data source for each is above.
How many people does Newberry Co W&Sa (sc3620002) serve?
Newberry Co W&Sa (sc3620002) reports serving 11,157 people in South Carolina, per its EPA record.
Has Newberry Co W&Sa (sc3620002) had any water quality violations?
The EPA has 97 violations on file for Newberry Co W&Sa (sc3620002), of which 66 are health-based (a contaminant limit or required treatment was breached) and 7 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.