← Pennsylvania

Tap water quality report

Veolia Water

EPA monitoring tested this supplier for 108 contaminants and detected 21. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

108
contaminants tested
21
detected
110,000
people served
13
health-based violations
Water source
Surface water
Ownership
Private
Counties served
Dauphin

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

13
health-based violations
138
violations on file
0
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2006-06-01 → 2006-06-30
TT Health-based Resolved 2006-06-01 → 2006-06-30
TT Health-based Resolved 2006-06-01 → 2006-06-30
TT Health-based Resolved 2006-06-01 → 2006-06-30
TT Health-based Resolved 2006-06-01 → 2006-06-30
TT Health-based Resolved 2004-09-01 → 2004-09-30
TT Health-based Resolved 2004-09-01 → 2004-09-30
TT Health-based Resolved 2004-09-01 → 2004-09-30
TT Health-based Resolved 2004-09-01 → 2004-09-30
TT Health-based Resolved 2004-09-01 → 2004-09-30

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
PFBS 0.0041 µg/L 3/8 2023
Pfhxa 0.0045 µg/L 2/8 2023
Pfpea 0.0054 µg/L 2/8 2023

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
TTHM
100.1 µg/L 125%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 130 µg/L
299/300 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
70.85 µg/L 118%
of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 95.1 µg/L
299/304 SYR4 2012–2019
Bromodichloromethane
19.03 µg/L
No EPA limit set
worst single sample: 119 µg/L
298/300 SYR4 2012–2019
Chloroform
84.82 µg/L
No EPA limit set
worst single sample: 105 µg/L
297/300 SYR4 2012–2019
Dibromochloromethane
6 µg/L
No EPA limit set
worst single sample: 11.3 µg/L
234/300 SYR4 2012–2019
Copper
116.3 µg/L 8.9%
of the EPA limit 1300 µg/L
worst single sample: 470 µg/L
154/155 SYR4 2013–2019
Trichloroacetic Acid
37.2 µg/L
No EPA limit set
worst single sample: 40.7 µg/L
51/51 SYR4 2018–2019
Dichloroacetic Acid
31.62 µg/L
No EPA limit set
worst single sample: 37 µg/L
50/51 SYR4 2018–2019
Monochloroacetic Acid
4.27 µg/L
No EPA limit set
worst single sample: 5.4 µg/L
36/51 SYR4 2018–2019
Nitrate
4058.5 µg/L 41%
of the EPA limit 10000 µg/L
worst single sample: 4090 µg/L
28/32 SYR4 2012–2019
Lead
9.08 µg/L 61%
of the EPA limit 15 µg/L
worst single sample: 31 µg/L
25/155 SYR4 2013–2019
Barium
42.25 µg/L 2.1%
of the EPA limit 2000 µg/L
worst single sample: 46 µg/L
16/16 SYR4 2012–2019
Bromoform
2.95 µg/L
No EPA limit set
worst single sample: 3.72 µg/L
11/300 SYR4 2012–2019
Lead
0.0021 mg/L 14%
of the EPA limit 0.0150 mg/L
11/11 LCR 2025
Monobromoacetic Acid
5.653 µg/L
No EPA limit set
worst single sample: 9.1 µg/L
10/51 SYR4 2018–2019
Dibromoacetic Acid
0.6494 µg/L
No EPA limit set
worst single sample: 0.6650 µg/L
5/51 SYR4 2018–2019
Atrazine
0.8400 µg/L 28%
of the EPA limit 3 µg/L
worst single sample: 0.8500 µg/L
3/17 SYR4 2014–2019
Hexachlorocyclopentadiene
0.2700 µg/L 0.5%
of the EPA limit 50 µg/L
1/15 SYR4 2014–2019
87 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumCombined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneFluorideGlyphosateHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideLassoMercuryMethoxychlorNetfosaaNfdhaNmefosaaNitriteOxamylPfbaPfdaPfdoaPfeesaPfhpaPfhpsPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
Sean Wolpert
Phone
717-561-1103

Frequently asked questions about Veolia Water

Is Veolia Water tap water safe to drink?

EPA monitoring detected 21 contaminants in Veolia Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Veolia Water's water?

EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Bromodichloromethane, Chloroform, Dibromochloromethane, and others. The full list with the level and data source for each is above.

How many people does Veolia Water serve?

Veolia Water reports serving 110,000 people in Pennsylvania, per its EPA record.

Has Veolia Water had any water quality violations?

The EPA has 138 violations on file for Veolia Water, of which 13 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.