Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2015-01-01 → 2015-03-31 |
| TT | Health-based | Resolved | 2015-01-01 → 2015-03-31 |
| TT | Health-based | Resolved | 2015-01-01 → 2015-03-31 |
| TT | Health-based | Resolved | 2015-01-01 → 2015-03-31 |
| TT | Health-based | Resolved | 2015-01-01 → 2015-03-31 |
| TT | Health-based | Resolved | 2015-01-01 → 2015-03-31 |
| TT | Health-based | Resolved | 2014-10-01 → 2014-12-31 |
| TT | Health-based | Resolved | 2014-10-01 → 2014-12-31 |
| TT | Health-based | Resolved | 2014-10-01 → 2014-12-31 |
| TT | Health-based | Resolved | 2014-10-01 → 2014-12-31 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 16.75 µg/L No EPA limit set
worst single sample: 18.1 µg/L | 47/47 | SYR4 | 2012–2019 |
| Chloroform | 37.68 µg/L No EPA limit set
worst single sample: 52.6 µg/L | 47/47 | SYR4 | 2012–2019 |
| Dibromochloromethane | 6.91 µg/L No EPA limit set
worst single sample: 8.6 µg/L | 47/47 | SYR4 | 2012–2019 |
| TTHM | 61.06 µg/L 76% of the EPA limit 80 µg/L
worst single sample: 75.3 µg/L | 44/44 | SYR4 | 2012–2019 |
| Nitrate | 3989 µg/L 40% of the EPA limit 10000 µg/L
worst single sample: 5300 µg/L | 40/40 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 80.2 µg/L 134% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 86 µg/L | 39/39 | SYR4 | 2012–2019 |
| Copper | 395 µg/L 30% of the EPA limit 1300 µg/L
worst single sample: 410 µg/L | 16/64 | SYR4 | 2013–2019 |
| Lead | 0.0020 mg/L 13% of the EPA limit 0.0150 mg/L | 10/10 | LCR | 2025 |
| Lead | 14.9 µg/L 99% of the EPA limit 15 µg/L
worst single sample: 17 µg/L | 7/64 | SYR4 | 2013–2019 |
| Dichloroacetic Acid | 14 µg/L No EPA limit set | 6/6 | SYR4 | 2017–2019 |
| Trichloroacetic Acid | 16 µg/L No EPA limit set
worst single sample: 17 µg/L | 6/6 | SYR4 | 2017–2019 |
| Bromoform | 0.7800 µg/L No EPA limit set
worst single sample: 0.8000 µg/L | 5/43 | SYR4 | 2012–2019 |
| Lithium | 21.8 µg/L No EPA limit set | 2/6 | UCMR-5 | 2023 |
| Combined Uranium | 1.21733 µg/L 4.1% of the EPA limit 30 µg/L | 1/2 | SYR4 | 2014–2019 |
89 contaminants tested, none detected
Utility contact
Frequently asked questions about New Oxford Munci Auth
Is New Oxford Munci Auth tap water safe to drink?
EPA monitoring detected 20 contaminants in New Oxford Munci Auth's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in New Oxford Munci Auth's water?
EPA monitoring detected Bromodichloromethane, Chloroform, Dibromochloromethane, TTHM, Nitrate, and others. The full list with the level and data source for each is above.
How many people does New Oxford Munci Auth serve?
New Oxford Munci Auth reports serving 3,963 people in Pennsylvania, per its EPA record.
Has New Oxford Munci Auth had any water quality violations?
The EPA has 508 violations on file for New Oxford Munci Auth, of which 27 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.