Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2006-11-01 → 2006-11-30 |
| MCL | Health-based | Resolved | 2006-11-01 → 2006-11-30 |
| MCL | Health-based | Resolved | 2006-11-01 → 2006-11-30 |
| MCL | Health-based | Resolved | 2006-11-01 → 2006-11-30 |
| MCL | Health-based | Resolved | 2006-09-01 → 2006-09-30 |
| MCL | Health-based | Resolved | 2006-09-01 → 2006-09-30 |
| MCL | Health-based | Resolved | 2006-09-01 → 2006-09-30 |
| MCL | Health-based | Resolved | 2005-12-01 → 2005-12-31 |
| MCL | Health-based | Resolved | 2005-12-01 → 2005-12-31 |
| MCL | Health-based | Resolved | 2005-12-01 → 2005-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 130 µg/L 10% of the EPA limit 1300 µg/L
worst single sample: 180 µg/L | 29/30 | SYR4 | 2013–2019 |
| Lead | 1.8645 µg/L 12% of the EPA limit 15 µg/L
worst single sample: 3.3 µg/L | 12/30 | SYR4 | 2013–2019 |
| Lead | 0.00025 mg/L 1.7% of the EPA limit 0.0150 mg/L | 10/10 | LCR | 2025 |
| Bromodichloromethane | 17.977 µg/L No EPA limit set
worst single sample: 19.36 µg/L | 7/7 | SYR4 | 2013–2019 |
| Chloroform | 31.221 µg/L No EPA limit set
worst single sample: 32.16 µg/L | 7/7 | SYR4 | 2013–2019 |
| Dibromoacetic Acid | 4.60613 µg/L No EPA limit set
worst single sample: 4.6559 µg/L | 7/7 | SYR4 | 2013–2019 |
| Dibromochloromethane | 13.464 µg/L No EPA limit set
worst single sample: 14.1 µg/L | 7/7 | SYR4 | 2013–2019 |
| Dichloroacetic Acid | 11.039 µg/L No EPA limit set
worst single sample: 11.18 µg/L | 7/7 | SYR4 | 2013–2019 |
| TTHM | 62.803 µg/L 79% of the EPA limit 80 µg/L
worst single sample: 66.7 µg/L | 7/7 | SYR4 | 2013–2019 |
| Total Haloacetic Acids (HAA5) | 19.745 µg/L 33% of the EPA limit 60 µg/L
worst single sample: 20.24 µg/L | 7/7 | SYR4 | 2013–2019 |
| Trichloroacetic Acid | 5.054 µg/L No EPA limit set
worst single sample: 5.06 µg/L | 7/7 | SYR4 | 2013–2019 |
| Bromoform | 4.055 µg/L No EPA limit set
worst single sample: 4.21 µg/L | 6/7 | SYR4 | 2013–2019 |
| Fluoride | 817.5 µg/L 20% of the EPA limit 4000 µg/L
worst single sample: 830 µg/L | 6/6 | SYR4 | 2014–2017 |
| Nitrate | 21 µg/L 0.2% of the EPA limit 10000 µg/L | 2/48 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 4.57 µg/L No EPA limit set | 1/7 | SYR4 | 2013–2019 |
63 contaminants tested, none detected
Utility contact
Frequently asked questions about Browns Ferry Water Co (sc2220003)
Is Browns Ferry Water Co (sc2220003) tap water safe to drink?
EPA monitoring detected 15 contaminants in Browns Ferry Water Co (sc2220003)'s water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Browns Ferry Water Co (sc2220003)'s water?
EPA monitoring detected Copper, Lead, Lead, Bromodichloromethane, Chloroform, and others. The full list with the level and data source for each is above.
How many people does Browns Ferry Water Co (sc2220003) serve?
Browns Ferry Water Co (sc2220003) reports serving 2,550 people in South Carolina, per its EPA record.
Has Browns Ferry Water Co (sc2220003) had any water quality violations?
The EPA has 51 violations on file for Browns Ferry Water Co (sc2220003), of which 22 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.