← South Carolina

Tap water quality report

Breezy Hill W/D (sc0220006)

EPA monitoring tested this supplier for 108 contaminants and detected 24. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

108
contaminants tested
24
detected
21,197
people served
16
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Aiken

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

16
health-based violations
17
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2015-01-01 → 2015-03-31
MCL Health-based Resolved 2015-01-01 → 2015-03-31
MCL Health-based Resolved 2015-01-01 → 2015-03-31
MCL Health-based Resolved 2015-01-01 → 2015-03-31
MCL Health-based Resolved 2015-01-01 → 2015-03-31
MCL Health-based Resolved 2014-10-01 → 2014-12-31
MCL Health-based Resolved 2014-10-01 → 2014-12-31
MCL Health-based Resolved 2014-10-01 → 2014-12-31
MCL Health-based Resolved 2014-10-01 → 2014-12-31
MCL Health-based Resolved 2014-10-01 → 2014-12-31

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
PFBS 0.0042 µg/L 5/9 2024
Pfba 0.0097 µg/L 1/9 2024
PFOA 0.0048 µg/L 1/9 2024

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
5850 µg/L 59%
of the EPA limit 10000 µg/L
worst single sample: 6500 µg/L
276/276 SYR4 2012–2019
Copper
1300 µg/L 100%
of the EPA limit 1300 µg/L
worst single sample: 2900 µg/L
120/120 SYR4 2013–2019
Dichloroacetic Acid
30.84 µg/L
No EPA limit set
worst single sample: 71.4 µg/L
84/102 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
74.9 µg/L 125%
of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 143 µg/L
84/102 SYR4 2012–2019
Chloroform
65.29 µg/L
No EPA limit set
worst single sample: 76.9 µg/L
83/102 SYR4 2012–2019
TTHM
73.16 µg/L 91%
of the EPA limit 80 µg/L
worst single sample: 88.9 µg/L
83/102 SYR4 2012–2019
Bromodichloromethane
11.14 µg/L
No EPA limit set
worst single sample: 17.2 µg/L
77/102 SYR4 2012–2019
Trichloroacetic Acid
41.76 µg/L
No EPA limit set
worst single sample: 73.2 µg/L
77/102 SYR4 2012–2019
Dibromochloromethane
2.6 µg/L
No EPA limit set
worst single sample: 2.8 µg/L
62/102 SYR4 2012–2019
Lead
5.9 µg/L 39%
of the EPA limit 15 µg/L
worst single sample: 12 µg/L
52/120 SYR4 2013–2019
Monochloroacetic Acid
4.12 µg/L
No EPA limit set
worst single sample: 4.6 µg/L
37/102 SYR4 2012–2019
Lead
0.00085 mg/L 5.7%
of the EPA limit 0.0150 mg/L
15/15 LCR 2025
Nitrate-Nitrite
4525 µg/L 45%
of the EPA limit 10000 µg/L
worst single sample: 5500 µg/L
14/14 SYR4 2012–2014
Combined Radium (-226 And -228)
4.15 pCi/L 83%
of the EPA limit 5 pCi/L
worst single sample: 4.5 pCi/L
11/18 SYR4 2013–2018
Mercury
0.5365 µg/L 27%
of the EPA limit 2 µg/L
worst single sample: 0.5400 µg/L
8/50 SYR4 2012–2019
2,4-D
7.971 µg/L 11%
of the EPA limit 70 µg/L
worst single sample: 8.8 µg/L
3/53 SYR4 2012–2019
Gross Alpha, Excl. Radon And U
2.69 pCi/L 18%
of the EPA limit 15 pCi/L
worst single sample: 2.7 pCi/L
3/18 SYR4 2013–2018
Dalapon
1.775 µg/L 0.9%
of the EPA limit 200 µg/L
worst single sample: 1.8 µg/L
2/53 SYR4 2012–2019
Dibromoacetic Acid
1.1 µg/L
No EPA limit set
2/102 SYR4 2012–2019
2,4,5-TP
0.1400 µg/L 0.3%
of the EPA limit 50 µg/L
1/53 SYR4 2012–2019
Picloram
0.1600 µg/L 0%
of the EPA limit 500 µg/L
1/53 SYR4 2012–2019
84 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicAtrazineBhc-GammaBariumBenzeneBenzo(A)PyreneBeryllium, TotalBromoformChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndrinEthylbenzeneFluorideGlyphosateGross Beta Particle ActivityHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMethoxychlorMonobromoacetic AcidNetfosaaNfdhaNmefosaaNitriteOxamylPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOSPfpeaPfpesPftaPftrdaPfunaPentachlorophenolSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
SMITH, RUSSELL
Phone
803-292-0674
Email
[email protected]

Frequently asked questions about Breezy Hill W/D (sc0220006)

Is Breezy Hill W/D (sc0220006) tap water safe to drink?

EPA monitoring detected 24 contaminants in Breezy Hill W/D (sc0220006)'s water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Breezy Hill W/D (sc0220006)'s water?

EPA monitoring detected Nitrate, Copper, Dichloroacetic Acid, Total Haloacetic Acids (HAA5), Chloroform, and others. The full list with the level and data source for each is above.

How many people does Breezy Hill W/D (sc0220006) serve?

Breezy Hill W/D (sc0220006) reports serving 21,197 people in South Carolina, per its EPA record.

Has Breezy Hill W/D (sc0220006) had any water quality violations?

The EPA has 17 violations on file for Breezy Hill W/D (sc0220006), of which 16 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.