Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2014-07-01 → 2014-07-31 |
| MCL | Health-based | Resolved | 2014-07-01 → 2014-07-31 |
| MCL | Health-based | Resolved | 2014-07-01 → 2014-07-31 |
| MCL | Health-based | Resolved | 2014-07-01 → 2014-07-31 |
| TT | Health-based | Resolved | 2013-12-01 → 2013-12-31 |
| TT | Health-based | Resolved | 2013-12-01 → 2013-12-31 |
| TT | Health-based | Resolved | 2013-12-01 → 2013-12-31 |
| TT | Health-based | Resolved | 2013-12-01 → 2013-12-31 |
| MCL | Health-based | Resolved | 2013-10-01 → 2013-10-31 |
| MCL | Health-based | Resolved | 2013-10-01 → 2013-10-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 1600 µg/L 16% of the EPA limit 10000 µg/L | 10/14 | SYR4 | 2012–2019 |
| Copper | 67.7 µg/L 5.2% of the EPA limit 1300 µg/L
worst single sample: 80 µg/L | 6/15 | SYR4 | 2013–2019 |
| Lead | 4.584 µg/L 31% of the EPA limit 15 µg/L
worst single sample: 4.7 µg/L | 3/15 | SYR4 | 2013–2019 |
| Arsenic | 5.555 µg/L 56% of the EPA limit 10 µg/L
worst single sample: 5.6 µg/L | 2/3 | SYR4 | 2012–2018 |
| Barium | 7.61 µg/L 0.4% of the EPA limit 2000 µg/L
worst single sample: 7.7 µg/L | 2/3 | SYR4 | 2012–2018 |
| Chloroform | 24.1 µg/L No EPA limit set | 2/2 | SYR4 | 2018 |
| Chromium | 2.165 µg/L 2.2% of the EPA limit 100 µg/L
worst single sample: 2.2 µg/L | 2/3 | SYR4 | 2012–2018 |
| Combined Uranium | 2.7866 µg/L 9.3% of the EPA limit 30 µg/L
worst single sample: 2.79524 µg/L | 2/2 | SYR4 | 2013–2019 |
| TTHM | 40.36 µg/L 50% of the EPA limit 80 µg/L
worst single sample: 42.2 µg/L | 2/2 | SYR4 | 2016–2018 |
| Bromodichloromethane | 11.2 µg/L No EPA limit set | 1/1 | SYR4 | 2018 |
| Bromoform | 1.3 µg/L No EPA limit set | 1/1 | SYR4 | 2018 |
| Dibromochloromethane | 5.6 µg/L No EPA limit set | 1/1 | SYR4 | 2018 |
| Dichloroacetic Acid | 6.9 µg/L No EPA limit set | 1/1 | SYR4 | 2018 |
| Lead | 0.0160 mg/L 107% above the EPA limit of 0.0150 mg/L | 1/1 | LCR | 1993 |
| Total Haloacetic Acids (HAA5) | 8.3 µg/L 14% of the EPA limit 60 µg/L | 1/2 | SYR4 | 2016–2018 |
| Trichloroacetic Acid | 1.4 µg/L No EPA limit set | 1/1 | SYR4 | 2018 |
62 contaminants tested, none detected
Utility contact
Frequently asked questions about Aqua Pa East Cameron
Is Aqua Pa East Cameron tap water safe to drink?
EPA monitoring detected 16 contaminants in Aqua Pa East Cameron's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Aqua Pa East Cameron's water?
EPA monitoring detected Nitrate, Copper, Lead, Arsenic, Barium, and others. The full list with the level and data source for each is above.
How many people does Aqua Pa East Cameron serve?
Aqua Pa East Cameron reports serving 200 people in Pennsylvania, per its EPA record.
Has Aqua Pa East Cameron had any water quality violations?
The EPA has 556 violations on file for Aqua Pa East Cameron, of which 30 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.