Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2005-07-01 → 2005-12-31 |
| TT | Health-based | Resolved | 2005-07-01 → 2005-12-31 |
| TT | Health-based | Resolved | 2005-07-01 → 2005-12-31 |
| TT | Health-based | Resolved | 2005-07-01 → 2005-12-31 |
| TT | Health-based | Resolved | 2005-07-01 → 2005-12-31 |
| TT | Health-based | Resolved | 2005-07-01 → 2005-12-31 |
| MCL | Health-based | Resolved | 1994-07-01 → 1994-07-31 |
| MCL | Health-based | Resolved | 1994-07-01 → 1994-07-31 |
| MCL | Health-based | Resolved | 1994-07-01 → 1994-07-31 |
| MCL | Health-based | Resolved | 1993-10-01 → 1993-10-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 3.2 µg/L No EPA limit set
worst single sample: 4.78 µg/L | 356/356 | SYR4 | 2012–2019 |
| Chloroform | 11.925 µg/L No EPA limit set
worst single sample: 14.24 µg/L | 356/356 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 10.9 µg/L No EPA limit set
worst single sample: 13.8 µg/L | 356/356 | SYR4 | 2012–2019 |
| TTHM | 14.6 µg/L 18% of the EPA limit 80 µg/L
worst single sample: 19.02 µg/L | 356/356 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 16.525 µg/L 28% of the EPA limit 60 µg/L
worst single sample: 21 µg/L | 356/356 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 6.925 µg/L No EPA limit set
worst single sample: 9.49 µg/L | 356/356 | SYR4 | 2012–2019 |
| Copper | 91.6 µg/L 7% of the EPA limit 1300 µg/L
worst single sample: 397 µg/L | 149/150 | SYR4 | 2012–2018 |
| Nitrate | 358.8 µg/L 3.6% of the EPA limit 10000 µg/L
worst single sample: 510 µg/L | 28/32 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 21/21 | LCR | 2024 |
| Fluoride | 692.5 µg/L 17% of the EPA limit 4000 µg/L
worst single sample: 700 µg/L | 16/16 | SYR4 | 2012–2019 |
| Lead | 54 µg/L 360% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 66 µg/L | 11/150 | SYR4 | 2012–2018 |
| Monobromoacetic Acid | 1.625 µg/L No EPA limit set
worst single sample: 1.66 µg/L | 6/356 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 1 µg/L No EPA limit set | 5/356 | SYR4 | 2012–2019 |
| Dibromochloromethane | 1.095 µg/L No EPA limit set
worst single sample: 1.1 µg/L | 2/356 | SYR4 | 2012–2019 |
91 contaminants tested, none detected
Utility contact
Frequently asked questions about Greenville Water (sc2310001)
Is Greenville Water (sc2310001) tap water safe to drink?
EPA monitoring detected 14 contaminants in Greenville Water (sc2310001)'s water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Greenville Water (sc2310001)'s water?
EPA monitoring detected Bromodichloromethane, Chloroform, Dichloroacetic Acid, TTHM, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does Greenville Water (sc2310001) serve?
Greenville Water (sc2310001) reports serving 426,057 people in South Carolina, per its EPA record.
Has Greenville Water (sc2310001) had any water quality violations?
The EPA has 39 violations on file for Greenville Water (sc2310001), of which 20 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.