← Pennsylvania

Tap water quality report

Municipal Water Auth Adams Twp

EPA monitoring tested this supplier for 44 contaminants and detected 13. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

44
contaminants tested
13
detected
8,700
people served
8
health-based violations
Water source
SWP
Ownership
Local government
Counties served
Butler

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

8
health-based violations
115
violations on file
0
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2019-04-15
TT Health-based Resolved 2019-04-15
TT Health-based Resolved 2019-04-15
TT Health-based Resolved 2019-04-15
MCL Health-based Resolved 2007-07-01 → 2007-07-31
MCL Health-based Resolved 2007-07-01 → 2007-07-31
MCL Health-based Resolved 2007-07-01 → 2007-07-31
MCL Health-based Resolved 2007-07-01 → 2007-07-31
Other Monitoring Resolved 2024-06-11
Other Monitoring Resolved 2024-06-11

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
266.05 µg/L 20%
of the EPA limit 1300 µg/L
worst single sample: 314 µg/L
84/85 SYR4 2013–2019
Total Haloacetic Acids (HAA5)
24.62 µg/L 41%
of the EPA limit 60 µg/L
worst single sample: 29.4 µg/L
65/65 SYR4 2012–2019
Bromodichloromethane
26.4 µg/L
No EPA limit set
worst single sample: 32.8 µg/L
64/64 SYR4 2012–2019
Chloroform
48.97 µg/L
No EPA limit set
worst single sample: 60.6 µg/L
64/64 SYR4 2012–2019
Dibromochloromethane
19.82 µg/L
No EPA limit set
worst single sample: 28.5 µg/L
64/64 SYR4 2012–2019
TTHM
79.585 µg/L 99%
of the EPA limit 80 µg/L
worst single sample: 100 µg/L
64/64 SYR4 2012–2019
Bromoform
8.205 µg/L
No EPA limit set
worst single sample: 12 µg/L
39/64 SYR4 2012–2019
Trichloroacetic Acid
9.2 µg/L
No EPA limit set
worst single sample: 10 µg/L
17/17 SYR4 2015–2019
Dichloroacetic Acid
12.13 µg/L
No EPA limit set
worst single sample: 12.2 µg/L
15/17 SYR4 2015–2019
Dibromoacetic Acid
2.9 µg/L
No EPA limit set
worst single sample: 3 µg/L
11/17 SYR4 2015–2019
Lead
0.00059 mg/L 3.9%
of the EPA limit 0.0150 mg/L
7/7 LCR 2025
Monochloroacetic Acid
1.202 µg/L
No EPA limit set
worst single sample: 1.28 µg/L
7/17 SYR4 2015–2019
Lead
1.84 µg/L 12%
of the EPA limit 15 µg/L
worst single sample: 1.9 µg/L
4/60 SYR4 2013–2019
31 contaminants tested, none detected
11Cl-PF3OUdS4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaHfpo-DaMonobromoacetic AcidNetfosaaNfdhaNmefosaaPfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaLithium

Utility contact

Contact
MATTHEW CRANMER
Phone
724-625-3166

Frequently asked questions about Municipal Water Auth Adams Twp

Is Municipal Water Auth Adams Twp tap water safe to drink?

EPA monitoring detected 13 contaminants in Municipal Water Auth Adams Twp's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Municipal Water Auth Adams Twp's water?

EPA monitoring detected Copper, Total Haloacetic Acids (HAA5), Bromodichloromethane, Chloroform, Dibromochloromethane, and others. The full list with the level and data source for each is above.

How many people does Municipal Water Auth Adams Twp serve?

Municipal Water Auth Adams Twp reports serving 8,700 people in Pennsylvania, per its EPA record.

Has Municipal Water Auth Adams Twp had any water quality violations?

The EPA has 115 violations on file for Municipal Water Auth Adams Twp, of which 8 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.