← Pennsylvania

Tap water quality report

New Oxford Munci Auth

EPA monitoring tested this supplier for 109 contaminants and detected 20. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

109
contaminants tested
20
detected
3,963
people served
27
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Adams

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

27
health-based violations
508
violations on file
0
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2015-01-01 → 2015-03-31
TT Health-based Resolved 2015-01-01 → 2015-03-31
TT Health-based Resolved 2015-01-01 → 2015-03-31
TT Health-based Resolved 2015-01-01 → 2015-03-31
TT Health-based Resolved 2015-01-01 → 2015-03-31
TT Health-based Resolved 2015-01-01 → 2015-03-31
TT Health-based Resolved 2014-10-01 → 2014-12-31
TT Health-based Resolved 2014-10-01 → 2014-12-31
TT Health-based Resolved 2014-10-01 → 2014-12-31
TT Health-based Resolved 2014-10-01 → 2014-12-31

PFAS detected

PFAS are industrial “forever chemicals”. These are the EPA's latest nationwide test results (2023–2025).
ContaminantMaxDetection ratePeriod
Pfhxa 0.0060 µg/L 3/6 2023
Pfpea 0.0096 µg/L 3/6 2023
Pfba 0.0281 µg/L 2/6 2023
PFBS 0.0053 µg/L 2/6 2023
PFOS 0.0048 µg/L 2/6 2023
PFOA 0.0043 µg/L 1/6 2023

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Bromodichloromethane
16.75 µg/L
No EPA limit set
worst single sample: 18.1 µg/L
47/47 SYR4 2012–2019
Chloroform
37.68 µg/L
No EPA limit set
worst single sample: 52.6 µg/L
47/47 SYR4 2012–2019
Dibromochloromethane
6.91 µg/L
No EPA limit set
worst single sample: 8.6 µg/L
47/47 SYR4 2012–2019
TTHM
61.06 µg/L 76%
of the EPA limit 80 µg/L
worst single sample: 75.3 µg/L
44/44 SYR4 2012–2019
Nitrate
3989 µg/L 40%
of the EPA limit 10000 µg/L
worst single sample: 5300 µg/L
40/40 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
80.2 µg/L 134%
of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 86 µg/L
39/39 SYR4 2012–2019
Copper
395 µg/L 30%
of the EPA limit 1300 µg/L
worst single sample: 410 µg/L
16/64 SYR4 2013–2019
Lead
0.0020 mg/L 13%
of the EPA limit 0.0150 mg/L
10/10 LCR 2025
Lead
14.9 µg/L 99%
of the EPA limit 15 µg/L
worst single sample: 17 µg/L
7/64 SYR4 2013–2019
Dichloroacetic Acid
14 µg/L
No EPA limit set
6/6 SYR4 2017–2019
Trichloroacetic Acid
16 µg/L
No EPA limit set
worst single sample: 17 µg/L
6/6 SYR4 2017–2019
Bromoform
0.7800 µg/L
No EPA limit set
worst single sample: 0.8000 µg/L
5/43 SYR4 2012–2019
Lithium
21.8 µg/L
No EPA limit set
2/6 UCMR-5 2023
Combined Uranium
1.21733 µg/L 4.1%
of the EPA limit 30 µg/L
1/2 SYR4 2014–2019
89 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS2,3,7,8-TCDD2,4,5-TP2,4-D4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaAntimony, TotalArsenicAtrazineBhc-GammaBariumBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDibromoacetic AcidDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneFluorideGlyphosateHexachlorobenzeneHfpo-DaHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNetfosaaNfdhaNmefosaaNitriteOxamylPfdaPfdoaPfeesaPfhpaPfhpsPFHXSPfmbaPfmpaPFNAPfpesPftaPftrdaPfunaPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
TOM BEAMER
Phone
717-624-2380

Frequently asked questions about New Oxford Munci Auth

Is New Oxford Munci Auth tap water safe to drink?

EPA monitoring detected 20 contaminants in New Oxford Munci Auth's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in New Oxford Munci Auth's water?

EPA monitoring detected Bromodichloromethane, Chloroform, Dibromochloromethane, TTHM, Nitrate, and others. The full list with the level and data source for each is above.

How many people does New Oxford Munci Auth serve?

New Oxford Munci Auth reports serving 3,963 people in Pennsylvania, per its EPA record.

Has New Oxford Munci Auth had any water quality violations?

The EPA has 508 violations on file for New Oxford Munci Auth, of which 27 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.