Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MR | Monitoring | Resolved | 2001-01-01 → 2001-12-31 |
| MR | Monitoring | Resolved | 2001-01-01 → 2001-12-31 |
| MR | Monitoring | Resolved | 2001-01-01 → 2001-12-31 |
| MR | Monitoring | Resolved | 2001-01-01 → 2001-12-31 |
| MR | Monitoring | Resolved | 2001-01-01 → 2001-12-31 |
| MR | Monitoring | Resolved | 2001-01-01 → 2001-12-31 |
| MR | Monitoring | Resolved | 2001-01-01 → 2001-12-31 |
| MR | Monitoring | Resolved | 2001-01-01 → 2001-12-31 |
| MR | Monitoring | Resolved | 1999-01-01 → 2001-12-31 |
| MR | Monitoring | Resolved | 1999-01-01 → 2001-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 1100 µg/L 11% of the EPA limit 10000 µg/L | 32/32 | SYR4 | 2012–2019 |
| Lead | 0.0020 mg/L 13% of the EPA limit 0.0150 mg/L | 12/12 | LCR | 2023 |
| Copper | 491 µg/L 38% of the EPA limit 1300 µg/L
worst single sample: 500 µg/L | 10/10 | SYR4 | 2014–2017 |
| Fluoride | 620 µg/L 16% of the EPA limit 4000 µg/L
worst single sample: 640 µg/L | 6/6 | SYR4 | 2013–2019 |
| Lead | 5.84 µg/L 39% of the EPA limit 15 µg/L
worst single sample: 7 µg/L | 5/10 | SYR4 | 2014–2017 |
| Bromodichloromethane | 2.729 µg/L No EPA limit set
worst single sample: 2.81 µg/L | 4/6 | SYR4 | 2014–2018 |
| Chloroform | 6.249 µg/L No EPA limit set
worst single sample: 7.05 µg/L | 4/6 | SYR4 | 2014–2018 |
| Combined Uranium | 20.55 µg/L 69% of the EPA limit 30 µg/L
worst single sample: 21 µg/L | 4/4 | SYR4 | 2012–2018 |
| Gross Alpha, Excl. Radon And U | 10.915 pCi/L 73% of the EPA limit 15 pCi/L
worst single sample: 11.2 pCi/L | 4/8 | SYR4 | 2012–2018 |
| TTHM | 12.375 µg/L 15% of the EPA limit 80 µg/L
worst single sample: 13.2 µg/L | 4/6 | SYR4 | 2014–2018 |
| Dibromochloromethane | 3.11 µg/L No EPA limit set
worst single sample: 3.18 µg/L | 2/6 | SYR4 | 2014–2018 |
| Dichloroacetic Acid | 1.6421 µg/L No EPA limit set
worst single sample: 1.6601 µg/L | 2/6 | SYR4 | 2014–2018 |
| Nitrate-Nitrite | 976 µg/L 9.8% of the EPA limit 10000 µg/L
worst single sample: 980 µg/L | 2/2 | SYR4 | 2012–2013 |
| Total Haloacetic Acids (HAA5) | 1.6421 µg/L 2.7% of the EPA limit 60 µg/L
worst single sample: 1.6601 µg/L | 2/6 | SYR4 | 2014–2018 |
| Barium | 38 µg/L 1.9% of the EPA limit 2000 µg/L | 1/6 | SYR4 | 2013–2019 |
| Bromoform | 2.1 µg/L No EPA limit set | 1/6 | SYR4 | 2014–2018 |
62 contaminants tested, none detected
Utility contact
Frequently asked questions about Bgwc Fox Trail (sc3250038)
Is Bgwc Fox Trail (sc3250038) tap water safe to drink?
EPA monitoring detected 16 contaminants in Bgwc Fox Trail (sc3250038)'s water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Bgwc Fox Trail (sc3250038)'s water?
EPA monitoring detected Nitrate, Lead, Copper, Fluoride, Lead, and others. The full list with the level and data source for each is above.
How many people does Bgwc Fox Trail (sc3250038) serve?
Bgwc Fox Trail (sc3250038) reports serving 94 people in South Carolina, per its EPA record.
Has Bgwc Fox Trail (sc3250038) had any water quality violations?
The EPA has 112 violations on file for Bgwc Fox Trail (sc3250038), of which 0 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.