← South Carolina

Tap water quality report

Bgwc Oakwood Estates (0450076)

EPA monitoring tested this supplier for 14 contaminants and detected 11. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

14
contaminants tested
11
detected
132
people served
3
health-based violations
Water source
SWP
Ownership
Private
Counties served
Anderson

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

3
health-based violations
14
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2004-11-01 → 2005-01-31
MCL Health-based Resolved 2004-11-01 → 2005-01-31
MCL Health-based Resolved 2004-11-01 → 2005-01-31
MR Monitoring Resolved 2007-10-01 → 2007-10-31
MR Monitoring Resolved 2007-10-01 → 2007-10-31
MR Monitoring Resolved 2007-10-01 → 2007-10-31
MR Monitoring Archived 1979-10-01 → 1982-09-30
MR Monitoring Archived 1979-10-01 → 1982-09-30
MR Monitoring Archived 1979-10-01 → 1982-09-30
MR Monitoring Archived 1979-10-01 → 1982-09-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
206 µg/L 16%
of the EPA limit 1300 µg/L
worst single sample: 543 µg/L
25/25 SYR4 2012–2019
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
18/18 LCR 2025
Bromodichloromethane
6.535 µg/L
No EPA limit set
worst single sample: 6.7 µg/L
12/12 SYR4 2014–2019
Chloroform
41.77 µg/L
No EPA limit set
worst single sample: 48.7 µg/L
12/12 SYR4 2014–2019
Dibromochloromethane
2.445 µg/L
No EPA limit set
worst single sample: 2.5 µg/L
12/12 SYR4 2014–2019
Dichloroacetic Acid
15.705 µg/L
No EPA limit set
worst single sample: 17.3 µg/L
12/12 SYR4 2014–2019
TTHM
49.345 µg/L 62%
of the EPA limit 80 µg/L
worst single sample: 57.1 µg/L
12/12 SYR4 2014–2019
Total Haloacetic Acids (HAA5)
23.575 µg/L 39%
of the EPA limit 60 µg/L
worst single sample: 25.5 µg/L
12/12 SYR4 2014–2019
Trichloroacetic Acid
8.715 µg/L
No EPA limit set
worst single sample: 9.1 µg/L
12/12 SYR4 2014–2019
Lead
74.745 µg/L 498%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 87 µg/L
4/25 SYR4 2012–2019
Monobromoacetic Acid
1.5 µg/L
No EPA limit set
1/12 SYR4 2014–2019
3 contaminants tested, none detected
BromoformDibromoacetic AcidMonochloroacetic Acid

Utility contact

Contact
BLUE GRANITE WATER COMPANY
Phone
864-483-4268
Email
[email protected]

Frequently asked questions about Bgwc Oakwood Estates (0450076)

Is Bgwc Oakwood Estates (0450076) tap water safe to drink?

EPA monitoring detected 11 contaminants in Bgwc Oakwood Estates (0450076)'s water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Bgwc Oakwood Estates (0450076)'s water?

EPA monitoring detected Copper, Lead, Bromodichloromethane, Chloroform, Dibromochloromethane, and others. The full list with the level and data source for each is above.

How many people does Bgwc Oakwood Estates (0450076) serve?

Bgwc Oakwood Estates (0450076) reports serving 132 people in South Carolina, per its EPA record.

Has Bgwc Oakwood Estates (0450076) had any water quality violations?

The EPA has 14 violations on file for Bgwc Oakwood Estates (0450076), of which 3 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.