Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2014-07-01 → 2014-07-31 |
| MCL | Health-based | Resolved | 2014-07-01 → 2014-07-31 |
| MCL | Health-based | Resolved | 2014-07-01 → 2014-07-31 |
| TT | Health-based | Resolved | 2012-04-01 → 2012-06-30 |
| TT | Health-based | Resolved | 2012-04-01 → 2012-06-30 |
| TT | Health-based | Resolved | 2012-04-01 → 2012-06-30 |
| TT | Health-based | Resolved | 2003-11-01 → 2003-11-30 |
| RPT | Monitoring | Resolved | 2025-05-11 |
| RPT | Monitoring | Resolved | 2025-05-11 |
| MR | Monitoring | Resolved | 2024-03-01 → 2024-03-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 7.0505 µg/L No EPA limit set
worst single sample: 8.39 µg/L | 122/128 | SYR4 | 2012–2019 |
| Chloroform | 73.465 µg/L No EPA limit set
worst single sample: 91.6 µg/L | 122/128 | SYR4 | 2012–2019 |
| TTHM | 80.795 µg/L 101% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 98.9 µg/L | 122/128 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 52.15 µg/L 87% of the EPA limit 60 µg/L
worst single sample: 66 µg/L | 118/128 | SYR4 | 2012–2019 |
| Copper | 137.5 µg/L 11% of the EPA limit 1300 µg/L
worst single sample: 620 µg/L | 94/94 | SYR4 | 2013–2019 |
| Lead | 21.72 µg/L 145% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 160 µg/L | 65/97 | SYR4 | 2013–2019 |
| Dichloroacetic Acid | 22.15 µg/L No EPA limit set
worst single sample: 25 µg/L | 20/20 | SYR4 | 2018–2019 |
| Trichloroacetic Acid | 47.25 µg/L No EPA limit set
worst single sample: 52 µg/L | 20/20 | SYR4 | 2018–2019 |
| Lead | 0.0060 mg/L 40% of the EPA limit 0.0150 mg/L | 16/16 | LCR | 2025 |
| Nitrate | 1220 µg/L 12% of the EPA limit 10000 µg/L | 16/54 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 1.655 µg/L No EPA limit set
worst single sample: 1.7 µg/L | 10/20 | SYR4 | 2018–2019 |
| Barium | 153.85 µg/L 7.7% of the EPA limit 2000 µg/L
worst single sample: 220 µg/L | 8/12 | SYR4 | 2012–2019 |
| Dibromochloromethane | 0.9100 µg/L No EPA limit set
worst single sample: 0.9800 µg/L | 8/128 | SYR4 | 2012–2019 |
| Fluoride | 892.5 µg/L 22% of the EPA limit 4000 µg/L
worst single sample: 959 µg/L | 8/12 | SYR4 | 2012–2019 |
| Nitrite | 846 µg/L 85% of the EPA limit 1000 µg/L
worst single sample: 860 µg/L | 2/27 | SYR4 | 2012–2019 |
| Di(2-ethylhexyl) Phthalate | 0.6320 µg/L 11% of the EPA limit 6 µg/L | 1/15 | SYR4 | 2012–2019 |
94 contaminants tested, none detected
Utility contact
Frequently asked questions about Boro of Waynesboro
Is Boro of Waynesboro tap water safe to drink?
EPA monitoring detected 16 contaminants in Boro of Waynesboro's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Boro of Waynesboro's water?
EPA monitoring detected Bromodichloromethane, Chloroform, TTHM, Total Haloacetic Acids (HAA5), Copper, and others. The full list with the level and data source for each is above.
How many people does Boro of Waynesboro serve?
Boro of Waynesboro reports serving 13,200 people in Pennsylvania, per its EPA record.
Has Boro of Waynesboro had any water quality violations?
The EPA has 501 violations on file for Boro of Waynesboro, of which 7 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.