← Rhode Island

Tap water quality report

Newport-City of

EPA monitoring tested this supplier for 105 contaminants and detected 29. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

105
contaminants tested
29
detected
42,155
people served
60
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Newport

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

60
health-based violations
135
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2013-01-01 → 2013-03-31
MCL Health-based Resolved 2013-01-01 → 2013-03-31
MCL Health-based Resolved 2013-01-01 → 2013-03-31
MCL Health-based Resolved 2013-01-01 → 2013-03-31
MCL Health-based Resolved 2013-01-01 → 2013-03-31
MCL Health-based Resolved 2012-07-01 → 2012-09-30
MCL Health-based Resolved 2012-07-01 → 2012-09-30
MCL Health-based Resolved 2012-07-01 → 2012-09-30
MCL Health-based Resolved 2012-07-01 → 2012-09-30
MCL Health-based Resolved 2012-07-01 → 2012-09-30

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
Pfpea 0.0061 µg/L 3/8 2024
Pfba 0.0059 µg/L 1/8 2024
Pfhxa 0.0051 µg/L 1/8 2024

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Chlorite
663.5 µg/L 66%
of the EPA limit 1000 µg/L
worst single sample: 970 µg/L
434/579 SYR4 2012–2019
TTHM
107.25 µg/L 134%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 151 µg/L
156/156 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
28.425 µg/L 47%
of the EPA limit 60 µg/L
worst single sample: 40.2 µg/L
156/156 SYR4 2012–2019
Nitrate
1650 µg/L 17%
of the EPA limit 10000 µg/L
worst single sample: 3320 µg/L
132/132 SYR4 2012–2019
Barium
12 µg/L 0.6%
of the EPA limit 2000 µg/L
worst single sample: 14 µg/L
94/94 SYR4 2012–2019
Copper
52.11 µg/L 4%
of the EPA limit 1300 µg/L
worst single sample: 96 µg/L
59/59 SYR4 2016–2019
Di(2-ethylhexyl) Phthalate
2.4 µg/L 40%
of the EPA limit 6 µg/L
worst single sample: 3 µg/L
53/130 SYR4 2012–2019
Lead
10.125 µg/L 68%
of the EPA limit 15 µg/L
worst single sample: 92.6 µg/L
40/60 SYR4 2016–2019
Bromodichloromethane
20.475 µg/L
No EPA limit set
worst single sample: 25 µg/L
36/36 SYR4 2017–2019
Bromoform
7.9 µg/L
No EPA limit set
worst single sample: 8.6 µg/L
36/36 SYR4 2017–2019
Chloroform
31.525 µg/L
No EPA limit set
worst single sample: 42.5 µg/L
36/36 SYR4 2017–2019
Dibromoacetic Acid
4.2 µg/L
No EPA limit set
worst single sample: 5.4 µg/L
36/36 SYR4 2017–2019
Dibromochloromethane
20.125 µg/L
No EPA limit set
worst single sample: 25.4 µg/L
36/36 SYR4 2017–2019
Dichloroacetic Acid
13 µg/L
No EPA limit set
worst single sample: 14.9 µg/L
36/36 SYR4 2017–2019
Trichloroacetic Acid
3.9 µg/L
No EPA limit set
worst single sample: 4.3 µg/L
35/36 SYR4 2017–2019
Lead
0.0044 mg/L 29%
of the EPA limit 0.0150 mg/L
25/25 LCR 2027
Arsenic
2 µg/L 20%
of the EPA limit 10 µg/L
worst single sample: 3 µg/L
23/94 SYR4 2012–2019
Monochloroacetic Acid
10.02 µg/L
No EPA limit set
worst single sample: 10.7 µg/L
23/36 SYR4 2017–2019
Benzo(A)Pyrene
0.2000 µg/L 100%
of the EPA limit 0.2000 µg/L
14/130 SYR4 2012–2019
Simazine
0.3000 µg/L 7.5%
of the EPA limit 4 µg/L
11/130 SYR4 2012–2019
Chromium
1.9 µg/L 1.9%
of the EPA limit 100 µg/L
worst single sample: 2 µg/L
3/94 SYR4 2012–2019
Nitrite
29 µg/L 2.9%
of the EPA limit 1000 µg/L
worst single sample: 30 µg/L
3/66 SYR4 2012–2019
Monobromoacetic Acid
1.48 µg/L
No EPA limit set
worst single sample: 1.5 µg/L
2/36 SYR4 2017–2019
Selenium
1 µg/L 2%
of the EPA limit 50 µg/L
2/94 SYR4 2012–2019
Atrazine
0.1000 µg/L 3.3%
of the EPA limit 3 µg/L
1/130 SYR4 2012–2019
Lasso
0.1000 µg/L 5%
of the EPA limit 2 µg/L
1/130 SYR4 2012–2019
76 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalBhc-GammaBenzeneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneCombined Radium (-226 And -228)DichloromethaneDalaponDi(2-ethylhexyl) AdipateDinosebEthylene DibromideEndrinEthylbenzeneFluorideHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneMercuryMethoxychlorNetfosaaNfdhaNmefosaaOxamylPFBSPfdaPfdoaPfeesaPfhpaPfhpsPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpesPftaPftrdaPfunaPentachlorophenolPicloramStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
SCHULTZ, ROBERT
Phone
401-845-5600
Email
[email protected]

Frequently asked questions about Newport-City of

Is Newport-City of tap water safe to drink?

EPA monitoring detected 29 contaminants in Newport-City of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Newport-City of's water?

EPA monitoring detected Chlorite, TTHM, Total Haloacetic Acids (HAA5), Nitrate, Barium, and others. The full list with the level and data source for each is above.

How many people does Newport-City of serve?

Newport-City of reports serving 42,155 people in Rhode Island, per its EPA record.

Has Newport-City of had any water quality violations?

The EPA has 135 violations on file for Newport-City of, of which 60 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.