Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2007-09-01 → 2007-09-30 |
| MCL | Health-based | Resolved | 2007-09-01 → 2007-09-30 |
| MCL | Health-based | Resolved | 2007-09-01 → 2007-09-30 |
| MCL | Health-based | Resolved | 2005-04-01 → 2006-03-31 |
| MCL | Health-based | Resolved | 2005-04-01 → 2006-03-31 |
| MCL | Health-based | Resolved | 1999-07-01 → 1999-09-30 |
| MCL | Health-based | Resolved | 1999-07-01 → 1999-09-30 |
| MCL | Health-based | Resolved | 1999-07-01 → 1999-09-30 |
| MCL | Health-based | Resolved | 1999-07-01 → 1999-09-30 |
| TT | Health-based | Archived | 1993-04-01 → 1993-04-30 |
PFAS detected
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Chloroform | 51.7 µg/L No EPA limit set
worst single sample: 71.1 µg/L | 149/149 | SYR4 | 2012–2019 |
| Bromodichloromethane | 11.13 µg/L No EPA limit set
worst single sample: 15.2 µg/L | 148/149 | SYR4 | 2012–2019 |
| TTHM | 65.075 µg/L 81% of the EPA limit 80 µg/L
worst single sample: 86.8 µg/L | 148/149 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 37.175 µg/L 62% of the EPA limit 60 µg/L
worst single sample: 51.8 µg/L | 146/149 | SYR4 | 2012–2019 |
| Nitrate | 3947 µg/L 39% of the EPA limit 10000 µg/L
worst single sample: 4290 µg/L | 104/116 | SYR4 | 2012–2019 |
| Dibromochloromethane | 3.4 µg/L No EPA limit set
worst single sample: 4.3 µg/L | 91/149 | SYR4 | 2012–2019 |
| Copper | 517 µg/L 40% of the EPA limit 1300 µg/L
worst single sample: 1000 µg/L | 83/91 | SYR4 | 2013–2019 |
| Dichloroacetic Acid | 16.45 µg/L No EPA limit set
worst single sample: 18 µg/L | 32/32 | SYR4 | 2018–2019 |
| Trichloroacetic Acid | 17.45 µg/L No EPA limit set
worst single sample: 18 µg/L | 32/32 | SYR4 | 2018–2019 |
| Lead | 9.29 µg/L 62% of the EPA limit 15 µg/L
worst single sample: 23 µg/L | 24/91 | SYR4 | 2013–2019 |
| Barium | 152 µg/L 7.6% of the EPA limit 2000 µg/L
worst single sample: 200 µg/L | 17/26 | SYR4 | 2012–2019 |
| Lead | 0.0020 mg/L 13% of the EPA limit 0.0150 mg/L | 13/13 | LCR | 2025 |
| Arsenic | 16 µg/L 160% of the EPA limit, at the 95th percentile of samples — 10 µg/L
worst single sample: 19 µg/L | 11/32 | SYR4 | 2012–2019 |
| Lithium | 37.2 µg/L No EPA limit set | 11/16 | UCMR-5 | 2025 |
| Combined Uranium | 8.02365 µg/L 27% of the EPA limit 30 µg/L
worst single sample: 8.1503 µg/L | 6/10 | SYR4 | 2013–2017 |
| Selenium | 2.46 µg/L 4.9% of the EPA limit 50 µg/L
worst single sample: 2.5 µg/L | 5/26 | SYR4 | 2012–2019 |
| Bromoform | 2.85 µg/L No EPA limit set
worst single sample: 3.1 µg/L | 3/149 | SYR4 | 2012–2019 |
| Tetrachloroethylene | 0.8490 µg/L 17% of the EPA limit 5 µg/L
worst single sample: 0.8600 µg/L | 3/92 | SYR4 | 2012–2019 |
| Fluoride | 119 µg/L 3% of the EPA limit 4000 µg/L
worst single sample: 120 µg/L | 2/26 | SYR4 | 2012–2019 |
| Chromium | 2.6 µg/L 2.6% of the EPA limit 100 µg/L | 1/26 | SYR4 | 2012–2019 |
| Xylenes, Total | 1.1 µg/L 0% of the EPA limit 10000 µg/L | 1/91 | SYR4 | 2012–2019 |
84 contaminants tested, none detected
Utility contact
Frequently asked questions about Gettysburg Muni Auth
Is Gettysburg Muni Auth tap water safe to drink?
EPA monitoring detected 26 contaminants in Gettysburg Muni Auth's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Gettysburg Muni Auth's water?
EPA monitoring detected Chloroform, Bromodichloromethane, TTHM, Total Haloacetic Acids (HAA5), Nitrate, and others. The full list with the level and data source for each is above.
How many people does Gettysburg Muni Auth serve?
Gettysburg Muni Auth reports serving 12,425 people in Pennsylvania, per its EPA record.
Has Gettysburg Muni Auth had any water quality violations?
The EPA has 735 violations on file for Gettysburg Muni Auth, of which 10 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.