← Pennsylvania

Tap water quality report

East Hempfield Water Auth

EPA monitoring tested this supplier for 108 contaminants and detected 21. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

108
contaminants tested
21
detected
20,988
people served
5
health-based violations
Water source
SWP
Ownership
Local government
Counties served
Lancaster

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

5
health-based violations
62
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2025-04-01 → 2025-06-30
MCL Health-based Resolved 2025-04-01 → 2025-06-30
MCL Health-based Resolved 2025-04-01 → 2025-06-30
MCL Health-based Resolved 2008-12-01 → 2008-12-31
MCL Health-based Resolved 2008-12-01 → 2008-12-31
RPT Monitoring Resolved 2025-07-01
MR Monitoring Resolved 2023-01-01 → 2023-03-31
RPT Monitoring Resolved 2022-11-15
RPT Monitoring Resolved 2022-11-15
RPT Monitoring Resolved 2022-11-15

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
PFBS 0.0057 µg/L 2/8 2025
Pfpea 0.0048 µg/L 2/8 2025
Pfhxa 0.0036 µg/L 1/8 2025
PFOA 0.0077 µg/L 1/8 2025
PFOS 0.0050 µg/L 1/8 2025

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
8058.5 µg/L 81%
of the EPA limit 10000 µg/L
worst single sample: 9170 µg/L
384/384 SYR4 2012–2019
Copper
220.4 µg/L 17%
of the EPA limit 1300 µg/L
worst single sample: 281 µg/L
85/90 SYR4 2013–2019
Lead
8.75 µg/L 58%
of the EPA limit 15 µg/L
worst single sample: 62 µg/L
58/90 SYR4 2013–2019
Dibromochloromethane
5.14 µg/L
No EPA limit set
worst single sample: 11.1 µg/L
47/49 SYR4 2012–2019
TTHM
40 µg/L 50%
of the EPA limit 80 µg/L
worst single sample: 68.1 µg/L
47/49 SYR4 2012–2019
Bromodichloromethane
7.3 µg/L
No EPA limit set
worst single sample: 14 µg/L
46/49 SYR4 2012–2019
Chloroform
32.81 µg/L
No EPA limit set
worst single sample: 62.4 µg/L
44/49 SYR4 2012–2019
Bromoform
3.24 µg/L
No EPA limit set
worst single sample: 4.1 µg/L
33/49 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
6.898 µg/L 11%
of the EPA limit 60 µg/L
worst single sample: 7.28 µg/L
22/47 SYR4 2012–2019
Lead
0.0080 mg/L 53%
of the EPA limit 0.0150 mg/L
14/14 LCR 2025
Fluoride
1192 µg/L 30%
of the EPA limit 4000 µg/L
worst single sample: 1330 µg/L
13/18 SYR4 2012–2018
Barium
34.8 µg/L 1.7%
of the EPA limit 2000 µg/L
worst single sample: 37 µg/L
12/18 SYR4 2012–2018
Chromium
3.45 µg/L 3.5%
of the EPA limit 100 µg/L
worst single sample: 4 µg/L
12/18 SYR4 2012–2018
Dichloroacetic Acid
4.954 µg/L
No EPA limit set
worst single sample: 5.34 µg/L
5/8 SYR4 2018–2019
Benzo(A)Pyrene
0.2490 µg/L 124%
of the EPA limit, at the 95th percentile of samples — 0.2000 µg/L
worst single sample: 0.2500 µg/L
2/37 SYR4 2012–2019
Cyanide
9 µg/L 4.5%
of the EPA limit 200 µg/L
1/18 SYR4 2012–2018
87 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,3,7,8-TCDD2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicAtrazineBhc-GammaBenzeneBeryllium, TotalChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDibromoacetic AcidDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNetfosaaNfdhaNmefosaaNitriteOxamylPfbaPfdaPfdoaPfeesaPfhpaPfhpsPFHXSPfmbaPfmpaPFNAPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroacetic AcidTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
STEVE GOHN, SUP
Phone
717-898-8231

Frequently asked questions about East Hempfield Water Auth

Is East Hempfield Water Auth tap water safe to drink?

EPA monitoring detected 21 contaminants in East Hempfield Water Auth's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in East Hempfield Water Auth's water?

EPA monitoring detected Nitrate, Copper, Lead, Dibromochloromethane, TTHM, and others. The full list with the level and data source for each is above.

How many people does East Hempfield Water Auth serve?

East Hempfield Water Auth reports serving 20,988 people in Pennsylvania, per its EPA record.

Has East Hempfield Water Auth had any water quality violations?

The EPA has 62 violations on file for East Hempfield Water Auth, of which 5 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.