← South Carolina

Tap water quality report

Lake View Town of (sc1710003)

EPA monitoring tested this supplier for 44 contaminants and detected 12. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

44
contaminants tested
12
detected
1,293
people served
8
health-based violations
Water source
GWP
Ownership
Local government
Counties served
Dillon

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

8
health-based violations
16
violations on file
0
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 1995-01-01
TT Health-based Resolved 1995-01-01
TT Health-based Resolved 1995-01-01
TT Health-based Resolved 1994-07-01
TT Health-based Resolved 1994-07-01
TT Health-based Resolved 1994-01-01
TT Health-based Resolved 1994-01-01
TT Health-based Resolved 1994-01-01
MR Monitoring Resolved 2007-10-02
MR Monitoring Resolved 1998-10-01

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
136 µg/L 10%
of the EPA limit 1300 µg/L
worst single sample: 190 µg/L
28/30 SYR4 2013–2019
Lead
2.915 µg/L 19%
of the EPA limit 15 µg/L
worst single sample: 3 µg/L
18/30 SYR4 2013–2019
Lead
0.0012 mg/L 8%
of the EPA limit 0.0150 mg/L
14/14 LCR 2025
Bromodichloromethane
5.5625 µg/L
No EPA limit set
worst single sample: 5.7 µg/L
12/12 SYR4 2014–2019
TTHM
13.485 µg/L 17%
of the EPA limit 80 µg/L
worst single sample: 15.3 µg/L
12/12 SYR4 2014–2019
Total Haloacetic Acids (HAA5)
6.335 µg/L 11%
of the EPA limit 60 µg/L
worst single sample: 6.6 µg/L
11/12 SYR4 2014–2019
Chloroform
5.9405 µg/L
No EPA limit set
worst single sample: 6.71 µg/L
10/12 SYR4 2014–2019
Dibromochloromethane
2.9785 µg/L
No EPA limit set
worst single sample: 3.1 µg/L
10/12 SYR4 2014–2019
Dichloroacetic Acid
3.344 µg/L
No EPA limit set
worst single sample: 3.58 µg/L
9/12 SYR4 2014–2019
Trichloroacetic Acid
2.4375 µg/L
No EPA limit set
worst single sample: 2.56 µg/L
8/12 SYR4 2014–2019
Monobromoacetic Acid
2.213 µg/L
No EPA limit set
worst single sample: 2.36 µg/L
7/12 SYR4 2014–2019
Dibromoacetic Acid
1.02 µg/L
No EPA limit set
1/12 SYR4 2014–2019
32 contaminants tested, none detected
11Cl-PF3OUdS4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaBromoformHfpo-DaMonochloroacetic AcidNetfosaaNfdhaNmefosaaPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaLithium

Utility contact

Contact
LEWIS, WADE
Phone
843-234-8989
Email
[email protected]; [email protected]; [email protected]; [email protected]

Frequently asked questions about Lake View Town of (sc1710003)

Is Lake View Town of (sc1710003) tap water safe to drink?

EPA monitoring detected 12 contaminants in Lake View Town of (sc1710003)'s water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Lake View Town of (sc1710003)'s water?

EPA monitoring detected Copper, Lead, Lead, Bromodichloromethane, TTHM, and others. The full list with the level and data source for each is above.

How many people does Lake View Town of (sc1710003) serve?

Lake View Town of (sc1710003) reports serving 1,293 people in South Carolina, per its EPA record.

Has Lake View Town of (sc1710003) had any water quality violations?

The EPA has 16 violations on file for Lake View Town of (sc1710003), of which 8 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.