← Pennsylvania

Tap water quality report

Icmsa Cherrytree

EPA monitoring tested this supplier for 80 contaminants and detected 19. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

80
contaminants tested
19
detected
400
people served
271
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Indiana

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

271
health-based violations
718
violations on file
3
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2020-04-01 → 2020-06-30
MCL Health-based Resolved 2020-04-01 → 2020-06-30
MCL Health-based Resolved 2020-04-01 → 2020-06-30
MCL Health-based Resolved 2020-04-01 → 2020-06-30
MCL Health-based Archived 2020-01-01 → 2020-03-31
MCL Health-based Archived 2020-01-01 → 2020-03-31
MCL Health-based Archived 2020-01-01 → 2020-03-31
MCL Health-based Archived 2019-10-01 → 2019-12-31
MCL Health-based Archived 2019-10-01 → 2019-12-31
MCL Health-based Archived 2019-10-01 → 2019-12-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
2029 µg/L 156%
of the EPA limit, at the 95th percentile of samples — 1300 µg/L
worst single sample: 4860 µg/L
68/82 SYR4 2013–2019
Bromodichloromethane
14.67 µg/L
No EPA limit set
worst single sample: 26.4 µg/L
47/47 SYR4 2012–2019
Chloroform
111.751 µg/L
No EPA limit set
worst single sample: 685 µg/L
47/47 SYR4 2012–2019
TTHM
126.8 µg/L 159%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 713 µg/L
47/47 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
158.25 µg/L 264%
of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 795 µg/L
46/47 SYR4 2012–2019
Dibromochloromethane
2.967 µg/L
No EPA limit set
worst single sample: 4.4 µg/L
27/47 SYR4 2012–2019
Dichloroacetic Acid
32.9 µg/L
No EPA limit set
worst single sample: 34 µg/L
12/12 SYR4 2015–2019
Trichloroacetic Acid
35.985 µg/L
No EPA limit set
worst single sample: 39 µg/L
10/12 SYR4 2015–2019
Lead
4.94 µg/L 33%
of the EPA limit 15 µg/L
worst single sample: 5.5 µg/L
8/76 SYR4 2013–2019
Nitrate
1760 µg/L 18%
of the EPA limit 10000 µg/L
8/18 SYR4 2012–2019
Barium
74.3 µg/L 3.7%
of the EPA limit 2000 µg/L
worst single sample: 83 µg/L
7/8 SYR4 2012–2019
Monochloroacetic Acid
75.4 µg/L
No EPA limit set
worst single sample: 76 µg/L
7/12 SYR4 2015–2019
Dalapon
1.9075 µg/L 1%
of the EPA limit 200 µg/L
worst single sample: 2.02 µg/L
4/14 SYR4 2012–2019
Dibromoacetic Acid
1.46 µg/L
No EPA limit set
worst single sample: 1.5 µg/L
3/12 SYR4 2015–2019
Hexachlorocyclopentadiene
0.2900 µg/L 0.6%
of the EPA limit 50 µg/L
worst single sample: 0.3000 µg/L
3/13 SYR4 2012–2019
Lead
0.0163 mg/L 109%
above the EPA limit of 0.0150 mg/L
3/3 LCR 2025
Xylenes, Total
2952.12 µg/L 30%
of the EPA limit 10000 µg/L
worst single sample: 3280 µg/L
3/12 SYR4 2012–2019
Antimony, Total
0.4000 µg/L 6.7%
of the EPA limit 6 µg/L
1/8 SYR4 2012–2019
Ethylbenzene
610 µg/L 87%
of the EPA limit 700 µg/L
1/12 SYR4 2012–2019
61 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,3,7,8-TCDD2,4,5-TP2,4-DArsenicAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromoformChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumCombined UraniumDichloromethaneDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinFluorideGlyphosateHexachlorobenzeneHeptachlorHeptachlor EpoxideLassoMercuryMethoxychlorMonobromoacetic AcidNitriteOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl Chloridecis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
MARTIN MASCHAK
Phone
724-349-6640

Frequently asked questions about Icmsa Cherrytree

Is Icmsa Cherrytree tap water safe to drink?

EPA monitoring detected 19 contaminants in Icmsa Cherrytree's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Icmsa Cherrytree's water?

EPA monitoring detected Copper, Bromodichloromethane, Chloroform, TTHM, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.

How many people does Icmsa Cherrytree serve?

Icmsa Cherrytree reports serving 400 people in Pennsylvania, per its EPA record.

Has Icmsa Cherrytree had any water quality violations?

The EPA has 718 violations on file for Icmsa Cherrytree, of which 271 are health-based (a contaminant limit or required treatment was breached) and 3 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.