Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2006-07-01 → 2006-09-30 |
| MCL | Health-based | Resolved | 2006-07-01 → 2006-09-30 |
| MCL | Health-based | Resolved | 2006-07-01 → 2006-09-30 |
| MCL | Health-based | Resolved | 2006-07-01 → 2006-09-30 |
| TT | Health-based | Resolved | 1996-05-01 → 1996-05-31 |
| TT | Health-based | Resolved | 1996-05-01 → 1996-05-31 |
| TT | Health-based | Resolved | 1996-04-01 → 1996-04-30 |
| TT | Health-based | Resolved | 1996-04-01 → 1996-04-30 |
| MCL | Health-based | Resolved | 1996-01-01 → 1996-03-31 |
| MCL | Health-based | Resolved | 1996-01-01 → 1996-03-31 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Chloroform | 57.5304 µg/L No EPA limit set
worst single sample: 68.78 µg/L | 46/46 | SYR4 | 2012–2019 |
| TTHM | 66.5775 µg/L 83% of the EPA limit 80 µg/L
worst single sample: 85 µg/L | 46/46 | SYR4 | 2012–2019 |
| Bromodichloromethane | 10.466 µg/L No EPA limit set
worst single sample: 14.7 µg/L | 45/46 | SYR4 | 2012–2019 |
| Copper | 213.5 µg/L 16% of the EPA limit 1300 µg/L
worst single sample: 591 µg/L | 40/40 | SYR4 | 2014–2017 |
| Total Haloacetic Acids (HAA5) | 70.209 µg/L 117% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 77.3 µg/L | 38/46 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 38.895 µg/L No EPA limit set
worst single sample: 40.24 µg/L | 36/46 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 28.918 µg/L No EPA limit set
worst single sample: 35.9 µg/L | 35/46 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 16/16 | LCR | 2023 |
| Nitrate | 1100 µg/L 11% of the EPA limit 10000 µg/L | 16/16 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 3.37094 µg/L No EPA limit set
worst single sample: 3.4284 µg/L | 14/46 | SYR4 | 2012–2019 |
| Fluoride | 746 µg/L 19% of the EPA limit 4000 µg/L
worst single sample: 760 µg/L | 8/8 | SYR4 | 2012–2019 |
| Dibromochloromethane | 1.79672 µg/L No EPA limit set
worst single sample: 2 µg/L | 7/46 | SYR4 | 2012–2019 |
| Lead | 7.355 µg/L 49% of the EPA limit 15 µg/L
worst single sample: 8 µg/L | 4/40 | SYR4 | 2014–2017 |
| Combined Radium (-226 And -228) | 0.5160 pCi/L 10% of the EPA limit 5 pCi/L | 1/3 | SYR4 | 2012–2018 |
89 contaminants tested, none detected
Utility contact
Frequently asked questions about Batesburg Leesville Dpw (sc3210002)
Is Batesburg Leesville Dpw (sc3210002) tap water safe to drink?
EPA monitoring detected 18 contaminants in Batesburg Leesville Dpw (sc3210002)'s water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Batesburg Leesville Dpw (sc3210002)'s water?
EPA monitoring detected Chloroform, TTHM, Bromodichloromethane, Copper, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does Batesburg Leesville Dpw (sc3210002) serve?
Batesburg Leesville Dpw (sc3210002) reports serving 6,814 people in South Carolina, per its EPA record.
Has Batesburg Leesville Dpw (sc3210002) had any water quality violations?
The EPA has 37 violations on file for Batesburg Leesville Dpw (sc3210002), of which 14 are health-based (a contaminant limit or required treatment was breached) and 3 remain open. The rest are monitoring or reporting failures.
Where does this data come from?