← Pennsylvania

Tap water quality report

Selinsgrove Center

EPA monitoring tested this supplier for 80 contaminants and detected 14. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

80
contaminants tested
14
detected
1,000
people served
8
health-based violations
Water source
Ground water under surface influence
Ownership
State government
Counties served
Snyder

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

8
health-based violations
630
violations on file
3
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2021-01-01
TT Health-based Resolved 2021-01-01
TT Health-based Resolved 2021-01-01
TT Health-based Resolved 2021-01-01
TT Health-based Resolved 2017-06-01 → 2017-06-30
TT Health-based Resolved 2017-06-01 → 2017-06-30
TT Health-based Resolved 2017-06-01 → 2017-06-30
TT Health-based Resolved 2017-06-01 → 2017-06-30
MR Monitoring Resolved 2026-03-01 → 2026-03-31
MR Monitoring Resolved 2026-03-01 → 2026-03-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
6720 µg/L 67%
of the EPA limit 10000 µg/L
worst single sample: 6880 µg/L
88/88 SYR4 2012–2019
Copper
120 µg/L 9.2%
of the EPA limit 1300 µg/L
worst single sample: 330 µg/L
50/50 SYR4 2012–2019
Lead
13.085 µg/L 87%
of the EPA limit 15 µg/L
worst single sample: 31 µg/L
28/50 SYR4 2012–2019
Bromodichloromethane
5.9575 µg/L
No EPA limit set
worst single sample: 6.18 µg/L
24/28 SYR4 2012–2019
Chloroform
11.23 µg/L
No EPA limit set
worst single sample: 12.1 µg/L
24/28 SYR4 2012–2019
TTHM
20.29 µg/L 25%
of the EPA limit 80 µg/L
worst single sample: 23.1 µg/L
23/28 SYR4 2012–2019
Dibromochloromethane
3.092 µg/L
No EPA limit set
worst single sample: 3.33 µg/L
18/28 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
8.665 µg/L 14%
of the EPA limit 60 µg/L
worst single sample: 9.58 µg/L
7/28 SYR4 2012–2019
Dichloroacetic Acid
7.354 µg/L
No EPA limit set
worst single sample: 7.56 µg/L
5/24 SYR4 2014–2019
Lead
0.0200 mg/L 133%
above the EPA limit of 0.0150 mg/L
4/4 LCR 2003
Trichloroacetic Acid
2.1715 µg/L
No EPA limit set
worst single sample: 2.2 µg/L
4/24 SYR4 2014–2019
Barium
32.73 µg/L 1.6%
of the EPA limit 2000 µg/L
worst single sample: 34 µg/L
2/6 SYR4 2012–2018
Beryllium, Total
2.13 µg/L 53%
of the EPA limit 4 µg/L
1/6 SYR4 2012–2018
Bromoform
2.2 µg/L
No EPA limit set
1/28 SYR4 2012–2019
66 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,3,7,8-TCDD2,4,5-TP2,4-DAntimony, TotalArsenicAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumCombined UraniumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDibromoacetic AcidDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneFluorideGlyphosateHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNitriteOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
AMY FREDERICK
Phone
570-372-5747

Frequently asked questions about Selinsgrove Center

Is Selinsgrove Center tap water safe to drink?

EPA monitoring detected 14 contaminants in Selinsgrove Center's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Selinsgrove Center's water?

EPA monitoring detected Nitrate, Copper, Lead, Bromodichloromethane, Chloroform, and others. The full list with the level and data source for each is above.

How many people does Selinsgrove Center serve?

Selinsgrove Center reports serving 1,000 people in Pennsylvania, per its EPA record.

Has Selinsgrove Center had any water quality violations?

The EPA has 630 violations on file for Selinsgrove Center, of which 8 are health-based (a contaminant limit or required treatment was breached) and 3 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.