← South Carolina

Tap water quality report

Macdougall Correctional Inst (sc0870050)

EPA monitoring tested this supplier for 75 contaminants and detected 13. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

75
contaminants tested
13
detected
790
people served
5
health-based violations
Water source
Ground water
Ownership
State government
Counties served
Berkeley

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

5
health-based violations
10
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2007-09-01 → 2007-09-30
MCL Health-based Resolved 2007-09-01 → 2007-09-30
MCL Health-based Resolved 2007-09-01 → 2007-09-30
MCL Health-based Resolved 2007-09-01 → 2007-09-30
MCL Health-based Resolved 2007-09-01 → 2007-09-30
MR Monitoring Resolved 2006-10-01 → 2006-10-31
MR Monitoring Resolved 2006-10-01 → 2006-10-31
MR Monitoring Resolved 2006-10-01 → 2006-10-31
MR Monitoring Resolved 1996-07-01
MR Monitoring Resolved 1996-07-01

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Lead
0.0026 mg/L 17%
of the EPA limit 0.0150 mg/L
13/13 LCR 2023
Chloroform
15.694 µg/L
No EPA limit set
worst single sample: 17.41 µg/L
12/14 SYR4 2012–2019
Dichloroacetic Acid
7.844 µg/L
No EPA limit set
worst single sample: 8.9 µg/L
12/14 SYR4 2012–2019
TTHM
21.9 µg/L 27%
of the EPA limit 80 µg/L
worst single sample: 24.32 µg/L
12/14 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
18.8435 µg/L 31%
of the EPA limit 60 µg/L
worst single sample: 19.3 µg/L
12/14 SYR4 2012–2019
Monobromoacetic Acid
5.585 µg/L
No EPA limit set
worst single sample: 6.13 µg/L
11/14 SYR4 2012–2019
Bromodichloromethane
5.3265 µg/L
No EPA limit set
worst single sample: 5.52 µg/L
10/14 SYR4 2012–2019
Trichloroacetic Acid
7.741 µg/L
No EPA limit set
worst single sample: 8.2 µg/L
10/14 SYR4 2012–2019
Copper
83.2 µg/L 6.4%
of the EPA limit 1300 µg/L
worst single sample: 94 µg/L
9/20 SYR4 2014–2017
Dibromochloromethane
1.38128 µg/L
No EPA limit set
worst single sample: 1.39 µg/L
5/14 SYR4 2012–2019
Fluoride
381 µg/L 9.5%
of the EPA limit 4000 µg/L
worst single sample: 390 µg/L
4/4 SYR4 2014–2017
Dibromoacetic Acid
1.6107 µg/L
No EPA limit set
1/14 SYR4 2012–2019
Lead
3.6 µg/L 24%
of the EPA limit 15 µg/L
1/20 SYR4 2014–2017
62 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalArsenicAtrazineBhc-GammaBariumBenzeneBenzo(A)PyreneBeryllium, TotalBromoformChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndrinEthylbenzeneGlyphosateHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonochloroacetic AcidNitrateNitrate-NitriteNitriteOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
CAIATI, FRANCINE
Phone
803-896-1918
Email
[email protected]

Frequently asked questions about Macdougall Correctional Inst (sc0870050)

Is Macdougall Correctional Inst (sc0870050) tap water safe to drink?

EPA monitoring detected 13 contaminants in Macdougall Correctional Inst (sc0870050)'s water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Macdougall Correctional Inst (sc0870050)'s water?

EPA monitoring detected Lead, Chloroform, Dichloroacetic Acid, TTHM, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.

How many people does Macdougall Correctional Inst (sc0870050) serve?

Macdougall Correctional Inst (sc0870050) reports serving 790 people in South Carolina, per its EPA record.

Has Macdougall Correctional Inst (sc0870050) had any water quality violations?

The EPA has 10 violations on file for Macdougall Correctional Inst (sc0870050), of which 5 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.