Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 1992-01-01 → 1997-02-04 |
| TT | Health-based | Resolved | 1992-01-01 → 1997-02-04 |
| TT | Health-based | Resolved | 1992-01-01 → 1997-02-04 |
| MCL | Health-based | Resolved | 1990-01-30 → 1990-02-28 |
| MCL | Health-based | Resolved | 1990-01-30 → 1990-02-28 |
| MCL | Health-based | Resolved | 1990-01-30 → 1990-02-28 |
| MCL | Health-based | Archived | 1984-05-16 → 1984-07-15 |
| MCL | Health-based | Archived | 1984-05-16 → 1984-07-15 |
| MCL | Health-based | Archived | 1984-05-16 → 1984-07-15 |
| MCL | Health-based | Archived | 1984-05-16 → 1984-07-15 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 615.2 µg/L 47% of the EPA limit 1300 µg/L
worst single sample: 725 µg/L | 30/30 | SYR4 | 2013–2019 |
| Chloroform | 17.67 µg/L No EPA limit set
worst single sample: 18 µg/L | 12/12 | SYR4 | 2012–2019 |
| Lead | 24.25 µg/L 162% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 29.2 µg/L | 11/30 | SYR4 | 2013–2019 |
| Bromodichloromethane | 5.521 µg/L No EPA limit set
worst single sample: 5.62 µg/L | 10/11 | SYR4 | 2012–2019 |
| TTHM | 24.715 µg/L 31% of the EPA limit 80 µg/L
worst single sample: 25.1 µg/L | 8/8 | SYR4 | 2012–2019 |
| Dibromochloromethane | 1.889 µg/L No EPA limit set
worst single sample: 1.97 µg/L | 7/9 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 7.1425 µg/L 12% of the EPA limit 60 µg/L
worst single sample: 7.21 µg/L | 6/8 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 5 µg/L No EPA limit set | 3/3 | SYR4 | 2017–2019 |
| Trichloroacetic Acid | 2.9 µg/L No EPA limit set
worst single sample: 3 µg/L | 3/3 | SYR4 | 2017–2019 |
| Barium | 61.83 µg/L 3.1% of the EPA limit 2000 µg/L
worst single sample: 62.6 µg/L | 2/3 | SYR4 | 2012–2018 |
| Combined Uranium | 0.2596 µg/L 0.9% of the EPA limit 30 µg/L | 1/1 | SYR4 | 2012 |
| Lead | 0.0400 mg/L 267% above the EPA limit of 0.0150 mg/L | 1/1 | LCR | 1995 |
| Mercury | 0.0490 µg/L 2.5% of the EPA limit 2 µg/L | 1/3 | SYR4 | 2012–2018 |
| Selenium | 0.2200 µg/L 0.4% of the EPA limit 50 µg/L | 1/3 | SYR4 | 2012–2018 |
66 contaminants tested, none detected
Utility contact
Frequently asked questions about Scma-Tremont
Is Scma-Tremont tap water safe to drink?
EPA monitoring detected 14 contaminants in Scma-Tremont's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Scma-Tremont's water?
EPA monitoring detected Copper, Chloroform, Lead, Bromodichloromethane, TTHM, and others. The full list with the level and data source for each is above.
How many people does Scma-Tremont serve?
Scma-Tremont reports serving 2,515 people in Pennsylvania, per its EPA record.
Has Scma-Tremont had any water quality violations?
The EPA has 164 violations on file for Scma-Tremont, of which 10 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.