Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2022-08-01 → 2022-08-31 |
| TT | Health-based | Resolved | 2022-08-01 → 2022-08-31 |
| TT | Health-based | Resolved | 2022-08-01 → 2022-08-31 |
| TT | Health-based | Resolved | 2022-08-01 → 2022-08-31 |
| TT | Health-based | Resolved | 2022-07-01 → 2022-07-31 |
| TT | Health-based | Resolved | 2022-07-01 → 2022-07-31 |
| TT | Health-based | Resolved | 2022-07-01 → 2022-07-31 |
| MCL | Health-based | Resolved | 2013-07-01 → 2013-09-30 |
| MCL | Health-based | Resolved | 2013-07-01 → 2013-09-30 |
| MCL | Health-based | Resolved | 2013-07-01 → 2013-09-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Arsenic | 12.9 µg/L 129% of the EPA limit, at the 95th percentile of samples — 10 µg/L
worst single sample: 16 µg/L | 23/42 | SYR4 | 2012–2019 |
| Copper | 145 µg/L 11% of the EPA limit 1300 µg/L
worst single sample: 180 µg/L | 15/15 | SYR4 | 2013–2019 |
| Nitrate | 280 µg/L 2.8% of the EPA limit 10000 µg/L | 6/16 | SYR4 | 2012–2019 |
| Chloroform | 1.847 µg/L No EPA limit set
worst single sample: 1.91 µg/L | 4/4 | SYR4 | 2013–2019 |
| Barium | 238 µg/L 12% of the EPA limit 2000 µg/L
worst single sample: 240 µg/L | 3/3 | SYR4 | 2012–2018 |
| Bromodichloromethane | 1.146 µg/L No EPA limit set
worst single sample: 1.18 µg/L | 3/4 | SYR4 | 2013–2019 |
| Lead | 2.72 µg/L 18% of the EPA limit 15 µg/L
worst single sample: 2.8 µg/L | 3/15 | SYR4 | 2013–2019 |
| TTHM | 3.867 µg/L 4.8% of the EPA limit 80 µg/L
worst single sample: 4.03 µg/L | 3/4 | SYR4 | 2013–2019 |
| Dibromochloromethane | 0.9180 µg/L No EPA limit set
worst single sample: 0.9400 µg/L | 2/4 | SYR4 | 2013–2019 |
| Fluoride | 197 µg/L 4.9% of the EPA limit 4000 µg/L
worst single sample: 200 µg/L | 2/3 | SYR4 | 2012–2018 |
| Lead | 0.0013 mg/L 8.7% of the EPA limit 0.0150 mg/L | 2/2 | LCR | 1996 |
| Dichloroacetic Acid | 1.49 µg/L No EPA limit set | 1/1 | SYR4 | 2019 |
| Total Haloacetic Acids (HAA5) | 2.54 µg/L 4.2% of the EPA limit 60 µg/L | 1/5 | SYR4 | 2013–2019 |
| Trichloroacetic Acid | 1.06 µg/L No EPA limit set | 1/1 | SYR4 | 2019 |
66 contaminants tested, none detected
Utility contact
Frequently asked questions about Stonebridge Health & Rehab Ctr
Is Stonebridge Health & Rehab Ctr tap water safe to drink?
EPA monitoring detected 14 contaminants in Stonebridge Health & Rehab Ctr's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Stonebridge Health & Rehab Ctr's water?
EPA monitoring detected Arsenic, Copper, Nitrate, Chloroform, Barium, and others. The full list with the level and data source for each is above.
How many people does Stonebridge Health & Rehab Ctr serve?
Stonebridge Health & Rehab Ctr reports serving 60 people in Pennsylvania, per its EPA record.
Has Stonebridge Health & Rehab Ctr had any water quality violations?
The EPA has 342 violations on file for Stonebridge Health & Rehab Ctr, of which 46 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.